Plan Review Details - Permit 04090888
| Plan Review Stops For Permit 04090888 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-18 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-18 |
Time |
08:55 |
Sent To |
M |
|
| Notes |
| 2005-04-18 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-20 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-20 |
Time |
17:05 |
Sent To |
M |
|
| Notes |
| 2004-10-20 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-04 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-04 |
Time |
09:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-22 |
Time |
07:51 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-04-22 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2005-04-22 00:00:00 | PROVISO: | | | FAN SHUTDOWN REQUIRED WITH NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS.2001 FBC/M 606.2.1 & 606.4.1 #2. | | | | | | PLEASE NOTE OUTSIDE AIR LOCATED A | | | MINIMUM OF 10 FT FROM NOXIOUS | | | CONTAMINANT I.E., STREETS, ALLEYS, | | | PARKING LOTS, PLUMBING OR EXHAUST VENTS. | | | 2001 FBC/M 401.5.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-26 |
Time |
13:24 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-10-26 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2004-10-26 00:00:00 | PROVISO: | | | OUTSIDE AIR SHALL BE LOCATED A MINIUM OF | | | 10 FT FROM HAZARDOUS OR NOXIOUS | | | CONTAMINANT I.E., STREETS, ALLEYS, | | | LOADING DOCKS, PARKING LOTS, EXHAUST | | | VENTS, ETC. (2001 FBC(M) 401.5.1). |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-20 |
Time |
17:06 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-10-05 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | DENIED: | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) 403.3.INDICATE | | | FRESH AIR INTAKE, DUCT SIZE AND MATERIAL | | | ON PLAN. | | | | | | PROVIDE SUBMITTAL ON THE CONDESING UNIT | | | STANDS.PLEASE NOTE, PER 2001 FBC(M) | | | 306.5 PERMANENT MEANS OF ACCESS REQUIRED | | | WHERE ROOF HEIGHT EXCEEDS 16 FT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |