Plan Review Details - Permit 04090888
Plan Review Stops For Permit 04090888
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 08:55 Sent To M
Notes
2005-04-18 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:06 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 17:05 Sent To M
Notes
2004-10-20 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:16 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 09:16 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-04-22 Cont ID  
Sent By pkrauss Date 2005-04-22 Time 07:51 Rev Time 0.35
Received By pkrauss Date 2005-04-22 Time 07:51 Sent To  
Notes
2005-04-22 00:00:00PROVISO:
 FAN SHUTDOWN REQUIRED WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS.2001 FBC/M 606.2.1 & 606.4.1 #2.
  
 PLEASE NOTE OUTSIDE AIR LOCATED A
 MINIMUM OF 10 FT FROM NOXIOUS
 CONTAMINANT I.E., STREETS, ALLEYS,
 PARKING LOTS, PLUMBING OR EXHAUST VENTS.
 2001 FBC/M 401.5.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-26 Cont ID  
Sent By pkrauss Date 2004-10-26 Time 13:24 Rev Time 0.40
Received By pkrauss Date 2004-10-26 Time 13:15 Sent To  
Notes
2004-10-26 00:00:00PROVISO:
 OUTSIDE AIR SHALL BE LOCATED A MINIUM OF
 10 FT FROM HAZARDOUS OR NOXIOUS
 CONTAMINANT I.E., STREETS, ALLEYS,
 LOADING DOCKS, PARKING LOTS, EXHAUST
 VENTS, ETC. (2001 FBC(M) 401.5.1).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:06 Rev Time 0.40
Received By pkrauss Date 2004-10-05 Time 08:39 Sent To  
Notes
2004-10-05 00:00:00DENIED:
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) 403.3.INDICATE
 FRESH AIR INTAKE, DUCT SIZE AND MATERIAL
 ON PLAN.
  
 PROVIDE SUBMITTAL ON THE CONDESING UNIT
 STANDS.PLEASE NOTE, PER 2001 FBC(M)
 306.5 PERMANENT MEANS OF ACCESS REQUIRED
 WHERE ROOF HEIGHT EXCEEDS 16 FT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.