Plan Review Details - Permit 04090827
Plan Review Stops For Permit 04090827
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-18 Cont ID  
Sent By nmccray Date 2004-10-18 Time 10:59 Rev Time 0.00
Received By nmccray Date 2004-10-18 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:24 Rev Time 0.00
Received By nmccray Date 2004-10-07 Time 11:09 Sent To  
Notes
2004-10-07 00:00:00************DENIED**********************
  
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 AND LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL OF APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 3) THE FIRE ALARM SYSTEM SHALL BE
 CLASS "A" OR FULLY ADDRESSABLE.
  
 4) THE WEST PALM BEACH FIRE MARSHAL
 REQUIRES DUCT DETECTORS TO ACTIVATE A
 GENERAL FIRE ALARM NOT A SUPERVISORY.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-18 Cont ID  
Sent By ptjomsto Date 2004-10-18 Time 10:49 Rev Time 0.00
Received By ptjomsto Date 2004-10-18 Time 10:48 Sent To  
Notes
2004-10-18 00:00:001ST RESUB GIVEN TO NATE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:24 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 09:24 Sent To FIRE
Notes
***NONE***