Plan Review Details - Permit 04090795
Plan Review Stops For Permit 04090795
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-09-07 Cont ID  
Sent By jgomez Date 2006-09-07 Time 16:33 Rev Time 0.50
Received By jgomez Date 2006-09-07 Time 16:33 Sent To  
Notes
2006-09-07 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENTRY DOORS PRODUCT APPROVAL PACKAGE
 SUBMITTED NEED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT APPLICATION AS AGREED ON
 PROVISO DATED 4/18/05. SEE ATTACHED
 COPY. AGREEMENT WITH CONTRACTOR WAS TO
 SEPARATE ENTRY DOORS FROM MAIN PERMIT TO
 ALLOW ISSUANCE OF BUILDING PERMIT AND
 ALLOW TIME FOR ENTRY DOORS PRODUCT
 APPROVAL PACKAGE.
  
 2- PACKAGE SUBMITTED IS FOR ANOTHER
 PROJECT. PACKAGE SUBMITTED IS FOR PERMIT
 #05030779 WHICH CORRESPONDS TO HOUSE
 LOCATED AT 6050 OLIVE AVE.
  
 3- MAKE SURE APPLICATION FOR SITE
 SPECIFIC DOORS IS FILLEDCORRECTLY AND
 IN ITS ENTIRETY.
  
 4- ENGINEER WILL NEED TO PROVIDE
 FABRICATION AND INSTALLATION
 CERTIFICATION FOR THIS ONE OF A KIND
 DOOR.
 ***NOTE:
 MR. ROBERT BROWN, LICENSE AND PERMIT
 SERVICES MANAGER, IS THE PERSON WHO WILL
 REVIEW THE LOCAL PRODUCT APPROVAL
 APPLICATION. ENGINEER TO CONTACT MR.
 BROWN AT (561)805-6652 TO COORDINATE
 LOCAL PRODUCT APPROVAL PROCESS AND MAKE
 SURE ALL REQUIRED INFORMATION IS
 PROVIDED.
  
 5- STORM SHUTTERS FOR DOOR: NEED TO
 PROVIDE COMPLETE INSTALLATION SPECS FOR
 DOOR GLASS PROTECTION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-08-22 Cont ID  
Sent By jgomez Date 2006-08-22 Time 11:26 Rev Time 0.50
Received By jgomez Date 2006-08-22 Time 11:26 Sent To M
Notes
2006-08-22 00:00:00RE-STAMPING PRODUCT APPROVALS.
 SENT TO MECH. FOR RE-STAMPING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-08-14 Cont ID  
Sent By jgomez Date 2006-08-14 Time 10:21 Rev Time 0.40
Received By jgomez Date 2006-08-14 Time 10:21 Sent To  
Notes
2006-08-14 00:00:00POLYFOAM PRODUCT APPROVAL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-06-01 Cont ID  
Sent By jgomez Date 2006-06-01 Time 10:17 Rev Time 0.50
Received By jgomez Date 2006-06-01 Time 10:17 Sent To PC
Notes
2006-06-01 00:00:00REVISION: CONCRETE SLAB AT REAR LOGGIA.
 PLANS UNDER "S".

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-03 Cont ID  
Sent By jgomez Date 2005-08-03 Time 10:07 Rev Time 0.50
Received By jgomez Date 2005-08-03 Time 10:07 Sent To M
Notes
2005-08-03 00:00:00BUILDING REVIEW REMAINDER:
 1- CONTRACTOR TO APPLY FOR SEPARATE
 PERMIT FOR ENTRY DOORS AS AGREED ON
 PROVISO DATED 5-2-05. AVOID DELAYS OR
 CONFLICTS BY APPLYING FOR THIS PERMIT
 PRIOR TO DOORS INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-02 Cont ID  
Sent By jgomez Date 2005-05-02 Time 11:11 Rev Time 0.33
Received By jgomez Date 2005-05-02 Time 11:11 Sent To PC
Notes
2005-05-02 00:00:00REMAINDER:
 NEED TO APPLY FOR SEPARATE PERMIT FOR
 ENTRY DOORS AS AGREED ON. PROVIDE
 COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID DELAY OR
 CONFLICTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-18 Cont ID  
Sent By jgomez Date 2005-04-18 Time 12:03 Rev Time 2.00
Received By jgomez Date 2005-04-18 Time 12:03 Sent To E
Notes
2005-04-18 00:00:00BUILDING REVIEW PROVISO:
  
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ENTRY DOORS UNDER A
 SEPARATE PERMIT. SEE PLANS FOR SIZE AND
 TYPE OF DOOR.
  
 2- PROVIDE SOIL TEST REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-16 Cont ID  
Sent By jgomez Date 2005-03-16 Time 16:45 Rev Time 2.00
Received By jgomez Date 2005-03-16 Time 16:43 Sent To E
Notes
2005-03-16 00:00:00SECOND CHECKLIST:
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEE SEC. 104.2.1.1 CITY
 AMENDEMNTS TO FBC 2001. IT'S NOT THE
 CONTRACTOR RESPONSIBILITY. THE
 CONTRACTOR'S RESPONSIBILITY IS TO
 PROVIDE PRODUCT APPROVAL THAT MEETS THAT
 CRITERIA.
  
 2- SOMEBODY CROSSED OUT THE ELEVATOR
 FROM ALL PLANS AND DETAILS. IF ELEVATOR
 IS NOT TO BE BUILT, THEN REVISE ORIGINAL
 PLANS ACCORDINGLY.
  
 3- RULE 9B-72 OFFERS TWO OPTIONS FOR
 PRODUCT APPROVAL: FLORIDA PRODUCT
 APPROVAL OR LOCAL PRODUCT APPROVAL. DADE
 COUNTY ALONE IS NOT AN OFFICIAL FLORIDA
 PRODUCT APPROVAL. MANUFACTURER NEEDS TO
 APPLY FOR FLORIDA PRODUCT APPROVAL TO
 THE FLORIDA BUILDING COMMISSION.
 OTHERWISE, MANUFACTURER NEEDS TO APPLY
 FOR LOCAL PRODUCT APPROVAL WITH THE CITY
 OF WEST PALM BEACH. SEE
 WWW.FLORIDABUILDING.ORG FOR ADDITIONAL
 INFORMATION AND REQUIRMENTS.
 CONSTRUCTION GLASS INDUSTRIES CORP.
 NEEDS TO APPLY FOR FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:
 A) FIXED WINDOWS AS SHOWN ON PLANS.
 B) CASEMENT WINDOWS.
 C) FRENCH DOORS.
 D) DOOR/WINDOW MULLIONS AND CLEARLY
 INDICATE MULLION SIZE AND ALL FASTENERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
 E) ENTRY DOORS WITH SIZE AS SHOWN ON
 PLANS.
  
 4- PROVIDE COMPLETE LISTING AND SPECS
 FOR BBQ.
 **NOTE: BBQ'S ARE DESIGNED FOR OUTDOOR
 USE ONLY. SEE INSTALLATION LIMITATIONS
 SPECIFIED BY MANUFACTURER. PROVIDE
 MANUFACTURER SPECS ALLOWING INSTALLATION
 OF BBQ IN PORCH.
  
 5- STILL OWES $3709.54 FOR UPDATE VALUE
 AND RADON FEES.
 **NOTE: RE-SUBMITTAL FEES WILL APPLY FOR
 NEXT SUBMITTAL.
  
 6- UPDATE REFERENCE STANDARDS SHOWN ON
 PAGE A-1. ACI EDITION TO BE USED IS 02
 NOT 99. SEE CHAPTER 35 (YELLOW ERRATA)
 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By pkrauss Date 2005-03-14 Time 16:50 Rev Time 0.00
Received By jgomez Date 2004-11-23 Time 16:41 Sent To PC
Notes
2004-11-23 00:00:00CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK PAID
 RECEIPT AND STAMPED DRAWINGS.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3-ENTRY DOOR DOESN'T COMPLY WITH TABLE
 1004 FBC 2001. NEED 32" MIN. CLEAR
 OPENING WHEN ONE LEAF IS OPEN. REVISE.
  
 4-BEDROOM IN GUEST ROOM TO HAVE DOOR
 THAT PROVIDES 29" CLEAR OPENING. SECTION
 11-11 OF FBC 2001 CHAPTER 11.
  
 5-GUEST BEDROOM WINDOW DOESN'T COMPLY
 WITH SEC. 1005.4.4 FBC 2001. MULLION
 DOESN'T ALLOW THE 20" MIN. CLEAR
 OPENING. REVISE AS REQUIRED.
 **SAME COMMENT APPLY FOR DEN ROOM. (IF
 USING THE ROOM FOR SLEEPING. OTHERWISE,
 CLEARLY INDICATE UNDER THE DEN THAT ROOM
 CAN NOT BE USED FOR SLEEPING PURPOSES.
  
 6-ELEVATIONS AND FLOOR PLANS DON'T
 MATCH. SEE NUMBER AND LOCATION OF
 FIREPLACES AND REVISE/CLARIFY AS REQ'D.
  
 7-PROVIDE ATTIC ACCES AT FAMILY ROOM
 WING. SEC. 2309.6
  
 8-UPDATE CONNECTOR SCHEDULE. SEE CURRENT
 SIMPSON CATALOGUE AND REVISE TYPE AND
 NUMBER OF FASTENERS TO MATCH ENGINERED
 PUBLISHED VALUES. SEE COMMENTS ON PLAN.
  
 9-PROVIDE ONLY DETAILS THAT APPLY TO
 THIS PROJECT TO EXPEDITE THE REVIEW.
  
 10-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 11-PROVIDE COMPLETE DRAWINGS AND SPECS
 FOR ELEVATOR OR APPLY FOR A SEPARATE
 PERMIT. INCLUDING ELEVATOR MACHINE
 ROOM.
  
 12-PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR: A) TRUSS CONNECTORS USED.
 B) CASEMENT WINDOWS.
 C) WINDOW/DOOR MULLIONS: CLEARLY SPECIFY
 MULLION SIZE AND FASTENERS TO BE USED.
 D) ARCHED WINDOWS.
 E) FRENCH DOORS.
 F) GARAGE SIDE DOOR.
 G) COMPLETE PACKAGE FOR FIREPLACE LISTED
 TO BE USED OUTDOORS.
 H) BBQ UL LISTING AND SPECS.
  
 13-OWES $3,709.54 FOR UPDATED VALUE AND
 BALANCE DUE AT TIME OF APPLICATION.
  
 14-UPDATE REFERENCE STANDARDS SHOWN ON
 PAGE A-1. SEE COMMENTS AND CHAPTER 35 OF
 FBC 2001 FOR CURRENT EDITION TO BE
 USED.
  
 15-SHEET A-5: "D" CONNECTOR DOESN'T
 RESIST THE UPLIFT CALCULATED ON PLAN.
 SEE COMMENTS ON PLAN & REVISE AS REQ'D.
 ** SAME APPLIES TO SHEET A-6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-22 Cont ID  
Sent By btrobaug Date 2006-03-22 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2006-03-21 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-06-27 Cont ID  
Sent By dpalmer Date 2005-06-27 Time 07:57 Rev Time 0.10
Received By dpalmer Date 2005-06-27 Time 07:57 Sent To  
Notes
2005-06-27 00:00:00REVISED RISER ONLY.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2005-05-11 Cont ID  
Sent By dpalmer Date 2005-05-11 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2005-05-11 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-20 Cont ID  
Sent By btrobaug Date 2005-04-20 Time 11:37 Rev Time 0.50
Received By btrobaug Date 2005-04-20 Time 10:55 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-17 Cont ID  
Sent By btrobaug Date 2005-03-17 Time 15:52 Rev Time 0.50
Received By btrobaug Date 2005-03-17 Time 15:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By btrobaug Date 2004-10-20 Time 15:38 Rev Time 0.50
Received By btrobaug Date 2004-10-20 Time 11:38 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 11:07 Sent To B
Notes
2006-09-05 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 14:51 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 14:51 Sent To B
Notes
2006-08-18 00:00:00TO "JGOMEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 08:16 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 08:16 Sent To B
Notes
2006-05-26 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 17:44 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 17:44 Sent To E
Notes
2006-03-16 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 14:10 Sent To B
Notes
2005-08-02 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 14:44 Sent To E
Notes
2005-06-21 00:00:00TO "DPALMER"DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 11:38 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 11:38 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-08 Cont ID  
Sent By adarroug Date 2005-04-08 Time 14:25 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 14:25 Sent To B
Notes
2005-04-08 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-04 Time 13:21 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 13:21 Sent To Z
Notes
2005-04-04 00:00:00TO "Z"BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 13:47 Sent To M
Notes
2005-02-28 00:00:00TO PKRAUSS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 11:54 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 11:54 Sent To Z
Notes
2005-02-25 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-23 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:40 Rev Time 0.00
Received By jgomez Date 2004-10-04 Time 11:11 Sent To PC
Notes
2004-10-18 00:00:00TO SFD RACK/E
2004-10-04 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-04 Cont ID  
Sent By prafter Date 2005-08-04 Time 08:31 Rev Time 0.50
Received By prafter Date 2005-08-04 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-14 Cont ID  
Sent By pkrauss Date 2005-03-14 Time 16:26 Rev Time 1.40
Received By pkrauss Date 2005-03-14 Time 15:36 Sent To B
Notes
2005-03-14 00:00:00PROVISO:
 MECHANICAL PLANS ARE CODE COMPLIANT &
 APPROVED.
  
 SUBMITTAL FOR THE VENTLESS FIRE PLACE IS
 STILL UNDER SCRUTINY.PER THE
 MANUFACTURER'S SPECIFICATIONS, WHEN THE
 APPLIANCE IS INSTALLATED IN BUILDINGS
 CONSIDERED "UNUSUALLY TIGHT
 CONSTRUCTION" ADDITIONAL FRESH AIR MUST
 BE PROVIDED.PLANS DO NOT HAVE ANY
 CALCUALTIONS FOR COMBUSTION AIR, WHETHER
 IT WILL BE REQUIRED OR NOT.PLANS DO
 NOT INDICATE WHICH MODEL IS TO BE
 INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By kstevens Date 2004-10-21 Time 09:53 Rev Time 1.00
Received By drunnels Date 2004-11-18 Time 13:30 Sent To P
Notes
2004-11-18 00:00:00R/A IS REQUIED OUT OF DEN.
  
 MUST COMPLY WITH2001 FBC MECH. 601.4
 .
  
 PAT RAFTER805 6719

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-26 Cont ID  
Sent By kstevens Date 2005-04-26 Time 14:47 Rev Time 1.00
Received By kstevens Date 2005-04-26 Time 14:47 Sent To  
Notes
2005-04-26 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED - SHOWER MISSING IN
 HER MASTER BATH - TUB MISLABELED AS
 SHOWER IN BATH #1

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-21 Cont ID  
Sent By gsalfeld Date 2005-03-21 Time 10:18 Rev Time 1.00
Received By gsalfeld Date 2005-03-21 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-21 Cont ID  
Sent By kstevens Date 2004-10-21 Time 09:53 Rev Time 0.00
Received By jgomez Date 2005-04-18 Time 10:51 Sent To M
Notes
2004-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT M-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) W/C IN THE POWDER ROOM IS NOT VENTED
 SECTION 901.2.1
 B) CABANA BATH SHOWN ON THE FLOOR PLAN
 IS NOT SHOWN ON THE RISER DIAGRAM. SECT-
 ION 104.2.1
 C) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. ALSO A CLEANOUT IS REQUIRED
 ON THE WASH MACHINE STACK MINIMUM 4'
 ABOVE THE FLOOR. SECTIONS 1002.1, 802.4,
 AND 708.10
 D) SHOW ALL PIPES SIZES ON THE SANT.
 RISER DIAGRAM. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-04-07 Cont ID  
Sent By mmclean Date 2005-04-07 Time 16:55 Rev Time 0.00
Received By mmclean Date 2005-04-07 Time 16:55 Sent To I
Notes
2005-04-07 00:00:00NOTE:
 1. MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE
 2. MUST PULL SEPERATE PERMIT FOR
 GATES/WALLS/FENCE WITH CITY OF WEST PALM
 BEACH UTILITY EASEMENT APPROVAL.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-02-28 Cont ID  
Sent By mmclean Date 2005-02-28 Time 12:39 Rev Time 0.00
Received By mmclean Date 2005-02-28 Time 12:39 Sent To I
Notes
2005-02-28 00:00:00DENIED,
 1. THE STRUCTURE EXCEEDS THE HEIGHT
 REQUIREMENT OF 33FT.MUST MEASURE FROM
 THE GRADE TO THE TOP OF THE CHIMNEY.
 MUST REDUCE CHIMNEY AND PROVIDE NEW
 ELEVATION SHEETS.CALLED CONTR LEFT MSG
 ON VOICE MAIL.
  
 MICHELLE MCLEAN
 ZONIG TECHNICIAN
 CONSTRUCTION SERVICES.
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-18 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:40 Rev Time 0.00
Received By mmclean Date 2004-10-18 Time 10:40 Sent To I
Notes
2004-10-18 00:00:00DENIED, CHIMNEY IS OVER THE HEIGHT
 REQUIREMENT. HOUSE HEIGHT MUST BE 30FT
 AND 10% ADDITIONAL FOR CHIMENEY, MAKING
 IT 33FT IN HEIGHT.CALLED CONTR