| 2004-10-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT (36): 04100051- DCA MODULAR BLDG |
| | (32)04090793- SITE/RAMP/DECK/ |
| | FACADE/ ROOF AND SKYLIGHT |
| | ADD: 419 LAKEVIEW |
| | CONT: THE WEITZ CO |
| | TEL: (561)686-5511 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN |
| | QUESTIONTHE BUILDING OFFICIAL MAY |
| | REQUIRE EXPLORATIONS, TEST OR OTHER |
| | ADEQUATE PROOF AS TO THE PERMISSIBLE |
| | SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) SALES TRAILER, PROVIDE DCA (DEPART- |
| | MENT OF COMMUNITY AFFAIRS) APPROVAL |
| | PACKAGE. THE DCA PACKAGE SUBMITTED |
| | STATES THESE REQUIREMENTS HAVE NOT BEEN |
| | COMPLETED BY THE BUILDING MANUFACTURER, |
| | AND ARE NOT CERTIFIED BY THE STATE MODU- |
| | LAR LABEL & OR CERTIFICATION. THE 17 |
| | ITEMS NOT COVERED BY THE STATE WILL NEED |
| | TO BE REVIEWED & COMPLIED WITH THROUGH |
| | THE LOCAL DESIGN PROFESSIONALS. |
| | (1) COMPLETE FOUNDATION SYSTEM |
| | (2) RAMPS AND STAIRS |
| | (6) STRUCTURAL AND AESTHETIC INTER- |
| | CONNECTIONS BETWEEN MODULES |
| | (7) INSTALLATION OF INSULATION @ |
| | FLOORS, CEILING & END WALLS AT |
| | MATING LINES |
| | (9) INSTALL FIRESTOPPING AT ALL MATE |
| | LINES FLOOR / CEILING. |
| | (10) STORM PROTECTION 1606.1.4. SEE |
| | BUILDING OFFICIAL INTERPRETATION |
| | (12) SKYLIGHT CONSTRUCTION |
| | (13) FLOOR FINISH MATERIALS |
| | (14) DOORS INDICATED ON FLOOR PLANS |
| | (17) GUTTERS AND DOWNSPOUTS |
| | |
| | THE EXEMPTION IN 553.10(8)(E) THAT THE |
| | LOCAL BUILDING DEPARTMENT DOES NOT |
| | INSPECT OR REVIEW MODULAR BUILDINGS IS |
| | ONLY WHEN NO RECONSTRUCTION OF THE UNIT |
| | IS TO OCCUR. THE FLOOR PLAN OF THE DCA |
| | UNIT VERSES THE FLOOR PLAN SUBMITTED BY |
| | BAP DEVELOPMENT INDICATES WORK BY ALL |
| | TRADES ALLOWING FOR LOCAL PLAN REVIEW |
| | COMMENTS AND INSPECTION. |
| | |
| | 4) F102.1 NO TYPE VI CONSTRUCTION |
| | ALLOWED IN THE "FIRE DISTRICT". DECK, |
| | EXTERIOR WALLS OR RAMPS NOR THE MANUFACT |
| | URED BUILDINGS. |
| | |
| | 5) ACCESSIBLE BUILDINGS: 11-4.1.3(8)(A) |
| | (III)ACCESIBLE ENTRANCES SHALL BE THE |
| | ENTRENCES USED BY THE MAJORITY OF |
| | PEOPLE VISITING OR WORKING IN THE BUILD- |
| | NG, NOT TO BE LOCATED IN THE BACK OF THE |
| | BUILDING. |
| | |
| | 6) WITH AN ACCESSIBLE ENTRANCE PARKING |
| | FACILITIES SHALL BE LOCATED ON THE SHORT |
| | EST ACCESSIBLE ROUTE OF TRAVEL TO AN |
| | ACCESSIBLE PEDESTRIAN ENTRY INTO THE |
| | FACILITY. 11-4.6.2 LOCATION. |
| | |
| | 7) A-4.0 PARKING STALL DETAIL TO COM- |
| | PLY WITH DOUBLE LINE STRIPING SEE ATTACH |
| | MENT. |
| | |
| | 8)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PROVIDE ELEVATIONS FOR HANDICAPPED PARK- |
| | ING AND ACCESS AISLE,CROSS SECTION SLOPE |
| | |
| | 9) A-4.0 HANDRAIL DETAIL TO COMPLY WITH |
| | 11-4.9.4(3) THE CLEAR SPACE BETWEEN HAND |
| | RAILS & WALL SHALL BE 1 1/2". |
| | |
| | 10)A-4.0 SECTION AA INDICATES THE USE OF |
| | HAND/ GUARDRAILS, TO COMPLY WITH: |
| | 1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 11) A-4.0 SAME SECTION AA INDICATES A |
| | SKYLIGHT BUT NO DETAILS,CURBS PRODUCT |
| | APPROVALS,ETC |
| | |
| | 12)SHEET A-2.0 HAS NOTES THAT WORK WILL |
| | BE PREFORMED BY OTHERS,EXTERIOR DOORS, |
| | EXTERIOR WINDOWS, INTERIOR WALLS, DECK & |
| | SKYLIGHT. WHO WILL BE INSTALLING THESE |
| | ITEMS IF NOT THE GC? THE GENERAL CONTRAC |
| | TOR WILL ASSUME RESPONSIBLITY FOR THE |
| | PROJECT? |
| | |
| | 13)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS, CURTAIN WALLS |
| | B) EXTERIOR DOORS |
| | C) SKYLIGHTS |
| | D) STORM SHUTTERS |
| | E) STRUCTURAL COMPONENTS,TRUSS ANCHORS |
| | F) ROOFING |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 14) SHEET A-6.0 INDICATES ELEVATIONS BUT |
| | NO FRAMING INFORMATION ON ELEVATIONS? |
| | NOR STOREFRONT, MULLIONS ETC |
| | |
| | 15) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 16) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 17)PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 18)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 19)1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 20) 1707.4.4.1 ANCHOR REQUIREMENTS: |
| | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| | ED IN ACCORDANCE WITH THE PUBLISHED |
| | MANUFACTURER'S RECOMMENDATIONS TO |
| | ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| | SUBSTITUTE ANCHORING SYSTEM USED FOR |
| | THE SUBSTRATE NOT SPECIFIED BY THE |
| | FENESTRATION MANUFACTURER SHALL PROVIDE |
| | EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| | TED BY ACCEPTED ENGINEERING PRACTICES. |
| | |
| | 21) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 22) S-1 INDICATES THE ANCHOR SCHEDULE |
| | BUT NO MANUFACTURER IS NOTED: |
| | 1707.3.1 JOIST HANGERS, FRAMING |
| | ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| | ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| | LABELED AND LISTED FOR THEIR LOAD CARRY- |
| | ING CAPACITY. |
| | |
| | 23) CORRECT THE STREET NAME TO THE SOUTH |
| | OF THE PROPERTY, TO LAKEVIEW, NOT |
| | JASSMINE OR OKEECHOBEE. |
| | |
| | 24)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |