Plan Review Details - Permit 04090781
Plan Review Stops For Permit 04090781
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By jwitmer Date 2004-10-28 Time 14:56 Rev Time 1.11
Received By jwitmer Date 2004-10-28 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 15:33 Rev Time 0.55
Received By jwitmer Date 2004-10-20 Time 15:33 Sent To PC
Notes
2004-10-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090781
 ADD: 600 S ROSEMARY AV# 162
 CONT: SCHIAPPA CONST
 TEL: (954)658-7493
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) A-2 GENERAL NOTES (9) CORRECT THE
 CODE SECTION TO 2001 FLORIDA BUILDING
 CODE, 2003 REVISIONS.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) NEW STOREFRONT DOOR
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) STAINLESS HANDRAIL SECTION TO COMPLY
 WITH 11-4.26.2 THE DIAMETER OR WIDTH OF
 THE GRIPPING SURFACES OF THE HANDRAIL
 ORGRABRAIL SHALL BE 1 1/4" TO 1 1/2" OR
 THE SHAPE SHALL PROVIDE AN EQUIVANT
 GRIPPING SURFACE.IF HANDRAILS OR GRAB
 BARS ARE MOUNTED ADJACENT TO A WALL, THE
 SPACE BETWEEN THE WALL AND THE GRAB BAR
 SHALL BE 1 1/2". SEE FIGURE ABC & D.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2004-11-01 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 06:47 Rev Time 0.33
Received By dpalmer Date 2004-10-06 Time 06:47 Sent To  
Notes
2004-10-06 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQUIRED INFORMATION ON TITLE BLOCK.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND ON
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE RECEPTS SHOWN AT
 WINDOW LOCATION FOR WHAT APPEARS TO BE
 THE REQUIRED SHOW WINDOW RECEPTS,
 HOWEVER THERE DOES NOT APPEAR ANY
 INDICATION OF CIRCUITING ? #?
 PLEASE SEE 210.62,220.12A
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING EM/EXT LTS SHOWN ON PLANS.
 THESE ARE NOW SHOWN ON AN INDIVIDUAL
 CIRCUIT. PLEASE SEE SECTION "E" OF 700.
 .12. TO BE ON WITH GEN LT IN AREA.
  
 PLEASE SEE ANY POSSIBLE COMMENTS BY
 OTHER REVIEWERS WHICH MAY HAVE NA AFFECT
 ONELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 PLANS AND ONLY INSERT NEW/ REVISED
 SHEETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-13 Cont ID  
Sent By mcarsill Date 2004-10-13 Time 17:21 Rev Time 0.00
Received By mcarsill Date 2004-10-13 Time 17:20 Sent To  
Notes
2004-10-13 00:00:001) FIRE SPRINKLER REMODEL PERMIT
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:11 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 16:11 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#41

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2004-10-04 Time 12:11 Sent To PC
Notes
2004-10-04 00:00:00TO COMM BD#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-14 Cont ID  
Sent By pkrauss Date 2004-10-14 Time 07:29 Rev Time 0.15
Received By pkrauss Date 2004-10-14 Time 07:26 Sent To  
Notes
2004-10-14 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLAN SHEET A-3 NOTE #3, A/C
 GRILLES TO REMAIN.REWORK GRILLES AT
 NEW CEILING AS REQUIRED. (SUBMIT A/C
 SHOP DRAWINGS).