Plan Review Details - Permit 04090764
Plan Review Stops For Permit 04090764
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-02-27 Cont ID  
Sent By rmcdouga Date 2007-02-27 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2007-02-27 Time 12:45 Sent To  
Notes
2007-02-27 13:24:21THE ARCHITECT CAME IN AND MADE REDLINE CORRECTIONS TO
 THE REVISED PLAN SHEETS A2, A3, A4, A6, A7, A9 AND A10.
 THEY ARE OK NOW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-01-24 Cont ID  
Sent By rmcdouga Date 2007-01-24 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2007-01-24 Time 15:22 Sent To  
Notes
2007-01-24 17:04:34DENIED BY BUILDING
  
 1)ALL OF THE NEW REVISIONS TO THE PLANS ARE NOT
 CLOUDED AND MARKED WITH THE REVISION NUMBER INSIDE THE
 TRIANGLE.
  
 2) THE TITLE BLOCKS ARE MISSING THE REVISION NUMBERS ON
 SEVERAL SHEETS.
  
 3) THE REVISION DATES IN THE TITLE BLOCK HAVE BEEN
 PARTIALLY CUT OF ON SHEET A6.
  
 4) SPECIFY THE SIZES OF THE ATTIC ACCESS OPENINGS.
  
 5) THE ATTIC ACCESS FROM THE SECOND FLOOR TO AHU-3 DOES
 NOT NEED TO BE SHOWN ON THE FIRST FLOOR PLAN A-2. SHOW
 IT AS A DOOR IN THE WALL OF CLOSET 204 ON THE SECOND
 FLOOR PLAN A-3.
  
 6) WINDOWS (B) IN THE RECONFIGURED 2ND FLOOR SHOWER ARE
 BOTH REQUIRED TO HAVE SAFETY GLAZING OR BE IMPACT
 RESISTANT. THE WINDOW SCHEDULE SHOWS ONLY ONE WITH
 TEMPERED GLASS. PRODUCT APPROVALS SUBMITTED ARE FOR
 LARGE MISSLE IMPACT GLAZING.
  
 7)PLEASE CORRECT THE DOOR AND WINDOW SCHEDULE ON A-9.
 SECOND FLOOR DOORS 71 AND 72 HAVE BEEN OMITTED BUT ARE
 STILL SHOWN ON A-3. CHECK DOORS 15, 16, 46 AND 63 ON
 THE FIRST FLOOR.
  
 8) REVISIONS TO OTHER TRADES AFFECTED BY THESE CHANGES
 WILL BE REQUIRED.
  
 9) THE DIMENSIONS LISTED IN ROOM 128 ARE ILLEGIBLE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-12-07 Cont ID  
Sent By rmcdouga Date 2006-12-07 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2006-12-07 Time 15:00 Sent To  
Notes
2006-12-07 16:18:37DENIED BY BUILDING
  
 REVISIONS TO SHEETS A-2(FIRST FLOOR PLAN) AND A-3
 (SECOND FLOOR PLAN) .
  
 1)SHEETS A-2AND A-3BOTH REFERENCE THE 2004
 FLORIDA BUILDING CODE. THIS PROJECT IS PERMITTED UNDER
 THE 2001 FBC. PLEASE SPECIFY 2001 FBC.
  
 2) THE FRONT ELEVATION IS AFFECTED BY THE ELIMINATION
 OF THE SECOND FLOOR WINDOW IN ROOM 206 ON SHEET A-3.
 SUBMIT REVISED ELEVATION.
  
 3) SUBMIT REVISED PLANS FOR MEP PLANS THAT WILL BE
 AFFECTED BY THE REVISIONS TO THE BUILDING PLANS.
  
 4) THE DOOR AND WINDOW SCHEDULES ON A-9NEED TO BE
 REVISED TO REFLECT THE CHANGES TO THE FLOOR PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-02 Cont ID  
Sent By rmcdouga Date 2005-08-02 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2005-08-02 Time 16:08 Sent To  
Notes
2005-08-02 00:00:001) REVISIONS TO SHEETS A2, A4, A5, A6,
 A7, A9, S1, S2 & S3 ARE OK.
  
 2) CONTRACTOR TO SUBMIT SPECIFICATIONS
 AND LISTING INFORMATION FOR THE VENTLESS
 FIREPLACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-07-07 Cont ID  
Sent By rmcdouga Date 2005-07-07 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2005-07-07 Time 07:31 Sent To  
Notes
2005-07-07 00:00:00REVISION DENIED
  
 1) ON SHEET A5 THERE IS AN OPENING WITH
 ID TAG (T). THERE IS NO SUCH TAG LISTED
 IN THE WINDOW AND DOOR SCHEDULES ON A9.
  
 2) OPENING #38 IS SHOWN AS A DOUBLE
 SCREEN DOOR ON A5, BUT IS LISTED IN THE
 DOOR SCHEDULE AS AN ARCHED FIXED SCREEN.
  
 3) THE ID TAGS FOR OPENINGS 33 AND 34 ON
 A7 ARE LISTED IN THE DOOR SCHEDULE ON A9
 AS ARCHED SWING DOORS. THE REVISED DOORS
 ARE NOT ARCHED.
  
 4) THE OPENING AT THE GUEST LOGGIA IS
 SPECIFIED AS SCREEN, BUT A PAIR OF
 FRENCH DOORS IS SHOWN ON THE ELEVATION
 ON A7.
  
 5) THE ROOF OF THE CHIMNEY THAT WAS
 CHANGED TO VENTLESS IS SHOWN FLOATING IN
 THE AIR ON SHEET A7.
  
 6) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE
 VENTLESS FIREPLACE.
  
 7) THE CHIMNEY SHOWN ON A4 AND A6 IS
 REQUIRED TO EXTEND AT LEAST 3' ABOVE THE
 HIGHEST POINT WHERE THEY PASS THROUGH
 THE ROOF PER FBC 2804.
  
 8) ON SHEET S2 THERE ARE TWO BEAM ID
 TAGS (B16 AND B17) THAT ARE NOT LISTED
 IN THE BEAM SCHEDULE ON S3.
  
 9) COORDINATE THE OPENING ID TAGS ON A2
 WITH THE SCHEDULES ON A9.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-25 Cont ID  
Sent By rmcdouga Date 2005-02-25 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2005-02-25 Time 11:33 Sent To P
Notes
2005-02-25 00:00:00PROVISO
  
 REVISE THE STAIR RISER AND TREAD
 DIMENSIONS TO COMPLY WITH FBC 1007.3.1.
 THE SUM OF TWO RISERS AND A TREAD
 EXCLUSIVE OF THE NOSING SHALL BE NOT
 LESS THAN 24" NOR MORE THAN 25".

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By rmcdouga Date 2005-01-10 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2005-01-10 Time 09:26 Sent To  
Notes
2005-01-10 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
  
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE SAFETY GLAZING IN BATH #2 IS
 SPECIFIED FOR THE WRONG WINDOW. PLEASE
 CORRECT.
  
 4) SUBMIT AN AFFIDAVIT FROM THE ASPHALT
 BASED ROOFING PRODUCT MANUFACTURER
 CERTIFYING THE USE OF THEIR PRODUCT OVER
 AN UNVENTED ATTIC SYSTEM. SEE ATTACHMENT
 FROM PALM BEACH COUNTY BCAB.
  
 5) SPECIFY THE SCUPPER SIZES FOR
 DRAINING THE FLAT ROOFS.
  
 6) RISER AND TREAD DIMENSIONS DO NOT
 COMPLY WITH FBC 1007.3.1.
  
 7) SHOP DRAWING WILL BE REQUIRED FOR THE
 FLOOR SYSTEM AT THE SECOND FLOOR.
  
 8) ITEM NUMBER (14) FROM THE FIRST
 REVIEW STATES THAT BUCK FASTENING
 DETAILS ON A10 CONFLICT WITH THOSE ON
 S4. THE NOTES ON THE BUCK DETAILS ON A10
 REFER TO S4 FOR DETAILS. THERE WAS NO
 SHEET S4 SUBMITTED.
  
 9) SUBMIT STRUCTURAL DETAILS FOR
 FIREPLACE AND CHIMNEY CONSTRUCTION.
 SPECIFY THE REQUIRED HEIGHT OF THE
 CHIMNEY ABOVE THE ROOF AND ROOF
 STRUCTURES. FBC 2114.3.2 REQUIRES THE
 FIREBOX TO HAVE A MINIMUM DEPTH OF 20"
 AND A THROAT AT LEAST 8" ABOVE THE
 FIREPLACE OPENING. SEE FBC 2114.3.8 FOR
 HEARTH DIMENSIONS.
  
 10) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. PLEASE
 SUBMIT THE COVER SHEETS WITH THE FL
 NUMBERS FOR EACH PRODUCT FROM THE STATE
 WEBSITE.
  
 11) SUBMIT THE FLORIDA PRODUCT APPROVALS
 FOR ALL OF THE TRUSS CONNECTORS THAT ARE
 SPECIFIED ON THEPLANS.
  
 12) SUBMIT STATE OR LOCAL PRODUCT
 APPROVALS WITH INSTALLATION INSTRUCTIONS
 FOR THE FOLLOWING:
 - ACHED TOP CASEMENT WINDOWS
 - HOPPER WINDOWS
  
 13) THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE SLIDING GLASS DOOR HAS
 ONLY SMALL MISSLE IMPACT RATING AND WILL
 BE REQUIRED TO BE COVERED BY STORM
 PANELS. SUBMIT STORM PANEL PRODUCT
 APPROVAL KEY PLAN AND INSTALLATION
 INSTRUCTIONS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-09 Cont ID  
Sent By rmcdouga Date 2004-11-09 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2004-11-09 Time 08:03 Sent To  
Notes
2004-11-09 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4) THE WINDOW (G) IN BEDROOM #2 IS
 SPECIFIED AS A 2' X 4' CASEMENT WINDOW
 ON THE SCHEDULE ON A9. VERIFY THAT THIS
 WILL MEET THE CLEAR OPENING REQUIREMENTS
 OF FBC 1005.4.
  
 5) FBC 2405.2 REQUIRES SAFETY GLAZING IN
 WINDOWS WITHIN 3' HORIZONTALLY AND LESS
 THAN 60" ABOVE THE WALKING OR STANDING
 SURFACES AT TUBS OR SHOWERS. PLEASE
 SPECIFY ON THE PLANS THAT THE WINDOWS IN
 THE MASTER BATH AND BATH #1 AT THE
 SHOWER ARE TO HAVE SAFETY GLAZING IF
 THEY ARE WITHIN THESE AREAS.
  
 6) 61G-16.004 OF THE FAC REQUIRES THE
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT ON EACH PLAN SHEET.
  
 7) SPECIFY THE LOCATION AND THE MINIMUM
 SIZE OF THE ATTIC ACCESSES AS REQUIRED
 BY FBC 2309.6.
  
 8) THE NOTE ON A8 SPECIFIES ATTIC
 VENTILATION AND THE WALL SECTIONS ON A11
 SPECIFY AN ICYNENE FOAM INSULATION
 SYSTEM WHICH IS VENTLESS. PLEASE
 CLARIFY. SPECIFY THE NUMBER SIZE AND
 SPACING OF ATTIC VENTS OR SUBMIT THE
 DESIGN DRAWINGS FROM A FLORIDA
 REGISTERED DESIGN PROFESSIONAL, THE
 ICYNENE SPECIFICATIONS FROM THE
 MANUFACTURER AND AN AFFIDAVIT CERTIFYING
 THE USE OF THE ASPHALT BASED ROOFING
 PRODUCTS OVER AN UNVENTED SYSTEM.
 SPECIFY THE R-VALUE OF THE INSULATION.
  
 9) PROVIDE DETAILS OF THE FLAT ROOFS AND
 INDICATE HOW DRAINAGE WILL BE ACHIEVED.
  
 10) REVISE THE BOTTOM RAIL NOTE ON A10
 TO STATE FLOOR OR DECK AND NOT ROOF.
  
 11) SPECIFY THE RISER HEIGHTS AND TREAD
 DEPTHS FOR THE STAIRS. SPECIFY THE
  
 12) SPECIFY THE EMBED DEPTH OF THE
 EXPANSION BOLTS AT THE TOP OF THE GARAGE
 DOOR BUCKS ON A10.
  
 13) SHOP DRAWINGS WILL BE REQUIRED TO BE
 SUBMITTED FOR APPROVAL FOR THE SECOND
 FLOOR SYSTEM.
  
 14) THE BUCK DETAILS ON A10 CONFLICT
 WITH THE BUCK FASTENING DETAILS ON S4.
 PLEASE CORRECT.
  
 15) BUCK DETAILS ON A10 SPECIFY 2-1/2"
 TAPCONS WITH 1-1/2" EMBED THROUGH A 2X
 BUCK. THIS IS NOT POSSIBLE. PLEASE
 CORRECT.
  
 16) SUBMIT DETAILS FOR FIREPLACE AND
 CHIMNEY CONSTRUCTION. SHOW DIMENSIONS,
 HEIGHT ABOVE ROOF AND COMPLIANCE WITH
 FBC 2113, 2114, 2804 & 2806.
  
 17) SUBMIT CUT SHEETS FOR THE ELEVATOR.
 SPECIFY LOCATION OF ELEVATOR EQUIPMENT,
 GUIDE RAIL ATTACHMENTS, ETC.
  
 18) THE BEAM SCHEDULE ON S3 HAS 2 NOTE
 B. ONE SHOULD BE NOTE C. PLEASE
 CORRECT.
  
 19) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:
 - TRUSS CONNECTORS
 - CUSTOM MAHOGANY ENTRY DOORS
 - ARCHED TOP FRENCH DOORS WITH AND
 WITHOUT SIDELITES
 - RADUIS CASEMENT WINDOWS
 - HOPPER WINDOW
 - SLIDING GLASS DOOR
  
 23) THE PRODUCT APPROVAL INSTALLATION
 DRAWINGS FOR THE CLOPAY GARAGE DORRS ARE
 ILLEGIBLE. SUBMIT LEGIBLE COPIES.
  
 24) SOME OF THE NOAS THAT WERE SUBMITTED
 ARE NOT THE CORRECT ONES FOR THE FLORIDA
 PRODUCT APPROVALS THAT WERE GIVEN.
 PLEASE SUBMIT THE CORRECT NOAS OR OTHER
 EVALUATION LISTED ON THE STATE WEB
 SITE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
  
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 08:36 Rev Time 0.50
Received By btrobaug Date 2007-04-03 Time 08:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-23 Cont ID  
Sent By btrobaug Date 2007-03-23 Time 08:39 Rev Time 0.75
Received By btrobaug Date 2007-03-23 Time 07:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-12 Cont ID  
Sent By btrobaug Date 2007-03-12 Time 08:39 Rev Time 2.00
Received By btrobaug Date 2007-03-06 Time 17:12 Sent To PC
Notes
2007-03-12 08:39:31 
  
 REVISION DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PANEL SCHEDULES MUST INCLUDE BRANCH/FEEDER
 CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION SO THAT
 COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC AS
 AMENDED. SEE PERMITTED SET .
  
 2} THE SCHEDULES MARKED "GENERAL, CENTER AND LEFT" IS
 UNACCEPTABLE AND CANNOT BE CORRELATED WITH LOCATION OF
 THE PANELS ON THE PLAN. INDICATE THE PANEL DESIGNATIONS
 AT THE LOCATION AND ON THE SCHEDULE.
  
 3} COMPLETE THE SERVICE CALCULATION. INDICATE SERVICE
 AMPERAGE. 215.5.
  
 4} A WOOD FUELED PIZZA OVEN SHOULD NOT BE IN THE
 ELECTRICAL CALCULATIONS. PLEASE REMOVE SAME.
  
 5} THE POOL PANEL LOCATION SHOWN ON THE PLAN IS IN
 VIOLATION OF 110.26 CLEARANCE REQUIREMENTS. PLEASE
 VISIT THE SITE FOR ACTUALLOCATIONS AND ADJUST THE
 DRAWING ACCORDINGLY.
  
 6} THE CONDENSER DISCONNECTS APPEAR TO BE IN VIOLATION
 OF 110.26, PLEASE VERIFY CLEARANCES OF 3' OR MORE.
  
 7} THERE IS A LUTRON LIGHTING CONTROL SYSTEM INDICATED
 ON THE DRAWING, THIS SYSTEM COST MUST BE ADJUSTED FOR,
 AS IT WAS NOT PART OF THE ORIGINAL PLAN. PLEASE
 INDICATE THE INCREASED VALUE TO THE PERMIT CLERK AND
 OBTAIN A PAID RECEIPT FOR SAME PRIOR TO RESUBMITTING
 CORRECTED REVISIONS. 108.3 FBC AS AMENDED.
  
 8} THE RISER DIAGRAM INCORRECTLY INDICATES THE CONDUIT
 FEEDING THE " HOUSE PANEL ", GOING TO THE TRANSFER
 SWITCH. ALSO SHOWS CONDUIT FROM THE " HOUSE PANEL" TO
 THE METER/MAIN. INDICATE DESIGNATION FOR THE "HOUSE
 PANEL" (SEE NOTE #2). CORRELATE THE RISER DIAGRAM.
  
 9} THE GENERATOR EQUIPMENT INDICATED ON THE PLAN MUST
 BE PERMITTED SEPARATELY. SUBMIT SPECIFICATIONS AND
 PLANS FOR SAME UNDER A RESIDENTIAL GENERATOR
 APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-15 Cont ID  
Sent By btrobaug Date 2007-02-15 Time 11:11 Rev Time 2.00
Received By btrobaug Date 2007-02-15 Time 06:43 Sent To PC
Notes
2007-02-15 11:11:28 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE FOLLOWING NEED TO BE ON THE PLAN, ON THE SHEETS
 THAT ARE BEING REVISED. PLEASE KEEP IN MIND THE SHEET
 THAT IS BEING REPLACED WILL BE BASICALLY VOIDED. ALL
 INFORMATION THAT PERTAINS TO THAT SHEET MUST THEREFORE
 APPEAR ON THE REVISED SHEET.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. NOTE THERE IS A GENERATOR PANEL NOW
 SHOWN ON THE PLAN, THERE WAS NO GENERATOR APPLICATION
 OR PERMIT FOR THIS RESIDENCE.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PROVIDE PANEL SCHEDULES PER 408.4.
  
 4}PROVIDE LOAD CALCULATIONS PER ARTICLE 220. INDICATE
 WHICH SECTION IS BEING USED.
  
 5} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED IN THE
 BATHROOMS PER 210.8(A)(1). SOME ARE MISSING THAT
 DESIGNATION ON THE PLAN.
  
 6} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED FOR THE
 KITCHENCOUNTERTOPS PER 210.8(A)(6)).
  
 7} AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH ISLAND COUNTER SPACE WITH A LONG DIMENSION OF 600
 MM (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM
 (12 IN.) OR GREATER. 210.52.(C)(2).
  
 8} WET BAR SINKS- WHERE THE RECEPTACLES ARE INSTALLED
 TO SERVE THE COUNTERTOP SURFACES AND ARE LOCATED WITHIN
 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE WET BAR SINK.,
 GFI PROTECTED 210.8(A)(7).
  
 9}SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} THE DISCONNECTS FOR THE CONDENSING UNITS ARE
 MISSING FROM THE PLAN INDICATE LOCATION PER 440.14 AND
 CLEARANCE PER 110.26.
  
 11} THE ARCHITECTS SEAL IS NOT LEGIBLE ON THE PLAN
 481.221 FAC.
  
 12} THERE ARE NO CLOUDS, HIGHLIGHTS OR DELTA 'S ON THE
 PLAN TO INDICATE AREAS IF REVISION. PLEASE INCLUDE SAME
 PER 106.1.3 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-09 Cont ID  
Sent By btrobaug Date 2005-02-09 Time 15:58 Rev Time 0.50
Received By btrobaug Date 2005-02-09 Time 14:54 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-01-05 Cont ID  
Sent By btrobaug Date 2005-01-05 Time 11:37 Rev Time 0.50
Received By btrobaug Date 2005-01-03 Time 09:47 Sent To M
Notes
2005-01-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECT DID NOT SEAL SHEET
 E-2.
  
 2} THE GROUNDING SYSTEM AND THE
 GROUNDING ELECTRODE CONDUCTOR MUST
 COMPLY WITH 250.50, 250.52,(FOOTER
 STEEL) AND 250.66 (1/0).
  
 3} THE DISCONNECTS FOR THE CONDENSING
 UNITS MUST COMPLY WITH
 110.26(CLEARANCE)
 IT DOES NOT APPEAR THIS IS POSSIBLE
 GIVEN THE PROXIMITY OF THE PRIVECY
 WALL.
  
 4} THERE ARE FIVE PANELS SHOWN ON THE
 RISER AND ONLY THREE ON THE PLAN. PLEASE
 SHOW AND LABEL ALL THE SERVICE
 EQUIPMENT.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 14:09 Rev Time 0.75
Received By btrobaug Date 2004-10-15 Time 12:33 Sent To M
Notes
2004-10-15 00:00:00 
 PLEASE SUBMIT LOAD CALCULATIONS AND A
 RISER DIAGRAM PER 215.5 NEC. ALSO
 SUBMIT PANEL SCHEDULES SO THAT BRANCH
 CIRCIUT CODE COMPLIANCE MAY BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:32 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:32 Sent To  
Notes
2007-04-02 17:32:32TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 16:08 Sent To E
Notes
2007-03-06 16:08:56TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 09:33 Sent To M
Notes
2007-02-14 09:33:39TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 09:28 Sent To E
Notes
2007-02-14 09:29:08TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 09:14 Sent To P
Notes
2007-02-14 09:19:56TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 12:55 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 12:55 Sent To M
Notes
2007-01-23 12:55:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 10:43 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 10:43 Sent To B
Notes
2007-01-23 10:44:45TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 09:37 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 09:37 Sent To B
Notes
2006-12-05 09:37:31TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 09:36 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 09:36 Sent To P
Notes
2006-12-05 09:36:27TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 09:34 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 09:34 Sent To M
Notes
2006-12-05 09:34:40TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 11:16 Sent To M
Notes
2006-08-10 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 14:23 Sent To B
Notes
2005-07-21 00:00:00TO "RMCDOGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 17:55 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 17:55 Sent To B
Notes
2005-07-01 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 09:59 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 09:59 Sent To E
Notes
2005-02-04 00:00:00TO "B TROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 11:18 Rev Time 0.00
Received By mjacobs Date 2004-12-29 Time 11:18 Sent To E
Notes
2004-12-29 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 13:09 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 13:09 Sent To Z
Notes
2004-12-21 00:00:00SENT TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-09 Cont ID  
Sent By mmclean Date 2004-10-14 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2005-02-25 Time 11:32 Sent To  
Notes
2004-10-15 00:00:00TO SFD RACK/E
2004-09-24 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-03-19 Cont ID  
Sent By hmoser Date 2007-03-19 Time 08:27 Rev Time 0.00
Received By hmoser Date 2007-03-19 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 08:44 Rev Time 0.30
Received By tgordon Date 2007-02-20 Time 08:44 Sent To  
Notes
2007-02-20 08:45:00REVISION TO MECH. PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-01-31 Cont ID  
Sent By tgordon Date 2007-01-31 Time 11:00 Rev Time 1.30
Received By tgordon Date 2007-01-31 Time 11:00 Sent To  
Notes
2007-01-31 11:32:03MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SHOW ON ENERGY CALCULATIONS SEER FOR 3 OTHER
 UNITS, LINE 12 C.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS SHOW TWO GAS WATER HEATERS, LINE
 14 A, AND B, PLEASE SHOW THE LOCATION OF THE GAS WATER
 HEATERS ON THE MECHANICAL PLANS, AND PROVIDE COMBUSTION
 AIR IF REQUIRED.
  
 4) MECHANICAL PLANS PAGE A/C1 SHOW TWO CU4 CONDENSER
 UNITS, PLEASE CORRECT.
  
 5) ARCHITECTURAL FIRM'S ADDRESS AND PHONE NUMBER MUST
 APPEAR IN THE TITLE BLOCK, PER FAC 61G1-16.004.
  
 6) ARCHITECT SEAL IS NOT LEGIBLE, IF SEAL CAN NOT BE
 READ PLANS WILL NOT PASS REVIEW, PLEASE CORRECT.
  
 7) ARCHITECT NEEDS TO DATE HIS SIGNATURE AT THE SEAL,
 PER FAC 61G1-16.004.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-12-05 Cont ID  
Sent By rregueir Date 2006-12-05 Time 18:30 Rev Time 0.00
Received By rregueir Date 2006-12-05 Time 18:30 Sent To PC
Notes
2006-12-05 19:06:17-----------------DENIED-----------------
  
 1. REVISED ENERGY CALCULATIONS AND MANUAL J IS
 REQUIRED. SEE PREVIOUS REVIEW NOTE #3 (ATTACHED).
  
 2. AHU#2: PLEASE SHOW 10" FLEX ON SUPPLY GOING TO
 DISTRIBUTION BOX RATHER THAN THE 8X4 GRILL.
  
 3. AHU#2: THERE IS NO RETURN DUCT SHOWN FROM 24X14 R?A
 GRILL TO AHU.
  
 4. AHU#3: DUCT SIZE IS MISSING ON SUPPLY FLEX THAT IS
 FEEDING THE DISTRIBUTION BOX IN THE FOYER/DINING ROOM
 AREA.
  
 5. AHU#5: THE SUPPLY FLEX FEEDING THE DISTRIBUTION BOX
 IN THE FAMILY ROOM IS MARKED AS BOTH 10" AND 12".
 PLEASE CLARIFY BY REMOVING THE INCORRECT SIZE.
  
 6. AHU#5: THE DISTRIBUTION BOX SERVING THE PANTRY AND
 BREAKFAST NOOK IS BEING FED BY A 5" FLEX. PLEASE
 CORRECT.
  
 7. PAGE A/C-1 SHOWS SIX CONDENSERS. THERE ARE ONLY 5
 SYSTEMS. PLEASE CLARIFY.
  
 8. THERE ARE AHUS ON FIRST AND SECOND FLOORS MARKED AS
 AHU#2, WHILE THERE IS NO UNIT MARKED AS AHU#1. PLEASE
 CORRECT.
  
 9. THERE ARE TWO DIFFERENT SYSTEMS ON THE EQUIPMENT
 SCHEDULE MARKED AS SYSTEM #3. PLEASE CORRECT.
  
 10. MECHANICAL NOTE #7 SHOWS 200 CFM FRESH AIR REQUIRED
 ON FIRST FLOOR. HOW IS THIS TO BE PROVIDED. PLEASE
 INDIATE ON THE PLANS.
  
 11. MECHANICAL NOTE #9, THIS REQUIREMENT DOES NOT APPLY
 TO ONE AND TWO FAMILY DWELLINGS. YOU MAY REMOVE THIS
 NOTE OR A FAN SHUT-DOWN TEST WILL BE REQUIRED FOR ALL
 A/C SYSTEMS AT THE FINAL INSPECTION.
  
 12. THE SERVICE PANEL OF ATTIC EQUIPMENT MUST BE
 LOCATED WITHIN SIX FEET OF THE ATTIC ACCESS (SCUTTLE
 HOLE) PER FBC CHAPTER 13, SEC 610.1.ABC.3.5.2
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 11:32 Rev Time 1.15
Received By tgordon Date 2006-08-11 Time 11:32 Sent To  
Notes
2006-08-11 00:00:00*** DENIED ***
 1) PLANS ON FILE WERE DONE BY AN ARCTECT
 (PATRICK SEGRAVES) AND ONLY HE CAN MAKE
 REVISIONS TO THE MECHANICAL PLANS.
  
 2) PLANS NEED THE JOB ADDRESS ON THEM.
  
 3) MANUAL J CALCULATIONS ON FILE ARE
 CALLING FOR 73,749 SENSIBLE BTU'S, THE
 MECHANICAL PLANS ARE CALLING FOR 145,880
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J CAL'S,
 PER 2001 FBC 13-607.1.ABC.1.1, YOU HAVE
 ABOUGHT 8 TONS TO MUCH. IF YOU ARE
 PLANING TO KEEP THIS AMOUNT OF COOLING
 YOU NEED TO SUBMIT NEW ENERGY
 CALCULATIONS AND MANUAL J CALCULATIONS.
  
 4) SHOW ATTIC ACCESS TO AHU ON PLANS.
  
 5) NEED TO PROVIDE RETURN AIR TO THE
 LIBRARY.
  
 6) RETURN AIR GRILL 36X16 TO AHU #5 IS
 TO SMALL FOR A 5 TON SYSTEM PLEASE
 CORRECT.
  
 7) AHU #1 RETURN AIR DUCT TO 30X18 GRILL
 IS NOT SIZED.
  
 8) CHECK ALL SUPPLY AIR GRILLS FOR SIZE
 AND CFM'S SOME ARE MISSING THIS
 INFORMATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-10 Cont ID  
Sent By prafter Date 2005-02-10 Time 11:03 Rev Time 2.00
Received By prafter Date 2005-02-10 Time 11:03 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-06 Cont ID  
Sent By prafter Date 2005-01-06 Time 13:38 Rev Time 0.00
Received By prafter Date 2005-02-10 Time 11:01 Sent To P
Notes
2005-01-06 00:00:001. A.H.U. IN ATTIC AREA MUST CONFORM
 WITH 2001 FBC/M 306.3 FOR ACCESS AND
 SERVICE SPACE .
 2. THE R/A DUCT FOR LIBARY REFLECT 10"
 ,SHOULD BE 14". 2001 FBC/M 604.1
 BALLANCE RETURN AIR .
 3. MASTER BATHROOM 208 REQUIREDS
 EXHAUST FAN. FBC/M 402.3.1 .
 4. PROVIDE MANF. INFORMATION FOR HOOD
 REFLECTED ON A-7.2 DRAWING 06-02-04 .
 HOOD COVERS PIZZA OVEN /GRILL /COOKTOP
 .
 5. THERMADOR OUTDOOR COOKTOP MODEL SB2B
 AND THERMADOR CHAR GLO OUTDOOR BARBECUE
 ARE LISTED FOR OUTDOOR ONLY .
 6.MODEL 60/THE HOME OVED DOES NOT
 REFLECT MANF. LISTING LOCATION USAGE .
 PAT RAFTER 561/805/6725 OR 805/6719 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 14:10 Rev Time 0.35
Received By pkrauss Date 2004-10-25 Time 09:40 Sent To  
Notes
2004-10-25 00:00:00DENIED:
 1.PLEASE PROVIDE MANUAL J CALUCALTIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 6
 SECTION 607.1.ABC.1.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.PROVIDE ADDITIONAL INFORMATION ON
 THE PIZZA OVEN, GRIDDLE AND 2 BURNER
 STOVE IN THE LANAI AREA.WILL THESE
 APPLIANCES BE GAS OR ELECTRIC?PROVIDE
 MANUFACTURER SUBMITTAL DATA AND VENTING
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-02-27 Cont ID  
Sent By jleech Date 2007-02-27 Time 08:51 Rev Time 0.00
Received By jleech Date 2007-02-27 Time 08:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-02-22 Cont ID  
Sent By jleech Date 2007-02-22 Time 08:52 Rev Time 0.00
Received By jleech Date 2007-02-22 Time 08:52 Sent To B
Notes
2007-02-22 08:58:32DENIED;
 1. GAS WATER HEATERS TO BE INSTALLED ON OUTSIDE OF
 BUILDING NOT IN GARAGE.
 2. SANITARY RISER DIAGRAM PAGE A-10.
 A) 1ST FLOOR W/M NOT VENTED.
 B) 2ND FLOORW/M NOT SHOWN
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-12-27 Cont ID  
Sent By jleech Date 2006-12-27 Time 08:25 Rev Time 0.00
Received By jleech Date 2006-12-27 Time 08:25 Sent To  
Notes
2006-12-27 08:26:31REVISED SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-26 Cont ID  
Sent By jleech Date 2005-02-26 Time 06:30 Rev Time 0.50
Received By jleech Date 2005-02-26 Time 06:30 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-07 Cont ID  
Sent By jleech Date 2005-01-07 Time 08:58 Rev Time 1.00
Received By jleech Date 2005-01-07 Time 08:58 Sent To B
Notes
2005-01-07 00:00:00DENIED;
 EXER. BATH; SHOWER NOT VENTED (WET VENT
 TO BE UP STREAM OF TOILET). MECHANICAL
 VENT REQUIRED FOR LAV.
 BOTH CLOTHES WASHERS; SHOW STAND PIPE
 AND CLEANOUT ABOVE WASHER DRAIN AT 48"
 AFF. SEE RED LINE ON RISER DIAGRAM.
 BATHROOM ONE; SHOWER NOT VENTED (WET
 VENT TO BE UPSTREAM OF TOILET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 17:17 Rev Time 1.25
Received By kstevens Date 2004-11-04 Time 17:17 Sent To B
Notes
2004-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 A) SHT A-10 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 1) LANAI BAR SINK SHALL CONNECT
 DOWNSTREAM OF THE HORIZONTAL WET VENT OF
 THE BATHROOM FIXTURES. SECTION 909.1
 2) VENTING FOR THE EXERCISE LAV AND THE
 LANAI BAR SINK IS NOT APPROVED. (SEE THE
 VENTING FOR THE OTHER BAR SINK).
 3) WASH MACHINE NOT VENTED, REQUIRES A
 STANDPIPE, AND A CLEANOUT IS REQUIRED 4'
 ABOVE THE FLOOR FOR ACCESS. SECTIONS
 1002.1, 802.4, 708.10
 4) KITCHEN SINK DOES NOT REFLECT THE
 FLOOR PLAN AS THE SINK IS SOUTH OF THE
 VEG. SINK NOT WEST OF VEG. SINK) SECTION
 104.2.1.
 5) BAR SINK IS MISSING. SECTION 104.2.1
 6) RISER DIAGRAM SHOWS 2 LAVS IN BATH
 #2
 BUT THE FLOOR PLAN SHOWS ONLY 1 LAV.
 7) HALL BAR SINK ON THE RISER DIAGRAM IS
 NOT SHOWN ON THE FLOOR PLAN. SECTION
 104.2.1.
 8) 2ND FLOOR SHOWS 2 WATER CLOSETS ON
 THE RISER DIAGRAM BUT ONLY ONE ON THE
 FLOOR PLAN. SECTION 104.2.1
 9) THE BIDET IS NOT VENTED. SECTION
 901.2.1.
 10) WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM FIXTURES.
 SECTION 909.1 AND IS NOT VENTED. SECTION
 901.2.1.
 11) THE LAVS ON THE RISER DIAGRAM FOR
 THE MASTER BATH DO NOT REFLECT THE FLOOR
 PLAN. LAVS ON SEPARATE WALLS AND EAST OF
 THE SHOWER. (SEE FLOOR PLAN). SECTION
 104.2.1.
 B) 61G1-16.003 THE PERSONAL SEAL,
 SIGNATURE, AND DATE ARE REQUIRED ON
 SIGNED AND SEALED PLANS. - NO DATE ON
 THE SEAL. FS 481.2055 - 61G1-16.004(5)
 C) 61G1-16.004(6) A SPACE FOR THE
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FS 481.2055
 D) MAKE CORRECTIONS TO RISER DIAGRAM AND
 RESUBMIT FOR REVIEW.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By mmclean Date 2004-12-29 Time 09:39 Rev Time 0.00
Received By mmclean Date 2004-12-29 Time 09:39 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-14 Cont ID  
Sent By mmclean Date 2004-10-14 Time 09:43 Rev Time 0.20
Received By mmclean Date 2004-10-14 Time 09:43 Sent To I
Notes
2004-10-14 00:00:00DENIED, NEED TO REMOVE THE DRIVEWAY OUT
 OF THE 10FT EASEMENT.THE LANAI WITH
 GRIDDLE, 2 BURNER, PIZZA OVEN, SINKS,
 BAR NEEDS TO BE REMOVED OR PUT OUTSIDE.
 IT'S INTERIOR AND WILL BE CONSIDER
 ANOTHER KITCHEN TO THE HOUSE.CALLED
 SHELDON. MM