Plan Review Details - Permit 04090729
| Plan Review Stops For Permit 04090729 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-11-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-11-15 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-11-15 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2004-11-16 00:00:00 | REVISION DATED 11-12-04 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-11-09 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-11-09 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-11-12 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | ON NOVEMBER 12, 2004, JONI KEMPTON | | | OF QUEST CONTRACTING BROUGHT IN PLANS | | | SHOWING HORN STROBES IN EACH BAY. | | | SINCE A FIRE ALARM PERMIT IS PRESENT | | | THESE COULD BE TREATED AS REVISIONS. | | 2004-11-09 00:00:00 | PROVISO ADD HORN/STROBE TO EACH BAY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-10-05 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | ************DENIED********************** | | | | | | 1) WHEN THE FIRE ALARM CONTROL UNIT, | | | INCLUDING THE DIALER-COMMUNICATOR, IS | | | REPLACED IN AN EXISTING SYSTEM, IT WILL | | | BE TREATED AS IF IT WERE A NEW SYSTEM. | | | | | | 2) NEW FIRE ALARM SYSTEMS SHALL BE UL | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 3) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 4) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | 5) THE WEST PALM BEACH FIRE MARSHAL | | | OFFICE REQUIRES DUCT DETECTORS TO SEND | | | A GENERAL FIRE ALARM. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-12 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-12 |
Time |
15:03 |
Sent To |
FIRE |
|
| Notes |
| 2004-11-12 00:00:00 | TO FIRE/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-28 |
Time |
15:52 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-09-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-23 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-23 |
Time |
14:14 |
Sent To |
FIRE |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |