Plan Review Details - Permit 04090570
Plan Review Stops For Permit 04090570
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2005-02-07 Cont ID  
Sent By dpalmer Date 2005-02-07 Time 13:53 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By alange Date 2004-12-15 Time 13:33 Rev Time 0.00
Received By alange Date 2004-12-15 Time 07:59 Sent To  
Notes
2004-12-15 00:00:00DENIED
 SEE ELECTRICAL REVIEW NOTES.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-04 Cont ID  
Sent By alange Date 2005-02-04 Time 14:02 Rev Time 1.00
Received By alange Date 2005-02-04 Time 11:23 Sent To E
Notes
2005-02-04 00:00:00TO DP DESK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-04 Cont ID  
Sent By alange Date 2005-02-04 Time 08:09 Rev Time 0.25
Received By alange Date 2005-02-04 Time 07:59 Sent To  
Notes
2005-02-04 00:00:00DENIED
  
 PLEASE SUBMIT 2 COMPLETE SETS OF PLANS
 FOR REVIEW.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-21 Cont ID  
Sent By alange Date 2004-10-21 Time 14:25 Rev Time 0.75
Received By alange Date 2004-10-21 Time 14:25 Sent To  
Notes
2004-10-21 00:00:00DENIED
 SEE NOTE REGARDING FS 471.023 AND
 FAC 61G15-23.002 FROM THE ELECTRICAL
 REVIEW.PERMIT CAN NOT BE ISSUED UNTIL
 IT IS RESOLVED.
 BUILDING REVIEW OK.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-07 Cont ID  
Sent By dpalmer Date 2005-02-07 Time 13:52 Rev Time 1.00
Received By dpalmer Date 2005-02-07 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-01-31 Cont ID  
Sent By dpalmer Date 2005-01-31 Time 15:59 Rev Time 0.25
Received By dpalmer Date 2005-01-31 Time 15:59 Sent To B
Notes
2005-01-31 00:00:00********** UNSAT 3RD REVIEW **********
  
 1)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
  
 OF PLANS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-14 Cont ID  
Sent By dpalmer Date 2004-12-14 Time 15:38 Rev Time 0.33
Received By dpalmer Date 2004-12-14 Time 15:38 Sent To  
Notes
2004-12-14 00:00:00*********** UNSAT 2ND REVIEW *********
  
 1)NOTE: PLEASE SEE PLANS WERE
 RESUBMITTED WITH ONLY ONE SET FOR
 REVIEW
 AND STAMPING.
 TWO SETS WITH CORRECTIONS WERE
 SUBMITTED
 FOR "FOUNDATION PERMIT", HOWEVER ONLY
 ONE OLD SET FOR ELECTRICAL PERMIT.
 PLEASE SUBMIT TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE REMOVE ANY AND ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 TWO COMPLETE SETS.
  
 2)NOTE: PLEASE SEE PREVIOUS NOTES FOR
 INFORMATION REQUIRED ON TITLE BLOCK.
 FAC 61G15-23.002, FS 471.023
 ONLY SHEETS FOR FOUNDATION WERE
 CORRECTED FOR THIS.
  
 ****PLEASE SEE NOC HAS EXPIRED SINCE
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING NOC.
 FS 713***************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:47 Rev Time 0.50
Received By dpalmer Date 2004-10-05 Time 18:21 Sent To  
Notes
2004-10-05 00:00:00*********** UNSAT **************
  
 ***PLEASE ALSO SEE NOTES UNDER 04070719
 PERMIT FOR FOUNDATION SHOULD NOT HAVE
 BEEN ISSUED DUE TO VIOLATIONS UNDER
 FS 471.023 AND FAC 61G15-23.002
 THIS WAS NOTED ON PREVIOUS REVIEW AS
 BEING REQUIRED FOR ALL SHEETS AND ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS. ***
 PERMIT/PLANS FOR 04070719 WILL BE PLACED
 ON HOLD.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK WHICH IS REQUIRED UNDER FS 471.023
 ONE SET OF PLANS WILL NOW BE RETAINED
 FOR POSSIBLE REVIEW BY THE FBPE'S FOR
 ABOVE.
  
 2)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS
 REVIEW. TELCO PANEL STILL APPEARS TO
 POSSIBLY HAVING TWO SERVICES FEEEDING
 THIS EQUIPMENT??
  
 3)NOTE: PLEASE CLARIFY TRANSFER AT
 TELCO PANEL. RISER SHOWS RECEPT/EM POWER
 BACK TO FEED EQUIPMENT IN THE EVENT OF A
 POWER FAILURE, PLEASE CLARIFY THIS CONN
 -ECTION SHOWN. IS THIS A TRANSFER SWITCH
 ?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-12-07 Cont ID  
Sent By mamini Date 2004-12-07 Time 10:52 Rev Time 0.50
Received By mamini Date 2004-12-07 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-04 Cont ID  
Sent By alange Date 2005-02-04 Time 11:21 Rev Time 0.00
Received By alange Date 2005-02-04 Time 11:21 Sent To  
Notes
2005-02-04 00:00:00TO ALANGE DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:47 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:47 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#52

Review Stop Z ZONING
Rev No 2 Status P Date 2004-11-23 Cont ID  
Sent By dkanning Date 2004-11-23 Time 14:35 Rev Time 0.00
Received By dkanning Date 2004-11-23 Time 14:02 Sent To  
Notes
2004-11-23 00:00:001. NEED TO PROVIDE PLANTING ON NORTH,
 SOUTH, AND EAST SIDE OF NEW DUMPSTER
 WALLS. SEE SECTION 94-444(B)
 2. PROVIDE VERIFICATION FROM SANITATION
 THAT DUMPSTER MEETS CITY STANDARDS IF
 CITY SERVICE IS REQUESTED. CONTACT GREG
 RODGERS: 659-8048
 3. PLANS ARE NOT DRAWN TO THE INDICATED
 SCALE.
 4. DO NOT RELEASE FOUNDATION PERMIT
 (04070719) UNTIL REVISIONS ARE
 SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-17 Cont ID  
Sent By dkanning Date 2004-11-17 Time 09:42 Rev Time 0.00
Received By dkanning Date 2004-11-17 Time 09:42 Sent To  
Notes
2004-11-17 00:00:001. NEED TO SUBMIT SURVEY.
 2. THE EXISTING CONDITIONS PLAN (P. C2)
 NEEDS TO SHOW THE CABINET LOCATION AND
 NEW DUMPSTER LOCATION IN RELATION TO
 THE
 REST OF THE SITE PLAN WITH DIMENSIONS.
 3. NEED TO PROVIDE PLANTING ON NORTH
 SIDE OF NEW DUMPSTER WALL.SEE SECTION
 94-444(B)
 4. PROVIDE VERIFICATION FROM SANITATION
 THAT DUMPSTER MEETS CITY STANDARDS IF
 CITY SERVICE IS REQUESTED.CONTACT
 GREG
 RODGERS: 659-8048
 5. PLANS ARE NOT DRAWN TO THE INDICATED
 SCALE.