Plan Review Details - Permit 04090561
Plan Review Stops For Permit 04090561
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-13 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 13:30 Rev Time 0.00
Received By rbrown Date 2004-10-12 Time 15:12 Sent To  
Notes
2004-10-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1601.2.1THE SPECIFIED TAPCONS
 ARE NOTED BUT THE WOOD WALL FRAMING SILL
 PLATE SHALL BE ADEQUATELY ANCHORED TO
 THE SLAB WITH 5/8' DIA ANCHOR BOLTS AND
 3"X 3" X 1/8" WASHERS AT 18" CENTERS (OR
 BETTER).AMEND/ANNOTATE THE CROSS-
 SECTION.
  
 2) FBC 2306UNLESS FRAMING ANCHORS ARE
 SPECIFIED, EACH STUD SHALL BE TOE-NAILED
 TO THE HEADER WITH (3)8D COMMON NAILS
 MINIMUM AND END-NAILED TO THE SILL PLATE
 WITH (2)16D COMMON NAILS MINIMUM.
 ANNOTATE THE PLANS.
  
 3) FBC* 1804.1THE PLANS (SEE ABOVE)
 SHALL CONFIRM THAT FINISH GRADE WILL BE
 SLOPED AWAY FROM THE BUILDING.ANNOTATE
 THE CROSS-SECTION.
  
 4) FBC 2504.2.1 AND ASTM C 926MINIMUM
 STUCCO THICKNESS OVER ANY SURFACE OTHER
 THAN MASONRY/CONCRETE SHALL BE 7/8"
 APPLIED IN THREE COATS.AMEND/ANNOTATE
 THE CROSS-SECTION TO SHOW THE THICKNESS
 AND EXTENT OF THE STUCCO WALL FINISH.
  
 5) FBC 1606.2.5THE PLANS SHALL BE
 AMENDED/ANNOTATED TO STATE THE SIZES OF
 THE PROPOSED DOOR AND WINDOWS.
  
 6) SUBMIT PRODUCT A APPROVAL FOR THE
 MULLION BETWEEN THE NEW WINDOWS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 7) NO PLUMBING PLANS SUBMITTED.A
 SEPARATE PLUMBING PERMIT APPLICATION
 WILL BE REQUIRED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By rbrown Date 2004-10-14 Time 18:10 Rev Time 0.25
Received By dpalmer Date 2004-10-05 Time 13:30 Sent To B
Notes
2004-10-05 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT DRAWING/PLAN SHOW-
 -ING MIN ELECTRICAL REQUIRED FOR NEW
 CABANA. RECEPTS/LTS ETC. SD'S
 210.52,210.70
  
 2)NOTE: PLEASE SHOW/INDICATE HOW DETACH-
 -ED BLDG/GARAGE IS FED OR HOW THIS WILL
 BE FED. NEW PANEL?
 MEANS OF DISC, GROUNDING, FEEDERS, AND
 CONDUCTORS. 215.5,225.31,250.32
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-14 Cont ID  
Sent By mjacobs Date 2004-09-22 Time 11:33 Rev Time 0.00
Received By rbrown Date 2004-09-22 Time 11:33 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-10-14 Cont ID  
Sent By kstevens Date 2004-10-14 Time 17:46 Rev Time 0.25
Received By kstevens Date 2004-10-14 Time 17:46 Sent To  
Notes
2004-10-14 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 1 Status F Date 2004-09-22 Cont ID  
Sent By mmclean Date 2004-09-22 Time 11:16 Rev Time 0.00
Received By mmclean Date 2004-09-22 Time 11:16 Sent To I
Notes
2004-09-22 00:00:00DENIED, NEED TO PROVIDE A FULL SIZE
 SURVEY SHOWING THE DIMENSION OF LOT &
 LOCATION OF STREET AND THE GARAGE.A
 FLOOR PLANS SHOULD BE PROVIDED WITH NO
 LIVING SPACE).