Plan Review Details - Permit 04090541
Plan Review Stops For Permit 04090541
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-16 Cont ID  
Sent By jwitmer Date 2005-03-16 Time 16:37 Rev Time 0.77
Received By jwitmer Date 2005-03-16 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-25 Cont ID  
Sent By jwitmer Date 2005-01-25 Time 15:58 Rev Time 1.11
Received By jwitmer Date 2005-01-25 Time 15:58 Sent To  
Notes
2005-01-25 00:00:00BUILDING PLAN REVIEW
 PERMIT:04090541
 ADD: 747 N CONGRESS
 CONT: WCI
 TEL: (561)662-3569
 BLD CODE= 2001 FLORIDA BUILDING CODE *
 WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMMENT# 4 FROM THE PREVIOUS REVIEW
 SHEET S-2 WIRE LATH FASTENING SCHEDULE.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
 PROVIDE THE ACTUAL DIAMETER & LENGHT
 OF NAILSREQUIRED FOR FLAT WIRE LATH
 AND RIBBED LATH BOTH FOR HORIZONTAL AND
 VERTICAL SURFACES. WE ALSO NEED TO KNOW
 THE WEIGHT OF THE WIRE LATH SPECIFIED
 FOR HRIZONTAL RUNS FOR SPAN LIMITATION.
 THE CODE REFERS YOU TO ASTM C-1063 TO
 LOCATE THE REQUIRED SPANS WEIGHT AND
 NAIL PENETRATION REQUIRED FOR EACH
 APPLICATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 09:40 Rev Time 1.11
Received By jwitmer Date 2004-10-19 Time 09:40 Sent To  
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090541
 ADD: 747 N CONGRESS
 CONT: WCI COMMUNITIES
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE IS A DIFFERENCE IN THE ORIGINAL
 PROPERTY CONTROL NUMBER AND THE CURRENT
 NUMBER ON THE PROPERTY APPRAISERS SITE,
 INFORMATION AS TO WAS THE PROPRETY
 REPLATED?
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4) SHEET S2 FASTENER SCHEDULE: WIRE LATH
 & 3/8" METAL RIB LATH THE SECTIONS
 QOUTED 2507 ARE THE HIGH VELOCITY HURRI-
 CANE ZONE. THE CORRECT SECTION IS
 2504.2.2 INSTALLATION OF EXTERIOR LATH-
 ING AND FRAMING SHALL COMPLY WITH ASTM
 C-1063.THE FIRST QUESTION IS FOR THE
 WIRE LATH, DIAMOND MESH WHAT WILL THE
 MINIMUM WEIGHT BE OF THE METAL PLASTER
 BASE? SEE FOOTNOTE "D" ON VERTICAL APPLI
 CATIONS, WIRE LATH SHALL BE FURRED AWAY
 FROM VERTICAL SUPPORTS OR SOLID SHEATH-
 ING AT LEAST 1/4". ONCE THE MINIMUM
 WEIGHT IS KNOWN WHAT IS THE MAXIMUM
 CENTER TO CENTER, WALLS AND CEILINGS.
 CORRECT MINIMUM EMBEDMENT FOR VERTICAL
 AND HORIZONTAL APPLICATIONS AND SPACING
 OF FASTENER.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS- HIGHLIGHT IF 1000 OR
 2000 SERIES WINDOWS WILL BE USED AND IF
 WINDOWS WILL BE IMPACT OR NON-IMPACT.
 B) EXTERIOR DOORS
 C) STORM SHUTTERS
 D) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 E) PANEL WALLS- SOFFITS
 F) ROOFING ASSEMBLIES
  
 6) ATTIC AREA OF THE GUARD HOUSE, WILL
 THERE BE STORAGE? DESIGN FOR 125LBS/ FT?
  
 7) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 471.025 ORIGINAL SIGNATURES REQUIRED,
 NO RUBBER STAMP SIGNATURES.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By dpalmer Date 2005-01-21 Time 11:20 Rev Time 0.33
Received By dpalmer Date 2005-01-21 Time 11:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 19:35 Rev Time 0.00
Received By jwitmer Date 2005-03-16 Time 16:37 Sent To  
Notes
2004-10-05 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS PME ARE CONTAIN
 A "RUBBERSTAMP" FOR THE REQUIRED
 SIGNATURE OF THE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025. THIS IS REQUIRED
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE 250.24, 250.6, AN
 EQUIPMENT GROUNDING CONDUCTOR IS NOT TO
 BE INSTALLED AFTER METER AND BEFORE THE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE VERIFY IF CWP IS "METAL/
 COPPER, IF SO, PLEASE ALSO INCLUDE AS
 PART IF THE GROUDING ELECTRODE SYSTEM.
  
 4)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED IN TITLE BLOCK.
 THIS HAS BEEN REQUESTED ON PREVIOUS
 REVIEWS UNDER OTHER PERMITS.
 PLEASE ALSO SEE FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-03-16 Cont ID  
Sent By jwitmer Date 2005-03-16 Time 16:37 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 15:05 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 15:05 Sent To Z
Notes
2005-02-28 00:00:00TO "Z"BOX/OFF BD#36

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-22 Cont ID  
Sent By mjacobs Date 2005-02-22 Time 09:33 Rev Time 0.00
Received By mjacobs Date 2005-02-22 Time 09:32 Sent To  
Notes
2005-02-22 00:00:00TO "COMM BD#36"/REV.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 16:00 Sent To  
Notes
2005-02-15 00:00:00TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 12:32 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 12:32 Sent To  
Notes
2005-01-14 00:00:00TO "COMM BD#45"/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-02-22 Cont ID  
Sent By mjacobs Date 2004-10-20 Time 08:55 Rev Time 0.00
Received By mjacobs Date 2004-09-22 Time 14:43 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#54

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 16:10 Rev Time 0.40
Received By pkrauss Date 2005-01-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By pkrauss Date 2004-10-15 Time 14:00 Rev Time 0.40
Received By pkrauss Date 2004-10-15 Time 13:45 Sent To  
Notes
2004-10-15 00:00:00DENIED:
 ORIGINAL SIGNATURE REQUIRED, STAMPED
 SIGNATURE IS UNACCEPTABLE IN ACCORDANCE
 WITH FS 471.025.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-16 Cont ID  
Sent By kstevens Date 2005-02-16 Time 18:24 Rev Time 0.48
Received By kstevens Date 2005-02-16 Time 18:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-31 Cont ID  
Sent By kstevens Date 2005-01-31 Time 08:25 Rev Time 0.64
Received By kstevens Date 2005-01-28 Time 16:55 Sent To  
Notes
2005-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT P-1 FULL OPEN VALVES SHALL BE
 INSTALLED ON THE TOP OF EVERY WATER
 DOWN-FEED PIPE. SECTION 606.1(4).
 2) FROM PREVIOUS REVIEW: SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.4 GRAB BARS
 11-4.16.5 FLUSH CONTROLS
 11-4.19.2 HEIGHT & CLEARANCES
 11-4.19.4 EXPOSED PIPES AND SURFACES
 11-4.19.5 FAUCETS
 WATER CLOSET SHALL BE 18" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. FIG.
 28
 LAV SHALL BE MINIMUM OF 15" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE 30" MEASURMENT OF THE
 CLEAR FLOOR SPACE.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-15 Time 21:42 Rev Time 0.50
Received By kstevens Date 2004-10-15 Time 21:41 Sent To  
Notes
2004-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM SHOWING ALL
 PIPE SIZES, POINT OF CONNECTION, RPZ
 BACKFLOW ECT. SECTION 104.3.1.1
 2) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 11-4.15, 11-4.16, 11-4.19
 AND 11-4.22 AND ALL SUBSECTIONS. - SHOW
 TURNING AREA REQUIRED IN TOILET ROOM PER
 SECTION 11-4.22.3
 3)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)/FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - ENGINEERS
 INDICATE A PARTNERSHIP AND REQUIRE THE
 CERTIFICATE OF AUTHORIZATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-03-11 Cont ID  
Sent By eschneid Date 2005-03-11 Time 15:15 Rev Time 0.25
Received By eschneid Date 2005-03-11 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-02-04 Cont ID  
Sent By eschneid Date 2005-02-04 Time 11:30 Rev Time 0.50
Received By eschneid Date 2005-02-04 Time 11:00 Sent To  
Notes
2005-02-04 00:00:001. NEED TO INCLUDE A SITE PLAN SHOWING
 THE GATEHOUSE LOCATION IN RELATION TO
 CONGRESS AVE, AND THE FACE OF BUILDINGS
 14C AND 15C.
 2. THE GROUND FLOOR PLAN ON SHEET A-1
 DOES NOT SHOW THE APPROVED DIMENSIONS OF
 THE LANDSCAPED/CURBED AREA IN FRONT OF
 (EAST SIDE) OF THE GATEHOUSE.APPROVED
 SITE AND LANDSCAPE PLANS SHOW A 13'6
 AREA WHILE SHEET A-1 (AND OTHER PERMIT
 PLANS) SHOW 23'6.
 3. THE REVISED GROUND FLOOR PLAN SHALL
 SHOW THE ENTIRE LANDSCAPED/CURB AREA ON
 WHICH THE GATEHOUSE SITS.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-27 Cont ID  
Sent By eschneid Date 2004-10-27 Time 13:57 Rev Time 0.50
Received By eschneid Date 2004-10-27 Time 13:57 Sent To  
Notes
2004-10-27 00:00:00SIGN NOT ALLOWED ON EAST FACADE.
 LANDSCAPE PLANS SHOW PLANTING OUTSIDE OF
 THE CURB LINE.
 LANDSCAPE PLANS DO NOT MATCH THE PLANS
 UNDER REVIEW FOR THE DOUBLE GATE AMEND.
 SITE PLAN SHOWING GUARDHOUSE SETBACKS
 REQUIRED.