Plan Review Details - Permit 04090472
Plan Review Stops For Permit 04090472
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 15:55 Rev Time 0.99
Received By jwitmer Date 2004-10-19 Time 15:49 Sent To  
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090472
 ADD: 515 N FLAGLER# 402
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: REVIEWED/ PROVISO
  
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-26 Cont ID  
Sent By dpalmer Date 2005-01-26 Time 10:50 Rev Time 0.30
Received By dpalmer Date 2005-01-26 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 07:05 Rev Time 0.33
Received By dpalmer Date 2004-09-24 Time 06:55 Sent To  
Notes
2004-09-24 00:00:00********* PROVISO/ REVISION *********
  
 1)NOTE: PLEASE SEE PANEL/METER ETC IS
 SHOWN AS 200A WITH A LOAD CALCULATION
 SHOWING 201A LOAD.
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 LOAD SHOWN IS FOR CONNECTED LOAD AT THIS
 TIME.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER FIRST MEANS
 OF DISCONNECT/TRANSFORMERS ETC.
 250.24,250.110,250.122 AND 250.30
  
 REVISE AND SUBMIT BEFORE ROUGH ALONG
 WITH ANY OTHER REVISIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-28 Cont ID  
Sent By mcarsill Date 2004-10-28 Time 16:08 Rev Time 0.00
Received By mcarsill Date 2004-10-28 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 10:51 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 10:51 Sent To E
Notes
2005-01-18 00:00:00TO "DP" DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 14:22 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#46

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 14:28 Rev Time 0.40
Received By pkrauss Date 2004-10-08 Time 14:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-15 Time 21:32 Rev Time 0.25
Received By kstevens Date 2004-10-15 Time 21:32 Sent To  
Notes
2004-10-15 00:00:00NO PLUMBING WORK SHOWN