Plan Review Details - Permit 04090403
Plan Review Stops For Permit 04090403
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 07:44 Rev Time 1.11
Received By jwitmer Date 2004-10-18 Time 09:43 Sent To PC
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090403
 ADD: 7750 OKKEECHOBEE BLVD
 CONT: SPANISH RIVER
 TEL: (561)723-9719
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS DO NOT INDICATE IF THE FRONT AND
 REAR DOORS ARE EXISTING OR NEW, IF NEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT DOORS
 B) STOREFRONT FIXED GLASS
 C) STEEL DOOR
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) 61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-03 Cont ID  
Sent By dpalmer Date 2004-11-03 Time 15:50 Rev Time 0.33
Received By dpalmer Date 2004-11-03 Time 15:29 Sent To  
Notes
2004-11-03 00:00:00ALL COMMENTS ADDRESSED, ELECTRICAL
 SHEETS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-23 Cont ID  
Sent By dpalmer Date 2004-09-23 Time 06:25 Rev Time 0.50
Received By dpalmer Date 2004-09-23 Time 06:18 Sent To  
Notes
2004-09-23 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SUBMIT FOR MAIN DISC ALSO.
  
 2)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 WINDOW RECEPTS> (ADVERTISEMENT) ETC.
  
 3)NOTE: PLEASE SEE IF THERE IS A MAIN '
 DISCONNECT ON THE LINE SIDE OF MAIN
 SHOWN, PLEASE SEE 250.24 FOR EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED.
  
 4)NOTE: PLEASE PROVIDE CONDUCTOR SIZES
 FROM WIREWAY TO METER/ MAIN. CONDUIT?
 215.5
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS, INCLUDING EM/EXT LTS. PLEASE
 ALSO SEE 700.12E
  
 6)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL INFORMATION REQUIRED ON TITLE BLOCK
 FOR ARCH/ARCH FIRM.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 CERTIFICATE OF AUTHRIZATION # REQUIRED
 FOR FIRM.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-21 Cont ID  
Sent By pkrauss Date 2004-10-21 Time 12:19 Rev Time 0.00
Received By mcarsill Date 2004-11-10 Time 13:02 Sent To  
Notes
2004-10-21 00:00:00APPROVED PER MIKE CARSILLO 10-1-04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:41 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:41 Sent To  
Notes
2004-10-29 00:00:00TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-21 Cont ID  
Sent By pkrauss Date 2004-10-21 Time 12:20 Rev Time 0.00
Received By pkrauss Date 2004-09-20 Time 13:44 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#30`

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-21 Cont ID  
Sent By pkrauss Date 2004-10-21 Time 12:07 Rev Time 0.40
Received By pkrauss Date 2004-10-21 Time 12:07 Sent To  
Notes
2004-10-21 00:00:00DENIED:
 SEE COMMENT #6 BY DEWEY PALMER ELEC PLAN
 REVIEW & COMMENT #3 BY KENNY STEVENS
 PLUMBING PLAN REVIEW.PLANS ARE OTHER
 WISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-12 Cont ID  
Sent By kstevens Date 2004-10-12 Time 07:52 Rev Time 1.00
Received By kstevens Date 2004-10-12 Time 07:52 Sent To  
Notes
2004-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. (ALSO SEE 410.1)
 2) SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE
 FIXTURES. SECTION 11-4.1.2, 11-4.19.3,
 AND 11-4.22.3. ALSO SHOW TURNING AREA
 REQUIRED PER 11-4.22.3.
 3) PER FAC 61G1-16.004(2)(4) THE LICENSE
 OF THE FIRM AND THE DATE PREPARED ARE
 REQUIRED IN THE TITLE BLOCK. FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]