Plan Review Details - Permit 04090393
Plan Review Stops For Permit 04090393
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2005-03-15 Time 10:50 Sent To PC
Notes
2005-03-10 00:00:00PERMIT 04090393
 BLDG # 31
 4610 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 07:20 Rev Time 0.20
Received By dpalmer Date 2005-03-08 Time 07:19 Sent To  
Notes
2005-03-08 00:00:00BLDG TYPE IV
  
 ALL THREE SETS OF ELECTRICAL SHEETS
 STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 05:14 Rev Time 0.00
Received By dpalmer Date 2005-02-15 Time 05:14 Sent To  
Notes
2005-02-15 00:00:00REDLINED FEEDER(S), N-SHOWN AS #3. #2
 MIN ALUM AS NOTED ON ED-1
 310-2B1 LOCAL AMENDMENTS.
  
 REDLINED A/C OCP ON ED-8
  
 THIS IS FOR ALL BLDGS AND TYPES.
  
 **ELECTRICAL PLANS STAMPED **

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 10:58 Rev Time 0.25
Received By dpalmer Date 2004-12-30 Time 10:58 Sent To  
Notes
2004-12-30 00:00:00SEE NOTES UNDER 04090380

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 13:08 Rev Time 2.00
Received By dpalmer Date 2004-10-08 Time 13:08 Sent To  
Notes
2004-10-08 00:00:00PLEASE SEE REVIEW UNDER 04090380

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 10:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-09-30 Cont ID  
Sent By mamini Date 2004-09-30 Time 14:57 Rev Time 1.00
Received By mamini Date 2004-09-30 Time 14:57 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT # 04120218 FOR UNDERGROUND
 UTILITIES AND SITE WORK, PHASE II.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 15:34 Rev Time 0.00
Received By nmccray Date 2005-03-01 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 12:14 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 12:14 Sent To  
Notes
2004-12-07 00:00:00SEE NOTES ON PERMITS
 04090383 TYPE I BLDG
 04090363 TYPE II BLDG
 04090369 TYPE III BLDG

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 08:24 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 08:24 Sent To  
Notes
2005-01-03 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 16:40 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#55/4 ROLLS & 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By hmoser Date 2006-02-27 Time 17:36 Rev Time 0.00
Received By hmoser Date 2006-02-27 Time 17:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 12:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:00MASTER 04090380

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 13:38 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 13:38 Sent To  
Notes
2005-01-10 00:00:00DENIED:TYPE IV / BUILDING #31
 COMMENT #1 & 3 FROM REVIEW DATED
 10-22-04 WERE NOT ADDRESSED.SEE
 PERMIT 04090380.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 06:52 Rev Time 0.15
Received By pkrauss Date 2004-10-25 Time 06:52 Sent To  
Notes
2004-10-25 00:00:00DENIED:TYPE IV BUILDING #31
 SEE COMMENTS ON PERMIT 03090380

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 09:19 Rev Time 0.25
Received By kstevens Date 2005-02-15 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By kstevens Date 2004-10-20 Time 10:12 Rev Time 0.25
Received By kstevens Date 2004-10-20 Time 10:12 Sent To  
Notes
2004-10-20 00:00:00DENIED
  
  
  
 SEE COMMENTS FROM PERMIT #04090380
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 12:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:0001-14-05 PLANS SIGNED BY M MCLEAN