Plan Review Details - Permit 04090389
Plan Review Stops For Permit 04090389
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 14:50 Rev Time 2.22
Received By jwitmer Date 2005-03-10 Time 14:50 Sent To PC
Notes
2005-03-10 00:00:00PERMIT 04090389
 BLDG # 27
 4625 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-27 Cont ID  
Sent By jwitmer Date 2004-10-27 Time 10:16 Rev Time 2.22
Received By jwitmer Date 2004-10-27 Time 10:16 Sent To  
Notes
2004-10-27 00:00:00SEE PERMIT 04090363 TYPE II BLDG FOR A
 COMPLETE LIST OF BUILDING COMMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-07 Cont ID  
Sent By dpalmer Date 2005-03-07 Time 18:09 Rev Time 0.25
Received By dpalmer Date 2005-03-07 Time 18:09 Sent To  
Notes
2005-03-07 00:00:00BLDG TYPE II
  
 ELECTRICAL SHEETS STAMPED FOR ALL THREE
 SETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 06:05 Rev Time 0.00
Received By dpalmer Date 2005-02-15 Time 06:05 Sent To  
Notes
2005-02-15 00:00:00******* UNSAT *****
  
  
  
  
 1)NOTE: PLEASE SEE OCP FOR SOME A/C
 UNITS HAVE NOT BEEN CHANGED.
  
 3)NOTE: PLEASE SEE MIN ALUM TO BE #2, #3
 SHOWN ON FEEDERS.
  
 4)NOTE: PLEASE SEE AS-1 STILL REFERENCES
 WRONG ELECTRICAL CODE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 09:13 Rev Time 0.00
Received By dpalmer Date 2004-12-30 Time 09:13 Sent To  
Notes
2004-12-30 00:00:00SEE NOTES UNDER 04090389

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-07 Cont ID  
Sent By dpalmer Date 2004-10-07 Time 15:03 Rev Time 0.50
Received By dpalmer Date 2004-10-07 Time 15:03 Sent To  
Notes
2004-10-07 00:00:00** PLEASE SEE NOTES UNDER 04090363

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-09-30 Cont ID  
Sent By mamini Date 2004-09-30 Time 14:53 Rev Time 1.00
Received By mamini Date 2004-09-30 Time 14:53 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT# 04120218 FOR
 UNDERGROUND UTILITIES AND SITE WORK,
 PHASE II.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 15:53 Rev Time 0.00
Received By nmccray Date 2005-03-01 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 10:39 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 10:39 Sent To  
Notes
2004-12-07 00:00:00SEE NOTES ON PERMIT 04090363

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 08:06 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 08:06 Sent To  
Notes
2005-01-03 00:00:00TO "COMM BD#60"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 16:37 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#55/4 ROLLS & 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By hmoser Date 2006-02-27 Time 17:26 Rev Time 0.00
Received By hmoser Date 2006-02-27 Time 17:26 Sent To  
Notes
2006-02-27 00:00:00LETTER WITH PERMIT 04090363

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 11:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:00MASTERTYPE II 04090363

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 12:15 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 12:12 Sent To  
Notes
2005-01-10 00:00:00DENIED: TYPE II BUILDING #27
 COMMENT #1 & 3 FROM REVIEW DATED
 10-22-04 WERE NOT ADDRESSED.SEE PERMIT
 04094363.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By pkrauss Date 2004-10-22 Time 07:36 Rev Time 0.20
Received By pkrauss Date 2004-10-22 Time 07:36 Sent To  
Notes
2004-10-22 00:00:00DENIED:TYPE II BUILDING #27
 SEE COMMENTS ON PERMIT 04090363

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 06:57 Rev Time 0.25
Received By kstevens Date 2005-02-15 Time 06:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By kstevens Date 2004-10-19 Time 07:31 Rev Time 0.25
Received By kstevens Date 2004-10-19 Time 07:31 Sent To  
Notes
2004-10-19 00:00:00DENIED
  
  
 SEE COMMENTS FROM PERMIT #04090363
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 11:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:00SIGNED ON PLAN 1-14-05 M MCLEAN