Plan Review Details - Permit 04090382
Plan Review Stops For Permit 04090382
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2005-03-15 Time 10:47 Sent To PC
Notes
2005-03-11 00:00:00 
 PERMIT 04090382
 BLDG # 21
 4655 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-10 Cont ID  
Sent By jwitmer Date 2005-03-10 Time 15:08 Rev Time 2.22
Received By jwitmer Date 2005-03-10 Time 15:08 Sent To PC
Notes
2005-03-10 00:00:00PERMIT 04090382
 BLDG # 21
 4655 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 07:16 Rev Time 0.25
Received By dpalmer Date 2005-03-08 Time 07:16 Sent To  
Notes
2005-03-08 00:00:00BLDG TYPE IV
  
 ALL THREE SETS OF ELECTRICAL SHEETS
 STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 05:11 Rev Time 0.25
Received By dpalmer Date 2005-02-15 Time 05:11 Sent To  
Notes
2005-02-15 00:00:00REDLINED FEEDER(S), N-SHOWN AS #3. #2
 MIN ALUM AS NOTED ON ED-1
 310-2B1 LOCAL AMENDMENTS.
  
 REDLINED A/C OCP ON ED-8
  
 THIS IS FOR ALL BLDGS AND TYPES.
  
 **ELECTRICAL PLANS STAMPED **

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 10:53 Rev Time 0.20
Received By dpalmer Date 2004-12-30 Time 10:52 Sent To  
Notes
2004-12-30 00:00:00SEE REVIEW UNDER 04090380

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 13:10 Rev Time 1.00
Received By dpalmer Date 2004-10-08 Time 13:10 Sent To  
Notes
2004-10-08 00:00:00PLEASE SEE NOTES UNDER 04090380

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-09-30 Cont ID  
Sent By mamini Date 2004-09-30 Time 14:45 Rev Time 1.00
Received By mamini Date 2004-09-30 Time 14:45 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT# 04120218 FOR
 UNDERGROUND UTILITIES AND SITE WORK,
 PHASE II.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 15:31 Rev Time 0.00
Received By nmccray Date 2005-03-01 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-01-25 Cont ID  
Sent By mcarsill Date 2005-01-25 Time 09:03 Rev Time 0.00
Received By mcarsill Date 2005-01-25 Time 09:02 Sent To  
Notes
2005-01-25 00:00:001. FIRE SPRINKLER CALCUALTIONS IN
 SUBMITTAL PACKAGE STILL DISPLAYS
 A SAFETY MARGIN OF LESS THAN 5LBS.
 PREVIOUS REVIEW COMMENTS INDICATED
 THAT THIS IS NOT ACCEPTABLE. PLEASE
 REVISE.
  
 2. NO EXIT SIGNS SHOWN ON FIRST FLOOR.
  
 THESE NOTES ALSO APPLY TO
  
 04090388
 04090392
 04090393
  
 TYPE IV BUILDINGS
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 12:05 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 12:05 Sent To  
Notes
2004-12-07 00:00:00SEE NOTES ON PERMITS
 04090383 TYPE I BLDG
 04090363 TYPE II BLDG
 04090369 TYPE III BLDG

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 08:19 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 08:19 Sent To  
Notes
2005-01-03 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 16:34 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#55/4 ROLLS & 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By hmoser Date 2006-02-27 Time 17:11 Rev Time 0.00
Received By hmoser Date 2006-02-27 Time 17:11 Sent To  
Notes
2006-02-27 00:00:00LETTER FOR CHANGE OF EQUIPMENT.LETTER
 WITH THE PLANS PERMIT # 04090363

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 12:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:00MASTER 04090380

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 13:28 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 13:27 Sent To  
Notes
2005-01-10 00:00:00DENIED:TYPE IV / BUILDING #21
 COMMENT #1 & 3 FROM REVIEW DATED
 10-22-04 WERE NOT ADDRESSED.SEE PERMIT
 04090380.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 06:46 Rev Time 0.15
Received By pkrauss Date 2004-10-25 Time 06:46 Sent To  
Notes
2004-10-25 00:00:00DENIED:TYPE IV BUILDING #21
 SEE COMMENTS ON PERMIT 04090380

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 09:15 Rev Time 0.25
Received By kstevens Date 2005-02-15 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By kstevens Date 2004-10-20 Time 10:09 Rev Time 0.25
Received By kstevens Date 2004-10-20 Time 10:08 Sent To  
Notes
2004-10-20 00:00:00DENIED
  
  
 SEE COMMENTS FROM PERMIT #04090380
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 12:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-03-15 00:00:0001-14-05 PLANS SIGNED BY M MCLEAN