Plan Review Details - Permit 04090380
Plan Review Stops For Permit 04090380
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 07:46 Rev Time 0.55
Received By jwitmer Date 2006-07-19 Time 07:45 Sent To  
Notes
2006-07-19 00:00:00DAIL REPORT FOR WEEK OF 6-05-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 07:38 Rev Time 0.56
Received By jwitmer Date 2006-07-19 Time 07:38 Sent To PC
Notes
2006-07-19 00:00:00DAILY REPORTS WEEK OF 5-15-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-07-25 Cont ID  
Sent By jwitmer Date 2005-07-25 Time 13:09 Rev Time 0.33
Received By jwitmer Date 2005-07-25 Time 13:09 Sent To PC
Notes
2005-07-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090380
 ADD: 4680 PORTOFINO WAY BLD# 20
 CONT: EPOCH
 TEL: (561)#718-0302
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 BEARING CAPACITY CERTIFICATION
 1ST REVIEW
 ACTION: DENIED
  
 1) THE CERTIFICATION LETTER ADDRESSES
 THE MAXIMUM ALLOWABLE SOILS BEARING
 CAPACITY. 1804.2.2 DEALING WITH
 QUESTIONABLE SOILS DEALS WITH THE
 MINIMUM SAFE BEARING VALUE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-13 Cont ID  
Sent By jwitmer Date 2005-06-13 Time 13:49 Rev Time 0.55
Received By jwitmer Date 2005-06-13 Time 13:49 Sent To  
Notes
2005-06-13 00:00:00SUBMITTAL# 6, SHORING PLANSOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2005-03-15 Time 10:43 Sent To PC
Notes
2005-03-11 00:00:00 
 PERMIT 04090380, 04090382, 04090388,
 04090392 & 04090393
  
 BLDG # 20, 21, 26, 30& 31
  
 4680, 4655, 4630, 4620 & 4610 PORTOFINO
 WAY
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-10 Cont ID  
Sent By jwitmer Date 2005-03-10 Time 15:07 Rev Time 2.22
Received By jwitmer Date 2005-03-10 Time 15:07 Sent To PC
Notes
2005-03-10 00:00:00PERMIT 04090380
 BLDG # 20
 4680 PORTOFINO WAY
  
 03-09-05 BUILDING PLANS ARE CODE
 COMPLIANT/ REQUIRES IMPACT FEES/ &
 REMAINDER OF PERMIT PAYMENT BEFORE
 ISSUANCE.
  
 BUILDING PROVISO:
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-02-15 Cont ID  
Sent By jwitmer Date 2005-02-15 Time 11:35 Rev Time 1.11
Received By jwitmer Date 2005-02-15 Time 11:35 Sent To  
Notes
2005-02-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090380
 ADD: MAASTER BLDG TYPE IV
 CONT:EPOCH
 TEL: (561)723-0152
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 COMMNETS FOR BLDG TYPE IV ARE THE SAME
 FOR BLDG TYPE I SEE 04080383.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-19 Cont ID  
Sent By jwitmer Date 2005-01-19 Time 16:14 Rev Time 1.00
Received By jwitmer Date 2005-01-19 Time 16:14 Sent To  
Notes
2005-01-19 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW: 04090380
 ADD:SITE 4600 PORTOFINO WAY
 CONT:EPOCH PROPERTIES
 TEL: (407)723-0152
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 SAME COMMENTS AS TYPE I BLDG.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By jwitmer Date 2004-10-28 Time 12:21 Rev Time 2.22
Received By jwitmer Date 2004-10-28 Time 12:21 Sent To  
Notes
2004-10-28 00:00:00BUILDING PLAN REVIEW
  
 PORTOFINO PHASE II
 BUILDING TYPE IV
  
 PERMIT: 04090380BLDG# 20
 ADD: 4680 PORTOFINO WAY
 PERMIT: 04090382BLDG#21
 ADD: 4655 PORTOFINO WAY
 PERMIT: 04090388BLDG# 26
 ADD: 4630 PORTOFINO WAY
 PERMIT: 04090392BLDG# 30
 ADD: 4620 PORTOFINO WAY
 PERMIT: 04090393BLDG# 31
 ADD: 4610 PORTOFINO WAY
  
 CONT: EPOCH PROPERTIES
 TEL: (407)718-8932
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)SHEET AS-1, BLDG# 30 FOOTPRINT APPEARS
 TO BE WITHIN 15' OFTHE PROPERTY LINE.
 IF THIS IS TRUE SINCE IT IS A 1HR PROTEC
 TED BUILDING 705.1.1.2. OPENING PROTEC-
 TIVES WOULD BE REQUIRED FOR ANY OPENING
 WITHIN THE 15' OF THE PROPERTY LINE.
  
 SEE COMMENTS FROM TYPE I-III BLDGS FOR
 THE REMAINDER OF COMMENTS.
 TYPE I BUILD- 04090383
 TYPE II- 04090363
 TYPE III - 04090369
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 07:14 Rev Time 0.50
Received By dpalmer Date 2005-03-08 Time 07:14 Sent To  
Notes
2005-03-08 00:00:00BLDG TYPE IV
  
 ALL THREE SETS OF ELECTRICAL SHEETS
 STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 05:08 Rev Time 0.30
Received By dpalmer Date 2005-02-15 Time 04:56 Sent To  
Notes
2005-02-15 00:00:00REDLINED FEEDER(S), N-SHOWN AS #3. #2
 MIN ALUM AS NOTED ON ED-1
 310-2B1 LOCAL AMENDMENTS.
  
 REDLINED A/C OCP ON ED-8
  
 AS-1 WRONG ELEC CODE.
  
 THIS IS FOR ALL BLDGS AND TYPES.
  
 **ELECTRICAL PLANS STAMPED **

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 10:47 Rev Time 1.50
Received By dpalmer Date 2004-12-30 Time 10:47 Sent To  
Notes
2004-12-30 00:00:00********* UNSAT 2ND REVIEW *********
  
 BLDG TYPE IV
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1: NO. PLEASE SEE PLANS
 STILL REFERENCE THE 2001 NEC. THIS WAS
 CORRECTED ON ED-1, PLEASE SEE AS-1
 PLEASE ALSO SEE ED-1, CODE REFERENCED ON
 PREVIOUS PLANS FROM THE 96 NEC WAS
 CHANGED, HOWEVER CODE IN THE 2002 WHICH
 CORRELATES WITH SAME CODE REFERENCED ON
 PREVIOUS PLANS(96) IS 250.50 FOR
 GROUNDING ELECTRODE SYSTEMS.
  
 2)NOTE: NOTE #2, YES? PLEASE SEE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO MAIN WAS REMOVED AS REQUIRED UNDER
 250.6,250.24, HOWEVER THE EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 10HP PUMP WAS ALSO REMOVED. PLEASE SEE
 250.122 FOR SIZING.
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS
 NOTES, MANY OF THE UNITS ARE STILL
 SHOWING SD'S ON MORE THAN ONE CIRCUIT.
 THESE ARE REQUIRED TO WIRED "IN-LINE",
 IF WIRED AS SHOWN, THEN THERE WOULD BE
 220VON 120V SD'S. PLEASE SEE PLANS, MANY
 OF THESE HAVE BEEN REDLINED ON ONE SET.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE THERE ARE
 UNITS WHICH DO NOT MEET 424.3B
 THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS.
 PLEASE SEE THERE WERE MORE THAN JUST THE
 8KW UNITS.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK
  
 9)NOTE: NOTE #9 OK
  
 10)NOTE: NOTE #10 OK
  
 11)NOTE: NOTE #11 OK
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 13:13 Rev Time 2.00
Received By dpalmer Date 2004-10-08 Time 13:12 Sent To  
Notes
2004-10-08 00:00:00********** UNSAT ****************
  
 BLDG TYPE IV, BLDG #'S,20,21,26,30,31
  
 1)NOTE: PLEASE SEE PLANS TO REFERENCE
 2002 NEC INCLUDING ANY CODES REFERENCED
 ON PLANS.
 PLEASE SEE GROUNDING DETAIL ON ED-1.
  
 2)NOTE: PLEASE SEE SITE RISER DIAGRAM,
 EQUIPMENT GRND FROM METER TO MAIN.
 250.6,250.24, THIS SHALL NOT BE INSTALL-
 -ED.
  
 3)NOTE: PLEASE COMPLETE ALL CIRCUITING
 IN UNITS. LIV RM RECEPT/ALCOVE AND
 CLOSET RECEPT ABOVE DOOR.
  
 4)NOTE: LOCK-OFF DEVICE TO BE APPROVED
 BY THIS OFFICE. AHJ.
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.6.1.2
 PLEASE SEE MULTIPLE CIRCUITS FOR SD'S
 IN SOME UNITS. SD'S ARE TO BE WIRED
 IN-LINE. MULTIPLE CIRCUITS WOULD NOT
 BE POSSIBLE.
  
 6)NOTE: PLEASE SEE MIN OCP FOR AHU'S TO
 BE 125% PER 424.3B ONLY SOME OF THESE
 ARE NOT CORRECT.
  
 7)NOTE: PLEASE SEE 210.52G FOR RECEPT
 REQUIRED IN GARAGE. MUST ALSO BE GFI,
 210.8
  
 8)NOTE: PLEASE SEE 210.25 FOR ATTIC
 LTS FED FROM HOUSE PANEL CIRCUITS 9&11.
 IF THESE ARE AT EACH UNIT, THEN THAT
 INDIVIDUAL UNIT SHALL FEED EACH LT.
  
 9)NOTE: PLEASE NOTE OCP.BRKRS ON RISER/
 METER/MAIN.
  
 10)NOTE: PLEASE CORRELATE NOTES FROM
 ED-1 WITH PLANS/PANELS/FEEDERS WITH
 RESPECT TO ALUM AWG.
  
 11)NOTE: PLEASE SEE NOTE# 24 FOR
 VOLTAGE VERIFICATION.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-09-30 Cont ID  
Sent By mamini Date 2004-09-30 Time 10:41 Rev Time 1.00
Received By mamini Date 2004-09-30 Time 10:41 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT# 04120218 FOR
 UNDERGROUND UTILITIES AND SITE WORK,
 PHASE II.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 15:26 Rev Time 0.00
Received By nmccray Date 2005-03-01 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 12:00 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 12:00 Sent To  
Notes
2004-12-07 00:00:00SEE NOTES ON PERMIT
 04090383 TYPE I BLDG
 04090363 TYPE II BLDG
 04090369 TYPE III BLDG

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 08:15 Sent To  
Notes
2004-12-27 00:00:00TO "COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 13:23 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 13:23 Sent To B
Notes
2005-07-21 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 13:48 Rev Time 0.00
Received By shill Date 2005-06-10 Time 13:48 Sent To B
Notes
2005-06-10 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 09:19 Sent To  
Notes
2005-03-03 00:00:00TO "COMM" BD#30/
 COMM RACK 4 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-03 Cont ID  
Sent By mjacobs Date 2005-02-03 Time 13:35 Rev Time 0.00
Received By mjacobs Date 2005-02-03 Time 13:35 Sent To  
Notes
2005-02-03 00:00:00TO "COMM BD#33/RESUB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-02-03 Cont ID  
Sent By mjacobs Date 2004-10-28 Time 13:32 Rev Time 0.00
Received By mjacobs Date 2004-09-22 Time 16:33 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#55/4 ROLLS & 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By hmoser Date 2006-02-27 Time 16:57 Rev Time 0.00
Received By hmoser Date 2006-02-27 Time 16:57 Sent To  
Notes
2006-02-27 00:00:00LETTER REVISING EQUIPMENT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By pkrauss Date 2005-02-23 Time 13:35 Rev Time 0.45
Received By pkrauss Date 2005-02-23 Time 12:54 Sent To  
Notes
2005-02-23 00:00:00AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M)307.2.3.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 13:19 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 13:05 Sent To  
Notes
2005-01-10 00:00:00DENIED:TYPE IV / BUILDING #20
 COMMENT #1 & 3 FROM REVIEW DATED
 10-22-04.SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT(561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By pkrauss Date 2004-10-22 Time 09:58 Rev Time 1.00
Received By pkrauss Date 2004-10-22 Time 09:58 Sent To  
Notes
2004-10-22 00:00:00DENIED:TYPE IV BUILDING #20
 1.PER 2001 FBC(M) 601.4 EXCEPTION #2
 & 3, RETURN TRANSFER GRILLES SHALL BE
 SIZED AS FOLLOWS:
 RETURN TRANSFER - 50 SQ INCHES OF FREE
 AREA TO 100 CFM OF SUPPLY AIR TO THAT
 AREA.ALLL SUPPLY AIR INTO THE MASTER
 SUITE SHALL BE INCLUDED FOR PROPER
 SIZING.
 THE FOLLOWING UNITS ARE NOT SIZED
 PROPERLY - A-1 (DWG AC-U1), A-1LS (DWG
 AC-U4), B-2 (AC-U5).
  
 2.PLEASE NOTE, THE TOILET EXHAUST
 TERMINATION SHALL BE SCREENED, IN
 ACCORDANCE WITH 2001 FBC(M) 401.6.
 (DRYER EXHAUST NON-SCREENED).
  
 3.PLAN SHEET PD-1 CONDENSATE RISER,
 CONDENSATE SHALL TERMINATE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 09:14 Rev Time 0.25
Received By kstevens Date 2005-02-15 Time 09:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-22 Cont ID  
Sent By kstevens Date 2005-01-22 Time 14:13 Rev Time 1.25
Received By kstevens Date 2005-01-22 Time 14:13 Sent To  
Notes
2005-01-22 00:00:00DENIED
 REFERENCE: FHA-98 DESIGN MANUAL
  
 1) ALL SHEETS WITH FLOOR PLANS FOR
 HANDICAP ADAPTABLE UNITS:THE CLEAR
 FLOOR SPACE DIMENSIONS ARE TO BE
 APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE
 REQUIREMENTS AT TOILET ARE BEING MET.
 SEE PAGE 7.43 OF THE DESIGN MANUAL.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By kstevens Date 2004-10-19 Time 15:16 Rev Time 1.50
Received By kstevens Date 2004-10-19 Time 15:16 Sent To  
Notes
2004-10-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98(AMEND) DESIGN MANUAL
  
 1) SHT A-U14 DETAILS FOR BACKING FOR THE
 TUB, SHOWER, AND W/C SHALL REFLECT THE
 BACKING REQUIREMENTS IN FHA DESIGN MAN-
 UAL PAGES 6.4/6.5, 6.8/6.9/, & 6.12/6.13
  
 2) SHTS P-T41 & P-T41A BUILDING DRAIN DO
 NOT REFLECT THE RISER DIAGRAM ON SHT P-
 T4.3. CLEANOUTS ON DRAIN SHALL BE TWO
 WAY CLEANOUTS IN BLDG DRAIN NOT ON BRAN-
 CH LINES. SHT P-T41 SHOWS RISER P/2B
 THAT IS NOT SHOWN ON RISER. RISER DIAG-
 RAM SHOWS P/2B TAKEN OFF ON THE STACK.
 - SHT P-T14A SHOW RISER 2 & 2A WHERE THE
 RISER DIAGRAM SHOWS 2A & 2B. CLEANOUT
 SHALL BE IN BLDG. DRAIN NOT BRANCH LINE.
 SECTION 104.2.1 PLEASE CORRELATE RISER
 DIAGRAM WITH BLDG DRAIN LAYOUT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-18 Cont ID  
Sent By mmclean Date 2005-01-10 Time 08:48 Rev Time 0.00
Received By mmclean Date 2005-01-10 Time 08:47 Sent To  
Notes
2005-02-18 00:00:00JOSH LONG, PLANNER 822-1449.