Plan Review Details - Permit 04090369
Plan Review Stops For Permit 04090369
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 07:50 Rev Time 0.45
Received By jwitmer Date 2006-07-19 Time 07:50 Sent To  
Notes
2006-07-19 00:00:00DAILY REPORTS WEEK OF 6-19-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 09:31 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 09:19 Sent To PC
Notes
2005-08-28 00:00:0008-28-05 SUBMITTALS:
 TIE IN SURVEY BLDG# 19
 DENSITY REPORTS
 SOIL LETTERS
 TERMITE TREATMENT CERTIFICATE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-13 Cont ID  
Sent By jwitmer Date 2005-06-13 Time 13:46 Rev Time 0.55
Received By jwitmer Date 2005-06-13 Time 13:46 Sent To  
Notes
2005-06-13 00:00:00SUBMITTAL # 4, SHORING PLANSOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-15 Cont ID  
Sent By jwitmer Date 2005-03-15 Time 14:57 Rev Time 2.22
Received By jwitmer Date 2005-03-10 Time 14:56 Sent To PC
Notes
2005-03-10 00:00:00PERMIT #'S 04090369, 04090385, 04090390,
 04090394 & 04090400
  
 BLDGS # 19, 24,28,32 & 34
  
 4670, 4690, 4695,4710 & 4740 PORTOFINO
 WAY
  
 BUILDING PROVISO:
  
 1)TRUSS DRAWINGS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
 2)TRUSS DRAWINGS TO BE RESUBMITTED
 BEFORE THE TRUSS ANCHOR AND TRUSS
 FRAMING INSPECTION WITH CORRECTIONS.
 .TRUSS ENGINEERING - IF THEY USE
 "FBC2001/ANSI95" FOR THE CODE, ALONG
 WITH THE PLATES INCREASE OF 1.33, IT
 USES A STRESS INCREASE FOR STEEL WHICH
 IS NOT PERMISSIBLE.THIS IS PER MITEK,
 THE SOFTWARE COMPANY.THE CORRECT CODE
 REFERENCE IS "FBC2001/TPI2002", WHICH
 DOES NOT TAKE A STRESS INCREASE FOR
 STEEL EVEN IF A 1.33 PLATE INCREASE IS
 USED.
  
 3) TRUSS SHOP DRAWING TO BE ORIGINAL
 SIGNATURES AND SEAL OR HAVE A SIGNED &
 SEALED INDEX PAGE LISTING ALL DRAWINGS.
 SEE 61G15-23.002(2)
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-15 Cont ID  
Sent By jwitmer Date 2005-02-15 Time 11:06 Rev Time 1.11
Received By jwitmer Date 2005-02-15 Time 11:06 Sent To  
Notes
2005-02-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090369
 ADD: MASTER BLDG TYPE III
 CONT:EPOCH PROPERTIES
 TEL: (561)723-0152
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 THE COMMENTS FOR BLDG TYPE III ARE THE
 SAME AS FOR BLDG TYPE I.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-27 Cont ID  
Sent By jwitmer Date 2004-10-27 Time 11:08 Rev Time 2.22
Received By jwitmer Date 2004-10-27 Time 11:08 Sent To  
Notes
2004-10-27 00:00:00BUILDING PLAN REVIEW
  
 PORTOFINO PHASE II LAND, LTC
 BUILDING TYPE III
  
 PERMIT:04090369BLDG# 19
 ADD: 4670 PORTOFINO WAY
 PERMIT:04090385BLDG# 24
 ADD: 4690 PORTOFINO WAY
 PERMIT:04090390BLDG# 28
 ADD: 4695 PORTOFINO WAY
 PERMIT:04090394BLDG# 32
 ADD: 4710 PORTOFINO WAY
 PERMIT:04090400BLDG#34
 ADD: 4740 PORTOFINO WAY
 CONT: EPOCH PROPERTIES, INC
 TEL: (407)718-8932
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE INCORRECT PROPERTY CONTROL NUMBER
 WAAS USED ON THE PERMIT APPLICATION ALSO
 CORRECT THE ADDRESSES FOR PHASE II, USE
 THE LIST DATED SEPT 21/04.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) SHEET A-U13 DETAILS INDICATE THE USE
 OF SEMCO STRAPS. SEMCO WAS BOUGHT OUT IN
 1999 BY USP, UPDATE PLANS TO REFLECT THE
 MANUFACTURER, MODEL NUMBER AND LOADS TO
 BE IMPOSED.SHEET A-T1.3 HURRICANE STRAP/
 CONNECTIONNOTES ALSO REFRENCE PRODUCTS
 DELETE SEMCO FROM A-DT4.
  
 4) SHEET A-U13 DETAIL# 5, RISERS ARE TO
 COMPLY WITH 1007.3.1. RISERS SHALL BE A
 MAXIMUM OF 7".
  
 5) SHEET A-T3.3 ROOF SHEATHING NOTES, 23
 .22.2.5 DEALS WITH THE HIGH VELOCITY
 HURRICANE ZONES, 22306.1* ZONE 3 EDGE
 NAILING ZONES BETWEEN 25'-35' REQUIRE
 8D RING SHANK NAILS @ 4"O.C. EDGES &
 6"O.C. FOR INTERMEDIATES.
 ENGINEER OF RECORD WILL PROVIDE ADDITION
 AL INFORMATION ON ROOF SHEATHING NAILING
 ABOVE 35'.
  
 6) SHEET A-T3.3 HURRICANE STRAPS:
 A) USP TSU24/26 TUNNEL TIE NOT LISTED
 IN THE 2004 CATALOG.
 B) USP DTC LISTED IN THE USP CATALOG AS
 A ROOF TRUSS CLIP, UPDATE LISTING.
 C) USP RT24 VALUE ON THE PLANS IS HIGH,
 SEE FOOTNOTE IN USP (VALUE REPRESENT
 LOADS WHICH DO NOT INCLUDE A STEEL
 INCREASE ON THE STEEL CALCULATION.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 7)903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
  
 8) A-DT1 WINDOW & DOOR SCHEDULE, PLANS
 DO NOT INDICATE IF THIS SCHEDULE IS FOR
 THE INTERIOR ZONE (4) OR END ZONE(5).
 ALSO THERE IS A MULTIPLIER OF 1.12 FOR
 OVER 40' SEE 1606.2D.
  
 9) ADT1 HARDWARE NOTES (6) IMPLIES THAT
 ON THE 2ND & 3RD FLOORS ONLY THE SLIDING
 GLASS DOORS REQUIRES IMPACT DOORS. THE C
 ITY'S OFFICIAL INTERPRETATION LIST ON
 LARGE PROJECTS THAT A PRESTORM PREPARED-
 NESS PLAN MUST BE SUBMITTED BY THE PROP-
 ERTY OWNERS OR MANAGING AGENT FOR REVIEW
 BY THE CONSTRUCTION DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINIMUM ON-SITE
 LOCATION OF SHUTTERS, PARTY RESPONSIBLE
 FOR SECURRING SHUTTERS, (SAID PARTY
 RESPONSIBLE FOR SECURRING THE SHUTTERS,
 SAID PARTY MUST LIVE WITHIN PALM BEACH
 COUNTY) THE TOTAL NUMBER OF OPENINGS TO
 BE PROTECTED & THE TOTAL TIME REQUIRED
 TO SECURE ALL OPENINGS. PROTECTION OF
 OPENINGS SHALL BE ACCOMPLISHED WITHIN
 (12) HRS OR LESS OF THE NATIONAL WEATHER
 SERVICE OFA HURRICANE WATCH.
  
 10) SHEET A-DT2 DETAILS 7&8 PROVIDE A
 CLEAR DETAIL OF THE STUCCO REVEL & THE
 EXSPANSION CONTROL JOINT, (ASTM C-1063)
 INDICATE HOW THE WATER TIGHT MEMBRANE
 WILL OCURR, BE INSTALLED?
  
 11)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 GEOTECH REPORTS ARE NOT SIGNED& SEALED.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRONT DOOR MASONITE REPORTS ARE
 ILLEGABLE, PROVIDE CLEAR COPIES
 B) CLOSPAY GARAGE DOORS MISSING THE
 FLORIDA PRODUCT APPROVAL COVER SHEET.
 C) ROOFING ASSEMBLIES
 1) HANSON ROOF TILE INDICATE THE METHOD
 OF ATTACHMENT
 2) MISSING THE FLORIDA COVER SHEET
 3) MISSING REPORTS FOR THE UNDERLAYMENT
 D) NOTHING ON THE SLIDING GLASS DOOR
 E) WINDOWS- MISSING THE FLORIDA PRODUCT
 APPROVAL COVER SHEET
 F) STRUCTURAL COMPONENTS- MISSING INFOR-
 MATION FOR TRUSS ANCHORS, FL APPROVAL.
 G) RAILINGS NO INFORMATION SUBMITTED
 H) SOFFITS(EXTERIOR) NO INFORMATION
  
 14) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE SEEMS TO BE DESCREPANCIES IN
 THE FOUNDATION AND THE RECOMENDATION OF
 THE GEOTECH ENGINEER. THE STRUCTURAL
 SHEETS INDICATE A WF-6A FOUNDATION. THE
 GEOTECH REPORT RECOMENDS THE FOUNDATION
 TO BE 18" BELOW FINISH GRADE & A MINIMUM
 OF 24" WIDE, WHY WAS THE GEOTECH REPORT
 RECOMMENDATION NOT FOLLOWED?
 THE SECOND ISSUE WITH THE FOUNDATION
 DEALS WITH THE APPLICATION OF GYPSUM
 WALLBOARD SHEATHING, 2504.4.1 DEALS WITH
 THE APPLICATION OF EXTERIOR GYPSUM WALL
 BOARD SHEATHING, THE GYPSUM BASE VENEER
 SHALL BE INSTALLED IN ACORDANCE WITH
 2506 OR GA 216. IN GA 216-4.6.6 GYPSUM
 BOARD USED IN BUILDING CONSTRUCTION SHAL
 L BE NOT LESS THAN 8" FROM FINISH GRADE
 IN FULLY WEATHER AND WEATHER PROTECTED
 SIDING SYSTEMS.
 THE ADDITIONAL 8" FROM THE BOTTOM OF THE
 GYPSUM BOARD TO GRADE HAS NOT BEEN ADD-
 RESSED?
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-07 Cont ID  
Sent By dpalmer Date 2005-03-07 Time 18:38 Rev Time 0.50
Received By dpalmer Date 2005-03-07 Time 18:24 Sent To  
Notes
2005-03-07 00:00:00BLDG TYPE III
  
 ELECTRICAL SHEETS STAMPED, ALL THREE
 SETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 05:32 Rev Time 0.33
Received By dpalmer Date 2005-02-15 Time 05:27 Sent To  
Notes
2005-02-15 00:00:00******* UNSAT *****
  
  
 PLEASE SEE OLD SHEETS STILL IN SETS.
  
 EU-11, EU-12 ETC
  
 1)NOTE: PLEASE SEE CIRCUITING FOR SD'S
 ON MULTIPLE CIRCUITS.
  
 2)NOTE: PLEASE SEE OCP FOR SOME A/C
 UNITS HAVE NOT BEEN CHANGED.
  
 3)NOTE: PLEASE SEE MIN ALUM TO BE #2, #3
 SHOWN ON FEEDERS.
  
 4)NOTE: PLEASE SEE AS-1 STILL REFERENCES
 WRONG ELECTRICAL CODE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 07:03 Rev Time 1.50
Received By dpalmer Date 2004-12-30 Time 06:35 Sent To  
Notes
2004-12-30 00:00:00********* UNSAT 2ND REVIEW *********
  
 BLDG TYPE III
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1: NO. PLEASE SEE PLANS
 STILL REFERENCE THE 2001 NEC. THIS WAS
 CORRECTED ON ED-1, PLEASE SEE AS-1
 PLEASE ALSO SEE ED-1, CODE REFERENCED ON
 PREVIOUS PLANS FROM THE 96 NEC WAS
 CHANGED, HOWEVER CODE IN THE 2002 WHICH
 CORRELATES WITH SAME CODE REFERENCED ON
 PREVIOUS PLANS(96) IS 250.50 FOR
 GROUNDING ELECTRODE SYSTEMS.
  
 2)NOTE: NOTE #2, YES? PLEASE SEE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO MAIN WAS REMOVED AS REQUIRED UNDER
 250.6,250.24, HOWEVER THE EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 10HP PUMP WAS ALSO REMOVED. PLEASE SEE
 250.122 FOR SIZING.
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS
 NOTES, MANY OF THE UNITS ARE STILL
 SHOWING SD'S ON MORE THAN ONE CIRCUIT.
 THESE ARE REQUIRED TO WIRED "IN-LINE",
 IF WIRED AS SHOWN, THEN THERE WOULD BE
 220VON 120V SD'S. PLEASE SEE PLANS, MANY
 OF THESE HAVE BEEN REDLINED ON ONE SET.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE THERE ARE
 UNITS WHICH DO NOT MEET 424.3B
 THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS.
 PLEASE SEE THERE WERE MORE THAN JUST THE
 8KW UNITS.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK
  
 9)NOTE: NOTE #9 YES, THIS WAS DONE,
 HOWEVER, PLEASE SEE BOTH METER CENTERS
 ARE LABLED AS MC#1. (MISPRINT).
  
 10)NOTE: NOTE #10 OK
  
 11)NOTE: NOTE #11 OK
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 09:14 Rev Time 2.00
Received By dpalmer Date 2004-10-08 Time 09:14 Sent To  
Notes
2004-10-08 00:00:00************* UNSAT ***************
  
 BLDG TYPE III,BLDG'S 19,24,28,32,34
  
 1)NOTE: PLEASE SEE PLANS FOR REFERENCE
 OF CODE. SHOULD BE 2002 NEC.
 PLEASE ALSO SEE ED-1 FOR CODE REFERENCED
 FROM 96 NEC.
  
 2)NOTE: PLEASE SEE EQUIPMNET GROUNDING
 CONDUCTOR ON SITE RISER FROM METER TO
 MAIN. THIS IS NOT PERMITTED. 250.6,250.
 .24.
  
 3)NOTE: PLEASE SEE CIRCUITING FOR ALL
 UNITS, SOME UNIT MISSING. LIV RM RECEPT
 AND CLOSET RECEPT.
  
 4)NOTE: PLEASE SEE "LOCK-OFF" DEVICE TO
 BE APPROVED BY CITY OF WEST PALM BEACH
 BEFORE USE.
 IF PANEL IS W/IN SITE, THIS DEVICE MAY
 NOT BE REQUIRED?
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.6.1.2
 PLEASE SEE SD'S ON MULTIPLE CIRCUITS
 IN MANY OF THE UNTIS. THESE ARE REQUIRED
 TO BE WIRED "IN-LINE". THIS WOULD NOT BE
 POSSIBLE AS SHOWN.
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP OF
 AHU'S. SOME OK, SOME NEED TO BE ADJUSTED
 FOR MIN REQUIREMENTS. 125%.
  
 7)NOTE: PLEASE SEE 210.52G FOR MISSING
 RECEPT IN GARAGE'S. PLEASE ALSO SEE
 210.8 FOR GFI REQUIREMENT.
  
 8)NOTE: PLEASE SEE LTS IN ATTICS IN LOFT
 UNITS MUST BE SERVED FROM EACH OF THOSE
 UNITS PANELS. 210.25
  
 9)NOTE: PLEASE NOTE OR SPECIFY OCP/BRKRS
 FOR APT PANELS AT METER/MAIN LOCATION
 ON RISER. THIS MAY BE IN A "TYPICAL"
 NOTE FORM.
  
 10)NOTE: PLEASE CORRELATE PLANS/FEEDERS
 AND NOTE # 20A ON ED-1.
  
 11)NOTE: PLEASE SEE NOTE #24, SHOWS 120/
 208V YET PANELS INDICATE 120/240V.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-09-30 Cont ID  
Sent By mamini Date 2004-09-30 Time 14:44 Rev Time 1.00
Received By mamini Date 2004-09-30 Time 14:44 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT# 04120218 FOR
 UNDERGROUND UTILITIES AND SITE WORK,
 PHASE II.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 11:35 Rev Time 0.00
Received By nmccray Date 2005-03-01 Time 10:52 Sent To  
Notes
2005-03-01 00:00:00PROVISO:
 ILLUMINATED EXIT SIGNS ARE REQUIRED ON
 THE FIRST FLOOR.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 11:44 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 10:53 Sent To  
Notes
2004-12-07 00:00:001) WORK IS TO COMPLY WITH NFPA 241.
  
 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 3) ILLUMINATED EXIT SIGNS ARE REQUIRED
 ON THE FIRST FLOOR.
  
 4) FIRE ALARM SYSTEMS SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 5) FIRE ALARM SYSTEMS SHALL BE UL LISTED
 FOR CENTRAL STATION SERVICE.
  
 6) ELECTRONIC SWITHES ARE REQUIRED ON
 THE FIRE LINE BACKFLOW DEVICES.
  
 7) PLEASE PROVIDE PERSCRIPTIVE STRENGTH
 REQUIREMENTS FOR BALCONY RAILINGS.
  
 8) THE SAFETY MARGIN FOR FIRE SPRINKLER
 CALCULATION IS LESS THAN 5 LBS FOR BLDG
 TYPE III AND TYPE IV. THIS IS NOT
 ACCEPTABLE.
  
 REVIEW NOTES ARE FOR PERMITS 04090385,
 04090390, 04090394, 04090400
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 16:45 Sent To B
Notes
2005-08-18 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 13:48 Rev Time 0.00
Received By shill Date 2005-06-10 Time 13:48 Sent To B
Notes
2005-06-10 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 09:18 Sent To  
Notes
2005-03-03 00:00:00TO "COMM" BD#30/
 COMM RACK 4 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-03 Cont ID  
Sent By mjacobs Date 2005-02-03 Time 13:40 Rev Time 0.00
Received By mjacobs Date 2005-02-03 Time 13:40 Sent To  
Notes
2005-02-03 00:00:00TO "COMM BD#33/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 12:12 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 12:12 Sent To  
Notes
2004-12-27 00:00:00TO "COMM BD#60"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-02-03 Cont ID  
Sent By mjacobs Date 2004-10-08 Time 13:39 Rev Time 0.00
Received By mjacobs Date 2004-09-22 Time 16:04 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#55/4 ROLLS & 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By hmoser Date 2006-02-27 Time 16:54 Rev Time 0.00
Received By hmoser Date 2006-02-27 Time 16:54 Sent To  
Notes
2006-02-27 00:00:00REVISON CHANGE OF EQUIPMENT(LETTER)

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By pkrauss Date 2005-02-23 Time 14:28 Rev Time 0.40
Received By pkrauss Date 2005-02-23 Time 14:10 Sent To  
Notes
2005-02-23 00:00:00AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M)307.2.3.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 14:11 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 14:06 Sent To  
Notes
2005-01-10 00:00:00DENIED:TYPE III / BUILDING #1
 COMMENT #1 & 3 FROM REVIEW DATED
 10-22-04 WERE NOT ADDRESSED.SEE
 ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By pkrauss Date 2004-10-22 Time 09:14 Rev Time 1.00
Received By pkrauss Date 2004-10-22 Time 08:22 Sent To  
Notes
2004-10-22 00:00:00DENIED:TYPE III BUILDING #19
 1.PER 2001 FBC(M) 601.4 EXCEPTION #2
 & 3, RETURN TRANSFER GRILLES SHALL BE
 SIZED AS FOLLOWS:
 RETURN TRANSFER - 50 SQ INCHES OF FREE
 AREA TO 100 CFM OF SUPPLY AIR TO THAT
 AREA.ALL SUPPLY AIR INTO THE MASTER
 SUITE SHALL BE INCLUDED FOR PROPER
 SIZING.
 THE FOLLOWING UNITS ARE NOT SIZED
 PROPERLY - A-1 (DWG AC-U1), A-1S (DWG
 AC-U2), A-1LS (AC-U4), B-2 (AC-U5), C-3
 (AC-U9), C-3S (AC-U10).
  
 2.PLEASE NOTE, THE TOILET EXHAUST
 TERMINATION SHALL BE SCREENED PER 2001
 FBC(M) 401.6. (DRYER EXHAUST SHALL BE
 NON-SCREENED).
  
 3.PLAN SHEET PD-1 CONDENSATE RISER,
 CONDENSATE SHALL TERMINATE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 07:33 Rev Time 0.25
Received By kstevens Date 2005-02-15 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-22 Cont ID  
Sent By kstevens Date 2005-01-22 Time 12:36 Rev Time 1.50
Received By kstevens Date 2005-01-22 Time 12:36 Sent To  
Notes
2005-01-22 00:00:00DENIED
 REFERENCE: FHA-98 DESIGN MANUAL
  
 1) ALL SHEETS WITH FLOOR PLANS FOR
 HANDICAP ADAPTABLE UNITS:THE CLEAR
 FLOOR SPACE DIMENSIONS ARE TO BE
 APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE
 REQUIREMENTS AT TOILET ARE BEING MET.
 SEE PAGE 7.43 OF THE DESIGN MANUAL.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By kstevens Date 2004-10-19 Time 12:16 Rev Time 1.50
Received By kstevens Date 2004-10-19 Time 12:16 Sent To  
Notes
2004-10-19 00:00:00DENIED
 REFERENCE: FHA-98(AMEND) DESIGN MANUAL
  
 SHT A-U14 DETAILS FOR BACKING FOR THE
 TUB, SHOWER, AND W/C SHALL REFLECT THE
 BACKING REQUIREMENTS IN FHA DESIGN MAN-
 UAL PAGES 6.4/6.5, 6.8/6.9, & 6.12/6.13
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-18 Cont ID  
Sent By mmclean Date 2005-01-10 Time 08:50 Rev Time 0.00
Received By mmclean Date 2005-01-10 Time 08:50 Sent To  
Notes
2005-02-18 00:00:00APPROVED BY JOSH LONG, PLANNER 822-1449