| 2004-10-26 00:00:00 | BUILDING PLAN REVIEW |
| | |
| | PORTOFINO PHASE II LAND, LTD |
| | |
| | BUILDING TYPE II |
| | |
| | PERMIT: 04090363BLDG# 18 |
| | ADD: 4660 PORTOFINO WAY |
| | PERMIT: 04090386BLDG# 25 |
| | ADD: 4640 PORTOFINO WAY |
| | PERMIT: 04090389BLDG# 27 |
| | ADD: 4625 PORTOFINO WAY |
| | PERMIT: 04090391BLDG# 29 |
| | ADD: 4700 PORTOFINO WAY |
| | PERMIT: 04090397BLDG# 33 |
| | ADD: 4720 PORTOFINO WAY |
| | |
| | CONT: EPOCH PROPERTIES, INC |
| | TEL: (407)718-8932 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE INCORECT PROPERTY CONTROL NUMBER |
| | WAS USED & CORRECT THE ADDRESSES FOR |
| | PHASE II DATED SEPT 21/04. |
| | |
| | 2) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3) SHEET A-U13 DETAILS INDICATE THE USE |
| | OF SEMCO STRAPS. SEMCO WAS BOUGHT OUT IN |
| | 1999 BY USP, UPDATE PLANS TO REFLECT THE |
| | MANUFACTURER, MODEL NUMBER, AND LOADS TO |
| | BE IMPOSED. A-T1.3 HURRICANE STRAP/ |
| | CONNECTION NOTES ALSO REFRENCE SEMCO |
| | PRODUCTS. DELETE SEMCO FROM A-DT4. |
| | |
| | 4) SHEET A-U13 DETAIL# 5, RISERS ARE TO |
| | COMPLY WITH 1007.3.1. RISERS SHALL BE A |
| | MAXIMUM HEIGHT OF 7". |
| | |
| | 5) SHEET A-T2.3 ROOF SHEATHING NOTES, 23 |
| | .22.2.5 DEALS WITH THE HIGH VELOCITY |
| | HURRICANE ZONES, 2306.1* ZONE# 3 EDGE |
| | NAILING ZONES BETWEEN 25'-35' REQUIRE |
| | 8D RING SHANK NAILS @ 4" O.C. EDGES & |
| | 6" O.C. INTERMEDIATES. |
| | ENGINEER OF RECORD WILL PROVIDE ADDTION- |
| | AL INFORMATION ON ROOF SHEATHING NAILING |
| | ABOVE 35'. |
| | |
| | 6) SHEET A-T2.3 HURRICANE STRAPS: |
| | A) USP TSUA24/26 TUNNEL TIE NOT LISTED |
| | IN THE 2004 CATALOG. |
| | B) USP DTC LISTED IN THE USP CATALOG AS |
| | A ROOF TRUSS CLIPS |
| | C) USP RT 24 VALUE ON THE PLANS IS HIGH |
| | SEE FOOTNOTE IN USP ( VALUE REPRESENT |
| | LOADS WHICH DO NOT INCLUDE A STEEL |
| | INCREASE ON THE STEEL CALCULATION). |
| | 1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | |
| | 7)903.8.2 FLOR ST STATUTE 553.895(2) |
| | ALL RESIDENTIAL BUILD. 3 OR MORE STORIES |
| | TALL WHETHER DESIGNATED AS TOWNHOUSE, |
| | CONDOMINIUMS, "APARTMENT HOUSES, |
| | TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| | OTHER NAME SHALL BE SUPPLIED BY FIRE |
| | SPRINKLERS MEETING NFPA 101. |
| | |
| | 8) A-DT1 WINDOW & DOOR SCHEDULE, PLANS |
| | DO NOT INDICATE IF THIS SCHEDULE IS FOR |
| | (4) INTERIOR ZONES OR (5) END ZONES. |
| | ALSO THERE IS A MULTIPLIER OF 1.12 FOR |
| | OVER 40', SEE 1606.2D. |
| | |
| | 9) A-DT1 HARDWARE NOTES (6) IMPLIES THAT |
| | ON THE 2ND & 3RD FLOORS ONLY THE SLIDING |
| | GLASS DOORS REQUIRES IMPACT GLASS. THE |
| | CITY'S OFFICIAL INTERPRETATION LIST ON |
| | LARGE PROJECTS THAT PRE-STORM PREPARED- |
| | NESS PLAN MUST BE SUBMITTED BY THE PROP- |
| | ERTY OWNERS OR MANAGING AGENT FOR REVIEW |
| | BY THE CONSTRUCTION DEPARTMENT. ANY SUCH |
| | PLAN SHALL INCLUDE, AT A MINIMUM ON-SITE |
| | LOCATION OF SHUTTERS, PARTY RESPONSIBLE |
| | FOR SECURRING THE SHUTTERS, (SAID PARTY |
| | RESPONSIBLE FOR SECURING THE SHUTTERS, |
| | SAID PARTY MUST LIVE WITHIN PALM BEACH |
| | COUNTY) THE TOTAL NUMBER OF OPENINGS TO |
| | BE PROTECTED AND THE TOTAL TIME REQUIRED |
| | TO SECURE ALL OPENINGS. PROTECTION OF |
| | OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | (12) HRS OR LESS OF THE NATIONAL WEATHER |
| | SERVICE OF A HURRICANE WATCH. |
| | |
| | 10) SHEET A-DT2 DETAILS 7&8 PROVIDE A |
| | CLEAR DETAIL OF THE STUCCO REVEL & THE |
| | EXSPANSION CONTROL JOINT, (ASTMC-1063) |
| | INDICATE HOW THE WATER TIGHT MEMBRANE |
| | WILL OCCUR, BE INSTALLED? |
| | |
| | 11)PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | GEOTECH REPORTS NOT SIGNED & SEALED. |
| | |
| | 12)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FRONT DOOR MASONITE REPORTS ARE |
| | ILEGABLE, PROVIDE CLEAR COPIES |
| | B) CLOSPAY GARAGE DOORS- MISSING THE |
| | FLORIDA PRODUCT APPROVAL COVER SHEET. |
| | C) ROOFING ASSEMBLIES- |
| | 1) HANSON ROOF TILE INDICATE THE |
| | METOF OF ATTACHMENT. |
| | 2) MISSING THE FL COVERSHEET |
| | 3)MISSING REPORTS FOR THE UNDERLAYMENT |
| | D) NOTHING ON THE SLIDING GLASS DOORS |
| | E) WINDOWS- MISSING THE FLORIDA PRODUCT |
| | APPROVAL COVERSHEET. |
| | F) STRUCTURAL COMPONENTS- MISSING INFOR- |
| | MATION FOR TRUSS ANCCHORS, FL APPROVAL. |
| | G) RAILINGS- NO INFORMATION SUBMITTED |
| | H) SOFFITS NO INFORMATION SUBMITTED. |
| | |
| | 14) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THERE SEEMS TO BE A DISCREPANCY IN THE |
| | RECOMENDATIONS OF THE GEO TECH ENGINEER. |
| | THE STRUCTURAL SHEETS INDICATE A WF-16A |
| | FOUNDATION. THE GEOTECH REPORT RECOMENDS |
| | THE FOUNDATION BE 18" BELOW FINISH GRADE |
| | & THE MINIMUM OF 24" WIDE, WHY WAS THE |
| | GEOTECH REPORT RECOMENDATIONS NOT FOLLOW |
| | ED? |
| | THE SECOND ISSUE WITH THE FOUNDATION |
| | DEALS WITH THE APPLICATION OF GYPSUM |
| | WALLBOARD SHEATHING, 2504.4.1 DEALS WITH |
| | THE APPLICATION OF EXTERIOR GYPSUM WALL- |
| | BOARD SHEATHING, THE GYPSUM BASE VENEER |
| | SHALL BE DONE WITH 2506 OR GA 216. IN |
| | GA216-4.6.6. GYPSUM BOARD USED IN BUILD- |
| | ING CONSTRUCTION SHALL BE NOT LESS THAN |
| | 8" FROM FINISH GRADE. |
| | THE ADDITIONAL 8" FROM THE BOTTOM OF |
| | THE GYPSUM BOARD TO GRADE HAS NOT BEEN |
| | ADDRESSED? |
| | |
| | 15)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |