Plan Review Details - Permit 04090291
Plan Review Stops For Permit 04090291
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-03 Cont ID  
Sent By jwitmer Date 2004-11-03 Time 07:00 Rev Time 0.25
Received By jwitmer Date 2004-11-03 Time 06:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 07:35 Rev Time 0.55
Received By jwitmer Date 2004-10-20 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-08 Cont ID  
Sent By dpalmer Date 2005-02-08 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2005-02-08 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 11:12 Rev Time 0.33
Received By dpalmer Date 2004-11-01 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-22 Cont ID  
Sent By dpalmer Date 2004-09-22 Time 10:44 Rev Time 0.50
Received By dpalmer Date 2004-09-22 Time 07:33 Sent To  
Notes
2004-09-22 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE SEE ELECTRICAL EQUIPMENT
 IS SHOWN IN A "CLOSET".
 PLEASE SEE 110.26,408.7. ETC
 NOT PERMITTED IN A STRORAGE CLOSET,
 MUST BE A DEDICATED SPACE.
  
 2)NOTE: PLEASE SHOW ACTUAL CONNECTION
 FOR GROUNDING OF TRANSFORMER. 250.30
  
 3)NOTE: PLEASE SEE FS 471.025 AND
 FAC 61G15-23.002, WHICH REQUIRES A
 SIGNATURE FOR ENGINEER.
 PLEASE SEE FIRST NAME APPEARS TO BE
 SIGNED AS AN INITIAL. IF THIS IS FULL
 AND LEGAL SIGNATURE, PLEASE PROVIDE
 A SIGNED AND SEALED NOTORIZED LETTER
 SO THAT WE MAY PLACE IN OUR SIGNATURE
 FILE FOR FUTURE PROJECTS.
 IF THERE ARE ANY QUESTIONS ON THE ABOVE
 COMMENT PLEASE DO NOT HESITATE IN
 CONTACTING ME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:51 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:51 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 16:31 Sent To P
Notes
2004-12-01 00:00:00SENT TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 11:16 Sent To E
Notes
2005-02-02 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-26 Cont ID  
Sent By csiegber Date 2004-10-26 Time 11:56 Rev Time 0.00
Received By csiegber Date 2004-10-26 Time 11:56 Sent To  
Notes
2004-10-26 00:00:00TO COMM BD#55

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2004-09-17 Time 08:53 Sent To PC
Notes
2004-09-17 00:00:00TO COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-13 Cont ID  
Sent By pkrauss Date 2004-10-13 Time 14:11 Rev Time 0.40
Received By pkrauss Date 2004-10-13 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-12-07 Cont ID  
Sent By kstevens Date 2004-12-07 Time 17:05 Rev Time 0.50
Received By kstevens Date 2004-12-07 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 16:32 Rev Time 0.50
Received By kstevens Date 2004-11-19 Time 08:32 Sent To  
Notes
2004-11-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 DETAIL FOR SINK SHALL SHOW KNEE
 CLEARANCE 11-4.24.3, SINK DEPTH
 11-4.24.4, - PARALLEL APPROACH STILL
 SHOWN ON SHTS 1 AND 4. FORWARD APPROACH
 IS REQUIRED 11-4.24.5.
  
 CLOUDED AREA SHT 1 SHOWS 36" WITH HAND
 DRAWN CORRECTIONS. THIS IS NOT APPROVED
 SECTION 104.2.1.3
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 16:13 Rev Time 0.50
Received By kstevens Date 2004-10-09 Time 16:13 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND SHUT OFF VALVE REQ-
 UIRED BY SECTION 606.1(4).
 2) DETAIL FOR SINK SHALL SHOW KNEE
 CLEARANCE 11-4.24.3, SINK DEPTH 11-4.24.
 4, CLEAR FLOOR SPACE SHALL BE PROVIDED
 IN FRONT OF A SINK TO ALLOW FORWARD APP-
 ROACH 11-4.24.6, EXPOSED PIPES AND SUR-
 FACES 11-4.24.6
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]