Plan Review Details - Permit 04090224
Plan Review Stops For Permit 04090224
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By jwitmer Date 2004-10-15 Time 14:59 Rev Time 1.11
Received By jwitmer Date 2004-10-15 Time 14:58 Sent To PC
Notes
2004-10-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090224
 ADD: 201 S NARCISSUS AV
 CONT: HOME TECHNICAL SERVICES
 TEL: (561)262-4068
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) THE PLANS DO NOT PROVIDE IF THE STEEL
 STUDS/ JOIST ARE STRUCTURAL OR DRYWALL,
 PROVIDE THE MINIMUM THICKNESS (MIL)?
 B) THE WIDTH & FLANGE WIDTH OF THE
 STUD/ JOIST ARE NOT PROVIDED?
 C) ARE THE STUDS/ JOIST 33 KSI OR 50KSI?
 D) WHAT DEFLECTION LIMITS ARE YOU
 DESIGNING TO L/240 OR L/360?
 E) WHAT PSF ARE YOU DESIGNING TO,INCLUDE
 STEEL STUD AND DRYWALL?
 F) WILL THE CEILING HAVE A MIDSPAN SUP-
 PORT, IF SO WHAT TYPE OR UNSUPPORTED?
 ONCE THESE FACTORS ARE KNOWN ,
 THE CEILING SPAN TABLES WILL GIVE THE
 ALLOWABLE SPANS FOR THE STEEL CEILING
 JOIST.
 PLANS INDICATE THAT THE DROPPED CEIL
 ING WILL BE ATTACHED TO AN EXISTING
 SOFFIT, HOW WILL THE NEW LOADS BE TRANS-
 FERRED TO THE EXISTING SOFFIT.
  
 3) TYPE I OR II BUILDING NO COMBUSTIBLES
 ALOWED IN WALLS609.1.2.
  
 4) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 17:11 Rev Time 0.25
Received By dpalmer Date 2004-10-05 Time 17:11 Sent To  
Notes
2004-10-05 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE FBC 104.2.1
 PLANS ARE REQUIRED TO HAVE THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-12 Cont ID  
Sent By nmccray Date 2004-10-12 Time 15:56 Rev Time 0.00
Received By nmccray Date 2004-10-12 Time 15:56 Sent To  
Notes
2004-10-12 00:00:00SEE NOTES ON PERMIT 04090221

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-15 Cont ID  
Sent By jwitmer Date 2004-10-15 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2004-09-16 Time 08:45 Sent To PC
Notes
2004-09-16 00:00:00TO COMM BD#13