Plan Review Details - Permit 04090215
Plan Review Stops For Permit 04090215
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-02 Cont ID  
Sent By jwitmer Date 2004-11-02 Time 16:17 Rev Time 1.11
Received By jwitmer Date 2004-11-02 Time 16:17 Sent To  
Notes
2004-11-02 00:00:00BUILDING PROVISO:
  
 803.4 FOAM PLASTIC TRIM SHALL NOT BE
 USED AS INTERIOR TRIM. SEE EXCEPTION:
 A) THE MINIMUM DENSITY IS 20LBS/CU FT.
 B) THE MAXIMUM THICKNESS OF THE TRIM IS
 1/2" AND THE MAXIMUM WIDTH IS 4".C)
 THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE WALL OR CEILING.
 D) THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84.
 THE SMOKE DEVELOPMENT RATING IS
 NOT LIMITED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 07:17 Rev Time 1.22
Received By jwitmer Date 2004-10-18 Time 09:42 Sent To PC
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090215
 ADD: 201 S NARCISSUS AV
 CONT: HOME TECHNICAL SERVICES, INC
 TEL: (561)262-4068
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE THE USE OF SOFFITS, NO
 DETAILS FOR FASTENING TO THE STRUCTURE
 ABOVE, NOR SPACING OF FRAMING OR FASTEN-
 ING OF FRAMING.
  
 3) 609.2.1 TYPE I OR II BUILDINGS, NO
 COMBUSTIBLE MATERIALS IN WALLS, STUDS,
 BACKING, ETC.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5)803.4 FOAM PLASTIC TRIM SHALL NOT BE
 USED AS INTERIOR TRIM. SEE EXCEPTION:
 A) THE MINIMUM DENSITY IS 20LBS/CU FT.
 B) THE MAXIMUM THICKNESS OF THE TRIM IS
 1/2" AND THE MAXIMUM WIDTH IS 4".
 C) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE WALL OR CEILING.
 D) THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84.
 THE SMOKE DEVELOPMENT RATING IS
 NOT LIMITED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 09:03 Rev Time 0.33
Received By dpalmer Date 2004-11-15 Time 09:03 Sent To  
Notes
2004-11-15 00:00:00SPECS SHEETS BROUGHT IN SHOWING LISTING
 FOR MR SAUNA.
 SPECS BROUGHT IN FOR STEAMIST DID NOT
 SHOW ANY LSITING FROM A NRTL.
  
 PRINTED ADDITIONAL SPEC SHEET FOR
 STEAMIST UNIT SHOWING LISTINGS.
  
 STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 10:37 Rev Time 0.33
Received By dpalmer Date 2004-11-01 Time 10:37 Sent To  
Notes
2004-11-01 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 OK, HOWEVER ELECTRICAL SPEC SHEETS FOR
 NEW STEAM UNIT AND SAUNA WERE NOT
 SUBMITTED.
 SPEC SHEETS ALSO NEED OT SHOW LISTING
 FROM A NRTL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 17:39 Rev Time 0.33
Received By dpalmer Date 2004-10-05 Time 17:38 Sent To  
Notes
2004-10-05 00:00:00*********** UNSAT ********
  
 1)NOTE: PLEASE SHOW NEW CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 215.5
  
 2)NOTE: PLEASE CORRELATE OCP AND AWG FOR
 SOME ITEMS ON PANEL SCHEDULES.
 60A OCP W/ #8
 20A OCP W/ #14
 COOKTOP, WATER HEATER, FRIG , EXISTING
 COOKTOP. PLEASE SEE 310.16 75 DEGREE
 COL. 110.14
  
 3)NOTE: PLEASE SUBMIT SPEC SHEETS FOR
 NEW SAUNA/ STEAM UNITS.
 LOADS SHOWN AT 5KW YET OCP IS SHOWN AT
 60A ALSO WITH #8 AWG??
 310.16,215.5
  
 4)NOTE: PLEASE VERIFY NEW DISHWASHER
 SHOWN AT 240V?
  
 5)NOTE: PLEASE CLARIFY SOME AREAS OF
 PLANS CALL FOR MINOR WORK, YET NOTHING
 IS INDICATED?
  
 6)NOTE: PLEASE SEE NOTE #8 OF ELECTRICAL
 NOTES. PLEASE SEE NEC 336 OF THE 2002
 NEC, NMC IS NOT PERMITTED IN THIS BLDG.
 THIS IS ONLY A NOTE FYI.
  
 7)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 IN REFERENCE TO REQUIRED UNITY OF TITLE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-17 Cont ID  
Sent By nmccray Date 2004-11-17 Time 15:55 Rev Time 0.00
Received By nmccray Date 2004-11-17 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-12 Cont ID  
Sent By nmccray Date 2004-10-12 Time 15:24 Rev Time 0.00
Received By nmccray Date 2004-10-12 Time 15:24 Sent To  
Notes
2004-10-12 00:00:00SEE NOTES ON PERMIT 04090221

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 11:37 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 11:37 Sent To M
Notes
2005-02-04 00:00:00TO PRAFTER DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 14:55 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#41

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2004-09-16 Time 08:47 Sent To PC
Notes
2004-09-16 00:00:00TO COMM BD#13

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-05 Cont ID  
Sent By prafter Date 2005-01-05 Time 13:47 Rev Time 0.00
Received By prafter Date 2005-01-05 Time 13:54 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2004-10-19 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-17 Cont ID  
Sent By kstevens Date 2004-11-17 Time 15:45 Rev Time 0.50
Received By kstevens Date 2004-11-17 Time 15:45 Sent To  
Notes
2004-11-17 00:00:00PASSED/PROVISO
  
 T/P RELIEF VALVE FROM STEAM UNIT SHALL
 DISCHARGE INTO THE EMERGENCY PAN OF THE
 STEAM UNIT. THE DRAIN FROM THE STEAM
 UNIT SHALL DISCHARGE INTO THE SHOWER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 15:14 Rev Time 0.75
Received By kstevens Date 2004-10-09 Time 15:07 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SUBMIT A SANITARY RISER DIAGRAM THAT
 INDICATES ALL ADDED FIXTURES. SHOW PIPE
 SIZE AND VENTING FOR NEW FIXTURES.
 SECTION 104.2.1
 2) SUBMIT A DETAIL SHOWING PIPING FOR
 THE RELIEF VALVE FOR THE STEAM UNIT. IN-
 DICATE TERMINATION POINT FOR RELIEF VAL-
 VE PIPING. SECTION 104.2.1 & 504.7.1.
 3) CLARIFY NOTE "MINOR WORK IN THESE
 AREAS"
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]