Plan Review Details - Permit 04090203
Plan Review Stops For Permit 04090203
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-19 Time 15:41 Rev Time 0.00
Received By nmccray Date 2004-10-28 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-28 Cont ID  
Sent By csiegber Date 2004-09-15 Time 12:38 Rev Time 0.00
Received By nmccray Date 2004-09-28 Time 11:38 Sent To  
Notes
2004-09-28 00:00:00************DENIED**********************
  
 1) PLEASE PROVIDE CUT SHEETS FOR FIRE
 ALARM PANEL AND ALL FIRE ALARM DEVICES
  
 2) REVISE NOTE # 10 FIRE ALARM SYSTEM
 SHALL BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 3) REVISE NOTE # 11 FIRE ALARM SYSTEM
 SHALL BE CLASS "A" OR FULLY ADDRESSABLE.
  
 4) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND A DOCUMENT
 ATTESTING TO THIS CERTIFICATION SHALL BE
 PROVIDE TO THE WEST PALM BEACH FIRE DEPT
 PRIOR TO FINAL APPROVAL OF THE
 INSTALLATION ON SITE.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 15:40 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 12:38 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 12:38 Sent To FIRE
Notes
***NONE***