Plan Review Details - Permit 04090170
Plan Review Stops For Permit 04090170
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:39 Rev Time 0.00
Received By nmccray Date 2004-10-06 Time 11:43 Sent To  
Notes
2004-10-06 00:00:00*********DENIED*************************
  
 1) PLEASE SUBMIT SHOP DRAWINGS AND CUT
 SHEETS SHOWING LOCATION OF THE FACP.
  
 2) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DIALER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS IF IT WERE A NEW SYSTEM.
  
 3) IS THIS BUILDING FIRE SPRINKLER
 PROTECTED? PLEASE BE AWARE THAT ALL NEW
 FIRE ALARM SYSTEMS THAT SUPERVISE FIRE
 SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENT ATTESTING
 TO THIS CERTIFICATION PRIOR TO FINAL
 APPROVAL OF THE FIRE ALARM SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE
 CLASS "A" OR FULLY ADDRESSABLE.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 09:39 Sent To FIRE
Notes
***NONE***