| Plan Review Stops For Permit 04090170 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-04 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-10-06 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | *********DENIED************************* | | | | | | 1) PLEASE SUBMIT SHOP DRAWINGS AND CUT | | | SHEETS SHOWING LOCATION OF THE FACP. | | | | | | 2) WHEN THE FIRE ALARM CONTROL UNIT, | | | INCLUDING THE DIALER-COMMUNICATOR, IS | | | REPLACED IN AN EXISTING SYSTEM, IT WILL | | | BE TREATED AS IF IT WERE A NEW SYSTEM. | | | | | | 3) IS THIS BUILDING FIRE SPRINKLER | | | PROTECTED? PLEASE BE AWARE THAT ALL NEW | | | FIRE ALARM SYSTEMS THAT SUPERVISE FIRE | | | SPRINKLER SYSTEMS SHALL BE UL | | | CERTIFICATED AND HAVE DOCUMENT ATTESTING | | | TO THIS CERTIFICATION PRIOR TO FINAL | | | APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 4) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|