Plan Review Details - Permit 04090117
Plan Review Stops For Permit 04090117
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:53 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 14:53 Sent To P
Notes
2004-10-05 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 12:05 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 12:05 Sent To P
Notes
2004-09-14 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-10 Cont ID  
Sent By kstevens Date 2004-11-10 Time 12:44 Rev Time 0.50
Received By kstevens Date 2004-11-10 Time 12:44 Sent To  
Notes
2004-11-10 00:00:00 
  
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 Q

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-23 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:53 Rev Time 0.00
Received By pschmitz Date 2004-10-23 Time 12:38 Sent To  
Notes
2004-10-23 00:00:00PLUMBING PLAN REVIEW FBC FUEL GAS 2001
 DENIED
 SEE NOTE #9 SUBMIT CUT SHEETS FOR 2# PSI
 GAS REGULATORS.
 REFERENCE GAS PIPE SIZING TABEL FOR
 SCH 40 STEEL PIPE, 2# SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-23 Cont ID  
Sent By csiegber Date 2004-09-14 Time 12:05 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-09-18 00:00:00DENIED GAS PERMIT APPLICATION REQUIRMENT
 ITEMS 1,2,3,4,5,7,8.