Plan Review Details - Permit 04090060
Plan Review Stops For Permit 04090060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-10 Cont ID  
Sent By jwitmer Date 2004-11-10 Time 14:12 Rev Time 1.11
Received By jwitmer Date 2004-11-10 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 08:34 Rev Time 2.22
Received By jwitmer Date 2004-10-19 Time 08:34 Sent To PC
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090060
 ADD: 700 S ROSEMARY AV# 131
 CONT: TLC CONTRACTING, INC
 TEL: (239)872-5336
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-16 Cont ID  
Sent By dpalmer Date 2004-11-16 Time 10:40 Rev Time 0.33
Received By dpalmer Date 2004-11-16 Time 10:40 Sent To  
Notes
2004-11-16 00:00:00TITLE BLOCK INFORMATION WRITTEN IN FOR
 ARCH AND ENGINEER'S.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By dpalmer Date 2004-11-03 Time 12:32 Rev Time 0.50
Received By dpalmer Date 2004-11-03 Time 12:32 Sent To  
Notes
2004-11-03 00:00:00************ UNSAT 2ND REVIEW *******
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PERVIOUS
 REVIEW.
 PLEASE INCLUDE ALL REQUIRED INFORMATION
 IN TITLE BLOCKS AS REQUIRED PER FAC
 61G1-16.004,FAC 61G15-23.002, FS
 481.219,FS471.023.
 THE ABOVE HAS NOT BEEN ADDED TO TITLE
 BLOCKS.
  
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 17:56 Rev Time 0.50
Received By dpalmer Date 2004-09-21 Time 17:34 Sent To  
Notes
2004-09-21 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ARCHITECTS AND FAC 61G15-23.002 FOR ENGI
 -NEERS. PLEASE INCLUDE ALL REQUIRED
 LICENSE #'S AND INFORMATION ON TITLE
 BLOCKS PER ABOVE.
 PLEASE SEE ALSO SEE FS 481.219 FOR ARCH'
 S AND 471.023 FOR ENG'S.
 THE ABOVE IS REQUIRED ON ALL SHEETS AND
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE COLOR CODING FOR
 277/480V IS TO BE (A) BROWN(B) PURPLE,
 (C) YELLOW. PER LOCAL AMENDMENTS.215
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 15:53 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:48 Sent To  
Notes
2004-10-01 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) PLANS ARE STAMPED WITH "CITY PLACE
 STAMP".
  
 3) COULD NOT LOCATE ANY EXISTING OR
 NEW FIRE ALARM EQUIPMENT IN TENANT
 SPACE.
  
 4) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-29 Time 10:56 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 10:56 Sent To  
Notes
2004-10-29 00:00:00TO COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2004-09-14 Time 16:21 Sent To PC
Notes
2004-09-14 00:00:00TO COMM BD#31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 07:37 Rev Time 0.45
Received By pkrauss Date 2004-11-16 Time 07:11 Sent To  
Notes
2004-11-16 00:00:00PLEASE INDICATE ON PLANS OR BY SIGNED,
 SEALED LETTER FROM THE ARCHITECT NO
 PLUMBING CHANGES OR MODIFICATIONS ARE
 BEING DONE UNDER THIS PERMIT.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By pkrauss Date 2004-10-15 Time 14:50 Rev Time 0.45
Received By pkrauss Date 2004-10-15 Time 14:34 Sent To  
Notes
2004-10-15 00:00:00DENIED:
 1.PLEASE PROVIDE LICENSE NUMBERS FOR
 ARCHITECTS AS REQUIRED PER FS 481.219
 AND FAC 61G1-16.004.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By lmartine Date 2004-11-16 Time 11:26 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***