Plan Review Details - Permit 04090017
Plan Review Stops For Permit 04090017
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-11 Cont ID  
Sent By rmcdouga Date 2005-01-11 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2005-01-11 Time 09:57 Sent To  
Notes
2005-01-11 00:00:00REVISIONS TO CHANGE OPENINGS IN FAMILY
 ROOM FROM FRENCH DOORS WITH SIDELITES TO
 TWO SETS OF FRENCH DOORS IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-15 Cont ID  
Sent By rmcdouga Date 2004-12-15 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2004-12-15 Time 14:30 Sent To  
Notes
2004-12-15 00:00:00BUILDING PROVISO
  
 PROVIDE ATTIC ACCESS TO ATTIC SPACE
 ABOVE MASTER BEDROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-30 Cont ID  
Sent By rmcdouga Date 2004-11-30 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2004-11-30 Time 07:27 Sent To  
Notes
2004-11-30 00:00:00DENIED
  
 1) THE WINDLOAD PRESSURES FOR THE
 BREAKFAST NOOK WINDOWS ARE GIVEN ON
 SHEET A-6 WITH THE ARROW POINTING TO
 THE
 WRONG LOCATION.
  
 2) ON SHEET A-5 TWO DIFFERENT SETS OF
 WINDLOAD PRESSURES ARE SPECIFIED FOR
 THE
 GOLF CART GARAGE DOOR. SEE FRONT AND
 LEFT ELEVATIONS. THE NEGATIVE PRESSURE
 GIVEN FOR THE DOOR ON THE LEFT
 ELEVATION
 EXCEEDS THE DESIGN PRESSURE ON THE
 PRODUCT APPROVAL.
  
 3) THE ATTIC ACCESS IN THE CEILING OF
 HIS WALK IN CLOSET ON THE FIRST FLOOR
 WILL NOT PROVIDE ACCESS TO THE ATTIC
 SPACE ABOVE THE MASTER SUITE BECAUSE IT
 IS LOCATED BELOW THE SECOND FLOOR
 BATHROOM. AN ACCESS THROUGH THE WALL OF
 THE SECOND FLOOR WALK IN CLOSET INTO
 THE
 ATTIC SPACE OF MASTER SUITE WOULD BE
 ADEQUATE.
  
 4) A LARGE PORTION OF THE SECOND FLOOR
 IS WOOD FRAME HOWEVER THE INSTALLATON
 SCHEDULE FOR THE STORM PANELS SPECIFIES
 CALK-IN FASTENERS WHICH ARE NOT FOR USE
 IN WOOD. PLEASE CORRECT.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By gsalfeld Date 2004-10-20 Time 12:56 Rev Time 0.00
Received By rmcdouga Date 2004-10-25 Time 14:50 Sent To  
Notes
2004-10-25 00:00:00DENIED
  
 1) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED ON THE ZERO LOT LINE. PLEASE
 SPECIFY THIS ON THE FLOOR PLAN.
  
 2) FBC 11-4.23.2 REQUIRES AT LEAST ONE
 FULL BATH ON THE FIRST FLOOR TO HAVE A
 DOOR WITH A 29" CLEAR OPENING.
  
 3) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE (2) 3050
 CSMT. WINDOWS IN BEDROOM #2, THE (2)
 FRENCH DOORS WITH SIDELITES IN THE
 FAMILY ROOM AND THE (3) FIXED GLASS
 PANELS IN THE BREAKFAST NOOK.
  
 4) UPDATE THE REFERENCE TO ASCE 7-88 IN
 THE GLASS BLOCK DETAIL ON A12. IT SHOULD
 BE ASCE 7-98.
  
 5) SUBMIT THE LISTING INFORMATION AND
 SPECIFICATIONS FOR THE ONE HOUR FIRE
 RATED GLASS BLOCKS.
  
 6) THE ATTIC ACCESS SPECIFIED IN THE
 CEILING OF HIS W.I.C. ON THE FIRST FLOOR
 IS WHERE THE FLOOR TRUSSES ARE LOCATED.
 PLEASE CORRECT.
  
 7) SPECIFY ATTIC ACCESS AT THE 3-CAR
 GARAGE AND MASTER SUITE AS REQUIRED BY
 FBC 2309.6.
  
 8) THE CIRCULAR STAIRS ARE REQUIRED TO
 HAVE A MINIMUM TREAD DEPTH OF 9" WITH A
 1" NOSING MEASURED 12" FROM THE SMALLER
 RADIUS PER FBC 1007.8.3. PLEASE CLARIFY
 THIS ON THE PLANS.
  
 9) SAFETY GLAZING IS REQUIRED WITHIN 3'
 HORIZONTALLY OF BATHTUBS OR SHOWERS PER
 FBC 2405.2.1 IF LESS THAN 60" ABOVE THE
 FLOOR OR WALKING SURFACE. SPECIFY TEMP.
 GLASS AT 2ND FLOOR BATH #3 AND #4.
  
 10) ATTIC VENTS ARE ALLOWED ON THE ZERO
 LOT LINE SIDE. SEE NOTE ON A13.
  
 11) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE MOUNT, FASTENERS AND FASTENER
 SPACING THAT WILL BE USED.
  
 12)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 13) THE ENTRY DOORS ON A3 SPECIFIED AS
 WOOD, HOWEVER, THE PRODUCT APPROVAL
 SUBMITTED IS FOR FIBERGLASS DOORS.
 PLEASE CLARIFY.
  
 14) THE NEGATIVE PRESSURE SPECIFIED ON
 A5 FOR THE 8'X8' GARAGE DOOR IS GREATER
 THAN THE NEGATIVE DESIGN PRESSURE ON THE
 PRODUCT APPROVAL. PLEASE CORRECT.
  
 15) SPECIFY ON SHEET A3 OF THE PLANS
 THAT THE DEN IS NOT TO BE USED AS A
 SLEEPING ROOM OR PROVIDE EGRESS WINDOWS.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-08-29 Cont ID  
Sent By dpalmer Date 2005-08-29 Time 20:01 Rev Time 0.40
Received By dpalmer Date 2005-08-29 Time 20:01 Sent To  
Notes
2005-08-29 00:00:00******** PLANS REDLINED *****
  
  
  
 1) PLEASE SEE LOAD FOR AHU ON PANEL "B"
 HAS BEEN DECREASED TO CORRELATE WITH KW
 RATING INDICATED ON LOAD CALCULATIONS,
 HOWEVER, PLEASE SEE PANEL SCHEDULE STILL
 INDICATES "60A" OVERCURRENT PROTECTION
 FOR A 5KW HEAT STRIP? THIS IS OVERSIZED.
  
 2) PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR HAS NOW BEEN CHANGED TO A #1 ?
  
 PLEASE SEE PREVIOUS COMMENT MENTIONED A
 1/0 MIN IS REQUIRED FOR 400A SERVICE.
 250.66,310.15B6
 A NOTE WAS ADDED TO FEEDERS, HOWEVER
 RISER WAS NOT CORRECTED.
 RISER WENT FROM THE PREVIOUS #2 TO #1.
  
 THE ABOVE HAS BEEN REDLINED ON PLANS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-08-24 Cont ID  
Sent By dpalmer Date 2005-08-24 Time 15:21 Rev Time 0.33
Received By dpalmer Date 2005-08-24 Time 14:55 Sent To  
Notes
2005-08-24 00:00:00** UNSAT ***
  
  
 PLEASE SEE COMMENTS FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE SEE PANEL "B" SHOWS AN
 AHU WITH A 10KW HEATM HOWEVER LOADS
 CALCS INDICATE A 5KW UNIT??
 PLEASE CORRELATE.
 215.5,220
  
 2)NOTE: PLEASE SEE GROUNDING ELECTRODE
 WAS NOTED AND CHANGED UNDER FEEDERS TO
 SUB-PANELS, HOWEVER PLEASE SEE GROUNDING
 ELECTRODE CONDUCTOR SHOWN ON RISER STILL
 SHOWS A #2. PLEASE CORRECT TO 1/0 MIN.
 250.66,310.15B6
  
 3)NOTE: REDLINED 210.52C1 FOR KITCHEN
 GFI? THIS IS A REDLINED ITEM, HOWEVER
 PLANS ARE COMING BACK. PLEASE SEE THIS
 WAS NOT NOTED ON PREVIOUS NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 20:30 Rev Time 0.50
Received By dpalmer Date 2005-08-18 Time 20:19 Sent To  
Notes
2005-08-18 00:00:00************ UNSAT *************
  
  
 1)NOTE: PLEASE SEE RISER DIAGRAM NOW
 SHOWS OCP FOR EACH PANEL. PLEASE SEE
 RISER NOW SHOWS PANEL "B" UPGRADED FROM
 THE PREVIOUS 150A PANEL TO 200A BRKR
 FEEDING A 200A PANEL. THIS IS OK,
 HOWEVER PLEASE SEE FEEDERS WERE NOT
 UPGRADED FROM 150A TO 200A. PLEASE SEE
 310.15B6 FOR MIN FEEDERS.
 PLEASE SEE MIN CONDUIT SIZE PER TABLES
 IN CHAPTER 9.
  
 2)NOTE: PLEASE SEE NOW SERVICE IS BEING
 SHOWN UPGRADED FROM PREVIOUS 300A'S TO
 400A'S. PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR IS TO BE A 1/0 PER
 310.15B6, 250.66.
  
 3)NOTE: PLEASE SEE REVISED LOAD
 CALCULATIONS FOR PANEL "B". PLEASE SEE
 PANEL SCHEDULE INDICATES THREE CENTRAL
 A/C SYSTEMS, 1-10KW AND TWO -5KW HEAT
 STRIPS, PLEASE SEE LOAD CALCULATIONS
 ONLY SHOW ONE 5KW UNIT?
 PLEASE CORRELATE.
 215.5,220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 09:28 Rev Time 0.20
Received By dpalmer Date 2005-05-18 Time 09:28 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 PLEASE SEE SOME MODELS SHOW THESE AS
 "OPT". EACH PLAN MUST REFLECT THE ACTUAL
 INSTALLATION PER WHICH ARE INSTALLED OR
 NOT INSTALLED.
 215.5
  
 7)NOTE:
  
 8)NOTE:
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 17:39 Rev Time 0.30
Received By dpalmer Date 2005-02-23 Time 17:39 Sent To  
Notes
2005-02-23 00:00:00REDLINED
 POOL EQUIPMENT SHOWN ON PLANS BUT NOT ON
 PANEL SCHEDULE/LOAD CALCS.
 THIS EQUIPMENT MAY NOT BE FULLY KNOWN AT
 THIS TIME AND MAY BE REVISED ON PANEL
 SCHEDULE AND LOAD CALCS BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 20:19 Rev Time 0.33
Received By dpalmer Date 2004-11-12 Time 20:09 Sent To P
Notes
2004-11-12 00:00:00 
  
 ******** NOTE **********
  
 PLEASE SEE LOAD CALCS SHOWS HI-HAT LOAD
 AT 48.0 KW? 64@75W IS 4.8KW??
  
 PLEASE SEE SERVICE SIZE HAS NOW BEEN
 CHANGED TO A 300A SERVICE.
 A #2 FOR GROUNDING ELECTRODE
 CONDUCTOR.250.66
  
 THE ABOVE WAS REDLINED ON PLANS AND MAY
 BE REVISED AFTER PERMIT IS ISSUED.
  
  
 ** SENT TO PLUMB DUE TO NEW SHEETS IN
 SETS.***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-20 Cont ID  
Sent By dpalmer Date 2004-09-20 Time 06:50 Rev Time 0.25
Received By dpalmer Date 2004-09-20 Time 06:50 Sent To M
Notes
2004-09-20 00:00:00********* UNSAT *******
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE VERIFY OCP SHOWN FOR
 WHAT APPEARS TO BE A 5KW HEAT-STRIP IN
 AHU #2. SHOWN W/ 60A W/ #6 AWG.
 424.3B
  
 4)NOTE: PLEASE SEE NOTE #14 IN GENERAL
 NOTES. MENTIONS SD'S TO WIRED W/ BATH/
 KITCHEN LTS. PLEASE SEE 210.12 2002 NEC,
 THIS WOULD REQUIRE EITHER CIRCUIT TO BE
 ARC FAULT PROTECTED.
  
 5)NOTE: PLEASE SEE MASTER SUITE, RECEPT
 REQUIRED TO BE W/IN 6' OF DOOR.
 210.52
  
 **PLEASE SEE IDENTIFICATION OF SINGLE
 GARAGE SHOWN AS 3-CAR GARAGE. THIS IS
 ONLY A NOTE FOR WHAT APPEARS TO BE A
 MISPRINT.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:37 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:37 Sent To E
Notes
2005-08-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 13:48 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 13:48 Sent To P
Notes
2005-08-19 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 17:50 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 17:50 Sent To E
Notes
2005-08-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 15:57 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 15:57 Sent To M
Notes
2005-05-24 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:38 Sent To E
Notes
2005-05-16 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-16 Cont ID  
Sent By adarroug Date 2005-02-16 Time 13:37 Rev Time 0.00
Received By adarroug Date 2005-02-16 Time 13:37 Sent To E
Notes
2005-02-16 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 14:22 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 14:22 Sent To B
Notes
2005-01-07 00:00:00TO "ROB MCD" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 11:12 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 11:12 Sent To B
Notes
2004-12-10 00:00:00SENT TO "ROB MCD" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 13:28 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 13:28 Sent To E
Notes
2004-11-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By mmclean Date 2004-09-16 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2004-09-15 Time 15:57 Sent To  
Notes
2004-09-17 00:00:00TO SFD RACK/E
2004-09-15 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date 2005-05-31 Cont ID  
Sent By pkrauss Date 2005-05-31 Time 14:21 Rev Time 0.00
Received By pkrauss Date 2005-05-31 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-07 Cont ID  
Sent By dpalmer Date 2004-09-20 Time 06:50 Rev Time 0.25
Received By pkrauss Date 2004-10-07 Time 13:25 Sent To P
Notes
2004-10-07 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW, ONLY ENERGY AND MANUAL J
 CALCULATIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-31 Cont ID  
Sent By jleech Date 2005-08-31 Time 13:41 Rev Time 0.50
Received By jleech Date 2005-08-31 Time 13:41 Sent To  
Notes
2005-08-31 00:00:00AS BUILTS PLUMBING RISER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 07:22 Rev Time 0.25
Received By kstevens Date 2004-11-22 Time 07:22 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 13:26 Rev Time 1.00
Received By gsalfeld Date 2004-10-20 Time 12:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-09-16 Cont ID  
Sent By mmclean Date 2004-09-16 Time 16:57 Rev Time 0.00
Received By mmclean Date 2004-09-16 Time 16:57 Sent To I
Notes
2005-01-12 00:00:00WALL WILL BE BUILT AT THE SAME TIME OF
 THE HOUSE.NO PERMIT IS REQUIRED TO BE
 PULLED SEPERATE.APPROVED WITH
 STURCTURE OF HOUSE.
2004-09-16 00:00:00MUST PULL SEPARATE PERMIT FOR PRIVACY
 WALL MM