Plan Review Details - Permit 04090003
Plan Review Stops For Permit 04090003
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By shill Date 2004-11-05 Time 07:14 Rev Time 1.00
Received By shill Date 2004-11-04 Time 17:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-12 Cont ID  
Sent By shill Date 2004-10-12 Time 16:00 Rev Time 2.00
Received By shill Date 2004-10-12 Time 16:00 Sent To PC
Notes
2004-10-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE LOCATION OF THE CUTTING OF THE
 FLOOR IS REQUIRED TO BE DESIGNED BY AN
 ENGINEER.ALSO A THRESHHOLD INSPECTOR
 IS REQUIRED TO INSPECT THIS WORK.THE
 INSPECTOR IS TO BE APPROVED BEFORE THE
 PERMIT IS ISSUED.PLEASE CONTACT HAROLD
 PISKURA, 805-6711.
  
 2.)POSSIBLE PROPOSED NICHES ARE SHOWN
 IN THE TENANT PARTITION WALL (TOP
 RIGHT).PROVIDE A DETAIL TO SHOW HOW
 THE REQUIRED FIRE RESISTANCE WILL BE
 MAINTAINED.
  
 3.)THE ARCHITECT'S SEAL IS REQUIRED TO
 BE DATED, FAC61G1-15.003,004.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-12-23 Cont ID  
Sent By btrobaug Date 2005-12-22 Time 09:14 Rev Time 0.75
Received By btrobaug Date 2005-12-16 Time 09:15 Sent To PC
Notes
2005-12-23 00:00:00MARC BROUGHT IN CALCS AND PROPOSAL
 INDICATING THE COST WAS IN THE APPLIED
 VALUE./WRT.
2005-12-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A LOAD CALCULATION
 INCLUDING THE ADDED LOADS.
  
 2} INCREASE THE VALUE OF THE PROJECT TO
 INCLUDE THE ADDED LABOR AND EQUIPMENT
 ASSOCIATED WITH THIS REVISION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-07-08 Cont ID  
Sent By btrobaug Date 2005-07-08 Time 11:48 Rev Time 0.50
Received By btrobaug Date 2005-07-08 Time 11:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-06 Cont ID  
Sent By btrobaug Date 2005-07-06 Time 12:46 Rev Time 0.50
Received By btrobaug Date 2005-07-06 Time 12:43 Sent To PC
Notes
2005-07-06 00:00:00 
  
 REVISIONS MADE TO PLANS MUST BE DONE BY
 THE DESIGNER OF RECORD PER 481 FS.
  
 PLEASE SUBMIT TWO SETS OF PLANS FOR
 REVIEW. ONLY ONE SET IS SIGNED AND
 SEALED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-06 Cont ID  
Sent By btrobaug Date 2005-06-06 Time 12:17 Rev Time 0.33
Received By btrobaug Date 2005-06-06 Time 11:56 Sent To PC
Notes
2005-06-06 00:00:00 
 REVISIONS MADE TO PLANS MUST BE DONE BY
 THE DESIGNER OF RECORD PER 481 FS.
  
 PLEASE SUBMIT TWO SETS OF PLANS FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 17:16 Rev Time 0.33
Received By dpalmer Date 2005-03-08 Time 17:16 Sent To  
Notes
2005-03-08 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE FROM PLANS SUBMITTED,
 COMPLETE SCOPE OF WORK HAS CHANGED FROM
 ORIGINAL PERMIT. IF SOME OF THIS WORK IS
 EXISTING, PLEASE SHOW.
 PLEASE SEE VLAUE FOR SCOPE OF WORK FROM
 ORIGINAL PERMIT APPLICATION SHALL
 INCREASE PER FBC 104.6.5.
  
 2)NOTE: PLEASE SEE ALL CHANGES TO PLANS
 MUST BE DONE BY THE ARCHITECT OF RECORD.
 PLEASE SEE PLANS MUST ALSO BE SIGNED ,
 DATED AND SEALED BY ARCH OF RECORD.
 PER FS 481.221
  
 PLEASE NOTE: IF REMODEL OF UNIT HAS
 EXCEEDED PERCENTAGE ALLOWED UNDER FBC
 CHAPTER 34, SUCH ITMES AS ARC FAULT
 PROTECTION MAY BE REQUIRED TO BE BROUGHT
 UP TO 2002 NEC 210.12.
 THIS BLDG WAS DONE UNDER 99 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 06:42 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 06:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:44 Sent To  
Notes
2004-10-01 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL.
  
 3) ALL EXISTING FIRE SAFETY EQUIPMENT
 SHALL REMAIN IN SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 14:42 Sent To E
Notes
2005-07-07 00:00:00TO "BTROBAUG" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 08:08 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 08:08 Sent To E
Notes
2005-06-30 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 11:50 Rev Time 0.00
Received By shill Date 2005-06-08 Time 11:50 Sent To E
Notes
2005-06-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 09:45 Sent To E
Notes
2005-03-08 00:00:00TO "DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 10:58 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 10:58 Sent To M
Notes
2005-03-03 00:00:00TO PKRAUSS DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 10:01 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 10:01 Sent To P
Notes
2004-12-10 00:00:00SENT TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 16:56 Sent To  
Notes
2004-12-07 00:00:00SENT TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 16:26 Sent To  
Notes
2004-11-16 00:00:00SENT TO "P" TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:35 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:34 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-12 Cont ID  
Sent By shill Date 2004-10-12 Time 16:10 Rev Time 0.00
Received By shill Date 2004-09-01 Time 10:13 Sent To  
Notes
2004-09-01 00:00:00TO COMM BD#16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-11 Cont ID  
Sent By pkrauss Date 2005-03-11 Time 13:27 Rev Time 0.25
Received By pkrauss Date 2005-03-11 Time 13:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2005-03-10 Time   Rev Time 0.00
Received By hmoser Date 2005-03-10 Time 15:22 Sent To  
Notes
2005-03-10 00:00:00PLAN DENIED
 REVISON ON ARCHITECT PAPPER.NEED SEAL
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-09-21 Cont ID  
Sent By pkrauss Date 2004-09-21 Time 07:33 Rev Time 0.15
Received By pkrauss Date 2004-09-21 Time 07:33 Sent To  
Notes
2004-09-21 00:00:00DENIED:
 PLEASE PROVIDE MECHANICAL SCOPE OF WORK
 AND PLANS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-10 Cont ID  
Sent By kstevens Date 2004-12-10 Time 11:21 Rev Time 0.75
Received By kstevens Date 2004-12-10 Time 11:21 Sent To  
Notes
2004-12-10 00:00:00SEE ATTACHED SHEET FOR BATHROOM LAYOUT
 FIXTURE CHANGE OUT - MOVE W/C AND LAV
 MINIMAL DISTANCE - NO RISER DIAGRAM
 REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 11:54 Rev Time 0.33
Received By kstevens Date 2004-11-27 Time 11:54 Sent To  
Notes
2004-11-27 00:00:00DENIED
 REFERENCE; FBC-2001 CHAPTER 1
  
 1) THE SANITARY SYSTEM IS A SOVENT
 SYSTEM AND THE WATER CLOSET CAN NOT
 DISCHARGE DIRECTLY INTO THE STACK ON A
 SOVENT SYSTEM, BUT MUST CONNECT INTO THE
 AERATOR BELOW THE FLOOR OF THE UNIT
 BEING MODIFIED PER THE DESIGN CRITERIA
 OF THE SYSTEM. SECTION 104.2.1 AND
 DESIGN CRITERIS OF THE SOVENT SYSTEM
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 13:59 Rev Time 0.62
Received By kstevens Date 2004-11-08 Time 13:59 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) WALL MOUNT WATER CLOSET SHALL BE
 PIPED IN DIFFERENT THAN THE FLOOR MOUNT
 WATER CLOSET. SINCE THIS IS AN
 ENGINEERED SYSTEM, AN ENGINEERED
 SANITARY RISER DIAGRAM WILL BE
 REQUIRED.
 SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 08:01 Rev Time 0.50
Received By kstevens Date 2004-10-09 Time 08:01 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PLANS INDICATE REMOVAL OF WASH
 MACHINE. SANITARY AND WATER CONNECTIONS
 FOR WASH MACHINE ARE REQUIRED PER TABLE
 403.1. PLEASE CLARIFY HOW THESE CONNECT-
 IONS WILL BE PRESERVED.
  
 2) DEMO SHEET A.001 INDICATES THAT THE
 W/C AND LAV WILL BE FLIPPED IN THE BATH
 ROOM BY DINING ROOM. NEW FLOOR PLAN DOES
 NOT REFLECT THIS NOTE. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]