| 2004-11-15 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE SOME OF THE COMMENTS |
| | |
| | FROM FIRST REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 2)NOTE: PLEASE INCLUDE CWP AS PART OF |
| | THE GROUNDING ELECTRODE SYSTEM. 250.50 |
| | |
| | 3)NOTE: PLEASE SEE NOT ALL SHEETS HAVE |
| | THE PRINTED NAME AND SIGNATURE OF PERSON |
| | RESPONSIBLE FOR PLAN, PLEASE ALSO SEE |
| | RISER DIAGRAM. FBC 104.2.1 |
| | |
| | 4)NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER 210.52D |
| | AND 210.11C3 20A/#12 |
| | |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED. 210.8A6 |
| | PLEASE ALSO SEE SPACING PER 210.52C1, |
| | (ABOVE) WINE COOLER AND DW? |
| | |
| | 7)NOTE: PLEASE SEE TWO DIFFERENT |
| | ELECTRICAL DRAWINGS FOR KITCHEN WAS |
| | SUBMITTED? |
| | |
| | 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER 220.31B |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE EACH ROOM IS SHOWN ON |
| | AN INDIVIDUAL SHEET. UNABLE TO CLEARLY |
| | SEE WHERE SD'S WOULD BE LOCATED OUTSIDE |
| | BEDRMS. |
| | NFPA-71 8-1.4.1.6.2 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL.' |
| | |