Plan Review Details - Permit 04081385
Plan Review Stops For Permit 04081385
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-02 Cont ID  
Sent By alange Date 2005-06-02 Time 09:53 Rev Time 0.00
Received By jleech Date 2005-08-09 Time 14:01 Sent To  
Notes
2005-08-09 00:00:00ADDED PLUMBING UNDER WRONG STOP.
2005-06-02 00:00:00WINDOW P/A REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-19 Cont ID  
Sent By alange Date 2005-05-19 Time 08:17 Rev Time 1.00
Received By alange Date 2005-05-19 Time 07:33 Sent To  
Notes
2005-05-19 00:00:00REVISIONS TO FLOOR PLAN OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-30 Cont ID  
Sent By alange Date 2004-12-30 Time 10:22 Rev Time 0.50
Received By alange Date 2004-12-30 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-23 Cont ID  
Sent By alange Date 2004-12-23 Time 14:35 Rev Time 1.00
Received By alange Date 2004-12-23 Time 14:35 Sent To  
Notes
2004-12-23 00:00:00DENIED
  
 1.NOC EXPIRED
 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-30 Cont ID  
Sent By alange Date 2004-11-30 Time 08:08 Rev Time 0.75
Received By alange Date 2004-11-30 Time 07:37 Sent To  
Notes
2004-11-30 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.SUBMIT TWO COMPLETE COPIES OF
 PRODUCT APPROVALS WITH QUALITY
 ASSURANCE
 FOR ALL EXTERIOR DOORS, WINDOWS.
 ALL PRODUCT APROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-09-20 Time 16:47 Rev Time 1.00
Received By alange Date 2004-10-08 Time 07:50 Sent To  
Notes
2004-10-08 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. IF SHUTTERS ARE TO BE USED FOR IMPACT
 PROTECTION SUBMIT PRODUCT APPROVALS.
  
 4.SEPERATE PERMIT REQUIRED FOR POOL.
  
 5.SUBMIT 2 COPIES OF DCA APPROVALS
 WITH EACH PRODUCT APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SMOKE DETECTORS SHALL COMPLY WITH
 FBC 905.2
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-07-12 Cont ID  
Sent By btrobaug Date 2005-07-12 Time 09:35 Rev Time 0.50
Received By btrobaug Date 2005-07-12 Time 09:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 11:20 Rev Time 1.00
Received By btrobaug Date 2005-06-08 Time 09:46 Sent To PC
Notes
2005-06-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 AS NOTED IN THE TWO PREVIOUS REVIEWS,
 THE OPTIONAL STANDBY SYSTEM (GENERATOR
 AND RELATED EQUIPMENT) MUST BE APPLIED
 FOR UNDER A SEPERATE PERMIT. SEE
 REQUIREMENTS, PRIOR REVIEW.
  
 REVISIONS TO THE PLANS MUST BE MADE BY
 THE ARCHITECT, HANDRAWN CHANGES ARE
 UNACCEPTABLE. SEE FS 481.
  
 THE PANEL SCHEDULES DO NOT CORRELATE TO
 THE CIRCUIT NUMBERS ON THE PLAN. SEE
 D-16, PLEASE CHECK ALL PRIOR TO
 RESUBMITTING.
  
 NOTE 3 FROM PRIOR, GEC STILL INCORRECT.
 SEE 250.66. NOTE: SERVICE INCREASED
 AGAIN, PLEASE LOOK AT REFERANCE THE
 TABLE INDICATED FOR PROPER SIZE.
  
 RECEPTACLE B-3 IN THE MASTER BEDROOM IS
 IN VIOLATION OF 210.11(C)(3).
  
 THIS REVISION IS BEING DENIED BECAUSE
 THE GENERATOR APPEARS AS PART OF THIS
 REVISION. ALL ITEMS NEED TO BE ADDRESSED
 ON RESUB.
  
 THE ORIGINAL VALUE MUST BE INCREASED TO
 REFLECT THE ADDITIONAL WORK. PLEASE SEE
 PERMIT CLERK WITH NEW VALUE AT TIME OF
 RESUBMITION. FEES MUST BE PAID PRIOR TO
 REVIEW. SEE 553.80 FS.
  
 PLEASE PROVIDE A SCHEMATIC OF THE
 ELECTRICAL SYSTEM FOR THE POOL WITH THAT
 PERMIT APPLICATION (TYPICAL).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-05-16 Cont ID  
Sent By dpalmer Date 2005-05-16 Time 07:16 Rev Time 0.30
Received By dpalmer Date 2005-05-16 Time 07:15 Sent To  
Notes
2005-05-16 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW. PLEASE SEE UNTIL PERMIT FOR GEN
 IS APPLIED FOR AND ISSUED. ELEC REV
 SHALL NOT BE ISSUED WITH APPROVAL OF
 GEN.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM. PLEASE
 METER/MAIN COMBO SHOWS 2-200A AND 1-125A
 BRKR FEEDING, 2-125A PANLES AND 1-200A
 PANEL??
 PLEASE LABEL AND CORRELATE.
 APPEARS TO HAVE 200A BRKR FEEDING 125A
 ATS/SUB-PANEL.
 PLEASE ALSO SEE CONDUCTORS SHOWN.
  
  
 PLEASE SEE REDLINED PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-04-12 Cont ID  
Sent By dpalmer Date 2005-04-12 Time 13:49 Rev Time 1.50
Received By dpalmer Date 2005-04-12 Time 13:49 Sent To P
Notes
2005-04-12 00:00:00*********** UNSAT ***************
  
 PLEASE SEE PLANS HAVE UNDERGONE MANY
 CHANGES SINCE PREVIOUS STAMPED PLANS.
 PLEASE SEE THE BELOW COMMENTS PERTAINING
 TO CHANGES.
  
  
 1)NOTE: PLEASE SEE PLANS NOW SHOW A NEW
 PROPOSED GENERATOR. PLEASE SEE THIS IS
 REQUIRED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT. THIS WILL REQUIRE SITE
 PLANS, COMPLETE RISER DIAGRAM,
 MANUFACTURE SPECS FOR GEN, ATS,
 PRIMEMOVER ETC.
 THIS WILL BE REVIEWED BY, ZONING, BLDG,
 PLUMB, MECH AND BLDG REVIEW ALL UNDER
 ONE PERMIT.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM FOR
 MAIN HOUSE PLANS WILL BE REQUIRED TO BE
 REVISED TO INCLUDE ALL NEW ELECTRICAL
 SERVICE EQUIPMENT. PLEASE SEE RISER DOES
 NOT INDICATE ANY ATS ETC AT THIS TIME.
  
 3)NOTE: PLEASE SEE SERVICE SIZE HAS NOW
 CHNAGED AND INCREASED TO 325A.
 PLEASE SEE MIN GROUNDING ELECTRODE
 CONDUCTOR PER 250.66. #2 MIN.
  
 4)NOTE: PLEASE SEE MIN CLEARENCE FOR
 PANEL "C" NOT SHOWN. 110.26
  
 5)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE MANY RECESSED LTS WERE ADDED,
 HOWEVER, NO ADDITIONAL LOADS PER ABOVE
 WAS ADDED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 04:13 Rev Time 0.25
Received By dpalmer Date 2004-12-23 Time 04:13 Sent To B
Notes
2004-12-23 00:00:00ELEC OK, STAMPED.
 \
 PREVIOUS BLDG REVIEW COMMENT REQUESTED A
 FILING OF NOC. RESPONSE: FILED 8/04,
 PLEASE SEE UNDER FS 713, NOC EXPIRES
 WITHIN 90 DAYS IF WORK HAS NOT
 COMMENCED.
 NOC NEEDS TO BE RE-RECORDED BEFORE
 PICKING UP OF PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-17 Cont ID  
Sent By dpalmer Date 2004-11-17 Time 10:50 Rev Time 0.50
Received By dpalmer Date 2004-11-17 Time 10:50 Sent To B
Notes
2004-11-17 00:00:00********* UNSAT ** 2ND REVIEW ********
  
 SOME NOTES FROM FIRST REVIEW STILL TO BE
 ADDRESSED.
  
  
 1)NOTE: PLEASE SHOW ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE(S) AS
 GFI/GFI PROTECTED PER 210.8A-6
 PLEASE SEE 210.52C1 FOR RECEPT SPACING.
  
 2)NOTE: PLEASE SEE OCP FOR AHU'S/ HEAT.
 PLEASE SEE 424.3B FOR SIZING @125%.
 MIN)
  
 3)NOTE: PLEASE SEE NOTES ON LOWER LEFT
 ARE NOW NOTEING 2000 NEC. ? MISPRINT?
 PLEASE SEE NOTE #22 MENTIONS ARC FAULT
 PROTECTION FOR RECEPTS ONLY.
 PLANS DO HAVE NOTE UNDER PANEL SCHEDULE
 FOR 210.12
 *** NOTE*** PLEASE SEE NOTE #20 STILL
 MENTIONS SD'S TO BE WIRED TO KIT AND
 BATH LT CIRCUITS. PLEASE SEE THAT THIS
 IS FINE AND PERMITTED BY CODE, HOWEVER,
 THEN THESE CIRCUITS ARE ALSO REQUIRED TO
 HAVE THE ARC FAULT PROTECTION. 210.12
 THIS IS ONLY A NOTE**
  
 4)NOTE: PLEASE SEE MCB PANEL INDICATES A
 250A MCB YET PANEL INDICATES A 200A
 BUS?
 PLEASE CORRELATE.
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS. THIS REQUIRES 1ST 8KW AT
 100% AND REMAINDER @40%. THE 100% FOR
 A/C HEAT LOAD WAS CORRECTED.
  
 6)NOTE: PLEASE SEE AIC CALCULATION IS
 SHOWN IN THE UPPER LEFT HAND CORNER OF
 PLANS WHICH INDICATES A 12,781 AVAILABLE
 FUALT CURRENT AT MAIN YET MCB PANEL IS
 SHOWN W/ AND 10,000 RATED MAIN? PLEASE
 CORRELATE. THIS PANEL "A" WOULD REQUIRE
 A 22,000 AIC RATING MIN.
 110.9
  
 7)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE OLD SHEETS AND INSERT ONLY
 NEW SHEETS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-14 Time 14:49 Rev Time 0.50
Received By dpalmer Date 2004-09-16 Time 17:37 Sent To P
Notes
2004-09-16 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 PLEASE SEE BOTH STAIRS
  
 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT. MIN 125%.
 30A SHOWN FOR 7.5KW
  
 7)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE ALSO CORRELATE LOADS ON EACH
 PANEL/ LOAD CALCS/ AND MDP.
  
 8 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 PLEASE ALSO SEE NOTES FOR SD'S ON KIT/
 BATH LT-ING CIRCUIT.
  
 9)NOTE: PLEASE SEE THERE ARE NOTES
 REFLECTING OLD CODE. PLEASE ADJUST NOTES
 AND CODES PER 2002 NEC.
 THE STATE ADOPTED THE 2002 NEC JULY 1ST,
 2003
  
 10)NOTE: PLEASE SEE 210.11C1, 220.16
 A MIN OF 2-SMALL APPLIANCE CIRCUITS
 REQUIRED. APPEARS TO SHOW ONE?
 MISPRINT?
  
 11)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 13:32 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 13:32 Sent To M
Notes
2005-08-18 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 14:25 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 14:25 Sent To M
Notes
2005-07-29 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 11:07 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 11:07 Sent To G
Notes
2005-07-05 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 13:40 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 13:40 Sent To B
Notes
2005-05-11 00:00:00TO "ALANGE" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 13:38 Sent To E
Notes
2005-05-11 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 11:33 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 11:33 Sent To M
Notes
2005-05-11 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 13:45 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 13:45 Sent To E
Notes
2005-04-06 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 13:26 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 13:26 Sent To E
Notes
2004-12-14 00:00:00SENT TO "DP" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-10 Cont ID  
Sent By csiegber Date 2004-11-10 Time 15:01 Rev Time 0.00
Received By csiegber Date 2004-11-10 Time 15:01 Sent To E
Notes
2004-11-10 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 14:49 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 14:49 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-09-01 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 14:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-07-13 Cont ID  
Sent By rregueir Date 2005-07-13 Time 17:17 Rev Time 0.00
Received By rregueir Date 2005-07-13 Time 17:17 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-19 Cont ID  
Sent By prafter Date 2005-05-19 Time 08:35 Rev Time 0.75
Received By prafter Date 2005-05-19 Time 08:34 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-20 Cont ID  
Sent By jleech Date 2004-09-18 Time 12:24 Rev Time 0.00
Received By PKRAUS Date 2004-09-18 Time 17:16 Sent To B
Notes
2004-09-20 00:00:00PROVISO:
 PROVIDE MANUFACTURER SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR THE GAS
 DRYER, WATER HEATER AND COOKTOP IF THE
 EQUIPMENT IS NEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-08-09 Cont ID  
Sent By jleech Date 2005-08-09 Time 14:38 Rev Time 0.00
Received By jleech Date 2005-08-09 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-08-09 Cont ID  
Sent By jleech Date 2005-08-09 Time 14:04 Rev Time 0.50
Received By jleech Date 2005-08-09 Time 14:04 Sent To  
Notes
2005-08-09 00:00:00 
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-10 Cont ID  
Sent By kstevens Date 2005-06-10 Time 11:35 Rev Time 0.48
Received By kstevens Date 2005-06-10 Time 11:35 Sent To  
Notes
2005-06-10 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 09:21 Rev Time 0.75
Received By kstevens Date 2005-05-28 Time 09:21 Sent To B1
Notes
2005-05-28 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A. FROM PREVIOUS REVIEW THE FOLLOWING
 COMMENTS WERE NOT ADDRESSED:
 1) SHT M-1 SANITARY RISER DIAGRAMS DO
 NOT MEET CODE REQUIREMENTS, NOR DO THEY
 REFLECT THE FLOOR PLAN. CORRECT THE
 FOLLOWING:
 A. KITCHEN SINK RISER INDICATES TO
 EXISTING 3" MAIN, BUT FLOOR PLAN STATES
 EXISTING 4" SAN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
 B. MASTER BATH RISER SHOWS A HORIZONTAL
 DRY VENT. THIS IS NOT APPROVED PER
 SECTIONS 905.3 & 905.4.
 C. UTILITY ROOM RISER SHOWS A BRANCH
 ARM TO "US" FIXTURE ABOVE THE WASH
 MACHINE DRAIN LINE. THIS IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 B. NO ACTION TAKEN ON THE FOLLOWING
 REQUIREMENTS:
 2) NEW GENERATOR SHOWN ON PLANS. A
 RES-GEN PERMIT IS REQUIRED. A SURVEY
 SHOWING THE LOCATION OF THE GENERATOR IS
 REQUIRED. SHOW THE LOCATION OF ALL
 OPENINGS IN THE HOUSE AND SHOW THE
 LOCATION OF ADJOINING PROPERTY LINE AND
 THE LOCATION OF STRUCTURES ON ADJOINING
 PROPERTY. A BUILDING, ZONING,
 MECHANICAL, ELECTRICAL, & GAS REVIEW
 WILL BE REQUIRED.
 3) SEPARATE GAS PLANS & PERMIT ARE
 REQUIRED. SEE ATTACHED SHEET SHOWING GAS
 PERMIT APPLICATION REQUIREMENTS. THESE
 REQUIREMENTS SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE GAS PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By kstevens Date 2005-04-20 Time 14:40 Rev Time 1.78
Received By kstevens Date 2005-04-20 Time 14:40 Sent To  
Notes
2005-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) SHT M-1 SANITARY RISER DIAGRAMS DO
 NOT MEET CODE REQUIREMENTS, NOR DO THEY
 REFLECT THE FLOOR PLAN. CORRECT THE
 FOLLOWING:
 A. KITCHEN SINK RISER INDICATES TO
 EXISTING 3" MAIN, BUT FLOOR PLAN STATES
 EXISTING 4" SAN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
 B. MASTER BATH RISER SHOWS A HORIZONTAL
 DRY VENT. THIS IS NOT APPROVED PER
 SECTIONS 905.3 & 905.4.
 C. UTILITY ROOM RISER SHOWS A BRANCH
 ARM TO "US" FIXTURE ABOVE THE WASH
 MACHINE DRAIN LINE. THIS IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 2) NEW GENERATOR SHOWN ON PLANS. A
 RES-GEN PERMIT IS REQUIRED. A SURVEY
 SHOWING THE LOCATION OF THE GENERATOR IS
 REQUIRED. SHOW THE LOCATION OF ALL
 OPENINGS IN THE HOUSE AND SHOW THE
 LOCATION OF ADJOINING PROPERTY LINE AND
 THE LOCATION OF STRUCTURES ON ADJOINING
 PROPERTY. A BUILDING, ZONING,
 MECHANICAL, ELECTRICAL, & GAS REVIEW
 WILL BE REQUIRED.
 3) SEPARATE GAS PLANS & PERMIT ARE
 REQUIRED. SEE ATTACHED SHEET SHOWING GAS
 PERMIT APPLICATION REQUIREMENTS. THESE
 REQUIREMENTS SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE GAS PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-09-18 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 17:38 Rev Time 0.50
Received By jleech Date 2004-09-18 Time 12:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-08-30 Time 14:31 Rev Time 0.00
Received By mmclean Date 2004-09-01 Time 15:19 Sent To I
Notes
2004-09-01 00:00:00MUST PULL SEPARATE PERMIT FOR POOL &
 FENCE & DECK MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved