| Plan Review Stops For Permit 04081385 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-02 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2005-08-09 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | ADDED PLUMBING UNDER WRONG STOP. | | 2005-06-02 00:00:00 | WINDOW P/A REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-19 |
Time |
08:17 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2005-05-19 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2005-05-19 00:00:00 | REVISIONS TO FLOOR PLAN OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-30 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-12-30 |
Time |
10:22 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-12-30 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-12-23 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-12-23 |
Time |
14:35 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-12-23 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2004-12-23 00:00:00 | DENIED | | | | | | 1.NOC EXPIRED | | | 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-11-30 |
Time |
08:08 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2004-11-30 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2004-11-30 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 5.SUBMIT TWO COMPLETE COPIES OF | | | PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE | | | FOR ALL EXTERIOR DOORS, WINDOWS. | | | ALL PRODUCT APROVALS REQUIRE THE | | | FOLLOWING. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-09-20 |
Time |
16:47 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-10-08 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2004-10-08 00:00:00 | DENIED | | | | | | 1. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY | | | COURTHOUSEAND A COPY SUBMITTED TO THIS | | | OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | 2. BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3. IF SHUTTERS ARE TO BE USED FOR IMPACT | | | PROTECTION SUBMIT PRODUCT APPROVALS. | | | | | | 4.SEPERATE PERMIT REQUIRED FOR POOL. | | | | | | 5.SUBMIT 2 COPIES OF DCA APPROVALS | | | WITH EACH PRODUCT APPROVAL. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 6.SMOKE DETECTORS SHALL COMPLY WITH | | | FBC 905.2 | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | ART LANGE | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6672 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-12 |
Time |
09:35 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-12 |
Time |
09:15 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-08 |
Time |
11:20 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2005-06-08 |
Time |
09:46 |
Sent To |
PC |
|
| Notes |
| 2005-06-08 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | AS NOTED IN THE TWO PREVIOUS REVIEWS, | | | THE OPTIONAL STANDBY SYSTEM (GENERATOR | | | AND RELATED EQUIPMENT) MUST BE APPLIED | | | FOR UNDER A SEPERATE PERMIT. SEE | | | REQUIREMENTS, PRIOR REVIEW. | | | | | | REVISIONS TO THE PLANS MUST BE MADE BY | | | THE ARCHITECT, HANDRAWN CHANGES ARE | | | UNACCEPTABLE. SEE FS 481. | | | | | | THE PANEL SCHEDULES DO NOT CORRELATE TO | | | THE CIRCUIT NUMBERS ON THE PLAN. SEE | | | D-16, PLEASE CHECK ALL PRIOR TO | | | RESUBMITTING. | | | | | | NOTE 3 FROM PRIOR, GEC STILL INCORRECT. | | | SEE 250.66. NOTE: SERVICE INCREASED | | | AGAIN, PLEASE LOOK AT REFERANCE THE | | | TABLE INDICATED FOR PROPER SIZE. | | | | | | RECEPTACLE B-3 IN THE MASTER BEDROOM IS | | | IN VIOLATION OF 210.11(C)(3). | | | | | | THIS REVISION IS BEING DENIED BECAUSE | | | THE GENERATOR APPEARS AS PART OF THIS | | | REVISION. ALL ITEMS NEED TO BE ADDRESSED | | | ON RESUB. | | | | | | THE ORIGINAL VALUE MUST BE INCREASED TO | | | REFLECT THE ADDITIONAL WORK. PLEASE SEE | | | PERMIT CLERK WITH NEW VALUE AT TIME OF | | | RESUBMITION. FEES MUST BE PAID PRIOR TO | | | REVIEW. SEE 553.80 FS. | | | | | | PLEASE PROVIDE A SCHEMATIC OF THE | | | ELECTRICAL SYSTEM FOR THE POOL WITH THAT | | | PERMIT APPLICATION (TYPICAL). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-16 |
Time |
07:16 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-05-16 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2005-05-16 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS | | | REVIEW. PLEASE SEE UNTIL PERMIT FOR GEN | | | IS APPLIED FOR AND ISSUED. ELEC REV | | | SHALL NOT BE ISSUED WITH APPROVAL OF | | | GEN. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM. PLEASE | | | METER/MAIN COMBO SHOWS 2-200A AND 1-125A | | | BRKR FEEDING, 2-125A PANLES AND 1-200A | | | PANEL?? | | | PLEASE LABEL AND CORRELATE. | | | APPEARS TO HAVE 200A BRKR FEEDING 125A | | | ATS/SUB-PANEL. | | | PLEASE ALSO SEE CONDUCTORS SHOWN. | | | | | | | | | PLEASE SEE REDLINED PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-12 |
Time |
13:49 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-04-12 |
Time |
13:49 |
Sent To |
P |
|
| Notes |
| 2005-04-12 00:00:00 | *********** UNSAT *************** | | | | | | PLEASE SEE PLANS HAVE UNDERGONE MANY | | | CHANGES SINCE PREVIOUS STAMPED PLANS. | | | PLEASE SEE THE BELOW COMMENTS PERTAINING | | | TO CHANGES. | | | | | | | | | 1)NOTE: PLEASE SEE PLANS NOW SHOW A NEW | | | PROPOSED GENERATOR. PLEASE SEE THIS IS | | | REQUIRED TO BE SUBMITTED UNDER A | | | SEPARATE PERMIT. THIS WILL REQUIRE SITE | | | PLANS, COMPLETE RISER DIAGRAM, | | | MANUFACTURE SPECS FOR GEN, ATS, | | | PRIMEMOVER ETC. | | | THIS WILL BE REVIEWED BY, ZONING, BLDG, | | | PLUMB, MECH AND BLDG REVIEW ALL UNDER | | | ONE PERMIT. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM FOR | | | MAIN HOUSE PLANS WILL BE REQUIRED TO BE | | | REVISED TO INCLUDE ALL NEW ELECTRICAL | | | SERVICE EQUIPMENT. PLEASE SEE RISER DOES | | | NOT INDICATE ANY ATS ETC AT THIS TIME. | | | | | | 3)NOTE: PLEASE SEE SERVICE SIZE HAS NOW | | | CHNAGED AND INCREASED TO 325A. | | | PLEASE SEE MIN GROUNDING ELECTRODE | | | CONDUCTOR PER 250.66. #2 MIN. | | | | | | 4)NOTE: PLEASE SEE MIN CLEARENCE FOR | | | PANEL "C" NOT SHOWN. 110.26 | | | | | | 5)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | PLEASE SEE MANY RECESSED LTS WERE ADDED, | | | HOWEVER, NO ADDITIONAL LOADS PER ABOVE | | | WAS ADDED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-23 |
Time |
04:13 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-23 |
Time |
04:13 |
Sent To |
B |
|
| Notes |
| 2004-12-23 00:00:00 | ELEC OK, STAMPED. | | | \ | | | PREVIOUS BLDG REVIEW COMMENT REQUESTED A | | | FILING OF NOC. RESPONSE: FILED 8/04, | | | PLEASE SEE UNDER FS 713, NOC EXPIRES | | | WITHIN 90 DAYS IF WORK HAS NOT | | | COMMENCED. | | | NOC NEEDS TO BE RE-RECORDED BEFORE | | | PICKING UP OF PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-17 |
Time |
10:50 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-11-17 |
Time |
10:50 |
Sent To |
B |
|
| Notes |
| 2004-11-17 00:00:00 | ********* UNSAT ** 2ND REVIEW ******** | | | | | | SOME NOTES FROM FIRST REVIEW STILL TO BE | | | ADDRESSED. | | | | | | | | | 1)NOTE: PLEASE SHOW ALL RECEPTS | | | SERVING KITCHEN COUNTERSPACE(S) AS | | | GFI/GFI PROTECTED PER 210.8A-6 | | | PLEASE SEE 210.52C1 FOR RECEPT SPACING. | | | | | | 2)NOTE: PLEASE SEE OCP FOR AHU'S/ HEAT. | | | PLEASE SEE 424.3B FOR SIZING @125%. | | | MIN) | | | | | | 3)NOTE: PLEASE SEE NOTES ON LOWER LEFT | | | ARE NOW NOTEING 2000 NEC. ? MISPRINT? | | | PLEASE SEE NOTE #22 MENTIONS ARC FAULT | | | PROTECTION FOR RECEPTS ONLY. | | | PLANS DO HAVE NOTE UNDER PANEL SCHEDULE | | | FOR 210.12 | | | *** NOTE*** PLEASE SEE NOTE #20 STILL | | | MENTIONS SD'S TO BE WIRED TO KIT AND | | | BATH LT CIRCUITS. PLEASE SEE THAT THIS | | | IS FINE AND PERMITTED BY CODE, HOWEVER, | | | THEN THESE CIRCUITS ARE ALSO REQUIRED TO | | | HAVE THE ARC FAULT PROTECTION. 210.12 | | | THIS IS ONLY A NOTE** | | | | | | 4)NOTE: PLEASE SEE MCB PANEL INDICATES A | | | 250A MCB YET PANEL INDICATES A 200A | | | BUS? | | | PLEASE CORRELATE. | | | | | | 5)NOTE: PLEASE SEE 220.31B FOR LOAD | | | CALCULATIONS. THIS REQUIRES 1ST 8KW AT | | | 100% AND REMAINDER @40%. THE 100% FOR | | | A/C HEAT LOAD WAS CORRECTED. | | | | | | 6)NOTE: PLEASE SEE AIC CALCULATION IS | | | SHOWN IN THE UPPER LEFT HAND CORNER OF | | | PLANS WHICH INDICATES A 12,781 AVAILABLE | | | FUALT CURRENT AT MAIN YET MCB PANEL IS | | | SHOWN W/ AND 10,000 RATED MAIN? PLEASE | | | CORRELATE. THIS PANEL "A" WOULD REQUIRE | | | A 22,000 AIC RATING MIN. | | | 110.9 | | | | | | 7)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL. THIS IS ONLY A NOTICE | | | GIVEN AT THIS TIME. | | | | | | | | | PLEASE REMOVE OLD SHEETS AND INSERT ONLY | | | NEW SHEETS INTO COMPLETE SETS FOR REVIEW | | | AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-09-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
14:49 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-09-16 |
Time |
17:37 |
Sent To |
P |
|
| Notes |
| 2004-09-16 00:00:00 | ********* UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 3) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 4)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 | | | PLEASE SEE BOTH STAIRS | | | | | | 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52E | | | | | | 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | | FOR AHU HEAT. MIN 125%. | | | 30A SHOWN FOR 7.5KW | | | | | | 7)NOTE: PLEASE SEE 220.31B FOR LOAD | | | CALCULATIONS. | | | PLEASE ALSO CORRELATE LOADS ON EACH | | | PANEL/ LOAD CALCS/ AND MDP. | | | | | | 8 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | PLEASE ALSO SEE NOTES FOR SD'S ON KIT/ | | | BATH LT-ING CIRCUIT. | | | | | | 9)NOTE: PLEASE SEE THERE ARE NOTES | | | REFLECTING OLD CODE. PLEASE ADJUST NOTES | | | AND CODES PER 2002 NEC. | | | THE STATE ADOPTED THE 2002 NEC JULY 1ST, | | | 2003 | | | | | | 10)NOTE: PLEASE SEE 210.11C1, 220.16 | | | A MIN OF 2-SMALL APPLIANCE CIRCUITS | | | REQUIRED. APPEARS TO SHOW ONE? | | | MISPRINT? | | | | | | 11)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-18 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-18 |
Time |
13:32 |
Sent To |
M |
|
| Notes |
| 2005-08-18 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-07-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-29 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-29 |
Time |
14:25 |
Sent To |
M |
|
| Notes |
| 2005-07-29 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-05 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-05 |
Time |
11:07 |
Sent To |
G |
|
| Notes |
| 2005-07-05 00:00:00 | TO "KSTEVENS" BOX/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-11 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-11 |
Time |
13:40 |
Sent To |
B |
|
| Notes |
| 2005-05-11 00:00:00 | TO "ALANGE" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-11 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-11 |
Time |
13:38 |
Sent To |
E |
|
| Notes |
| 2005-05-11 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-11 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-11 |
Time |
11:33 |
Sent To |
M |
|
| Notes |
| 2005-05-11 00:00:00 | TO "PKRAUSS" BOX/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
13:45 |
Sent To |
E |
|
| Notes |
| 2005-04-06 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-12-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-14 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-14 |
Time |
13:26 |
Sent To |
E |
|
| Notes |
| 2004-12-14 00:00:00 | SENT TO "DP" DESK./RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-10 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-10 |
Time |
15:01 |
Sent To |
E |
|
| Notes |
| 2004-11-10 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-09-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-14 |
Time |
14:49 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-30 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-09-01 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-30 |
Time |
14:31 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-07-13 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-07-13 |
Time |
17:17 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-05-19 |
Time |
08:35 |
Rev Time |
0.75 |
| Received By |
prafter |
Date |
2005-05-19 |
Time |
08:34 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-09-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-09-18 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
PKRAUS |
Date |
2004-09-18 |
Time |
17:16 |
Sent To |
B |
|
| Notes |
| 2004-09-20 00:00:00 | PROVISO: | | | PROVIDE MANUFACTURER SUBMITTAL AND | | | INSTALLATION INSTRUCTIONS FOR THE GAS | | | DRYER, WATER HEATER AND COOKTOP IF THE | | | EQUIPMENT IS NEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-09 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2005-08-09 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-09 |
Time |
14:04 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-08-09 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-10 |
Time |
11:35 |
Rev Time |
0.48 |
| Received By |
kstevens |
Date |
2005-06-10 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2005-06-10 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-05-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-28 |
Time |
09:21 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-05-28 |
Time |
09:21 |
Sent To |
B1 |
|
| Notes |
| 2005-05-28 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | A. FROM PREVIOUS REVIEW THE FOLLOWING | | | COMMENTS WERE NOT ADDRESSED: | | | 1) SHT M-1 SANITARY RISER DIAGRAMS DO | | | NOT MEET CODE REQUIREMENTS, NOR DO THEY | | | REFLECT THE FLOOR PLAN. CORRECT THE | | | FOLLOWING: | | | A. KITCHEN SINK RISER INDICATES TO | | | EXISTING 3" MAIN, BUT FLOOR PLAN STATES | | | EXISTING 4" SAN. PLEASE CORRELATE RISER | | | AND FLOOR PLAN. SECTION 104.2.1. | | | B. MASTER BATH RISER SHOWS A HORIZONTAL | | | DRY VENT. THIS IS NOT APPROVED PER | | | SECTIONS 905.3 & 905.4. | | | C. UTILITY ROOM RISER SHOWS A BRANCH | | | ARM TO "US" FIXTURE ABOVE THE WASH | | | MACHINE DRAIN LINE. THIS IS NOT SHOWN ON | | | THE FLOOR PLAN. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | B. NO ACTION TAKEN ON THE FOLLOWING | | | REQUIREMENTS: | | | 2) NEW GENERATOR SHOWN ON PLANS. A | | | RES-GEN PERMIT IS REQUIRED. A SURVEY | | | SHOWING THE LOCATION OF THE GENERATOR IS | | | REQUIRED. SHOW THE LOCATION OF ALL | | | OPENINGS IN THE HOUSE AND SHOW THE | | | LOCATION OF ADJOINING PROPERTY LINE AND | | | THE LOCATION OF STRUCTURES ON ADJOINING | | | PROPERTY. A BUILDING, ZONING, | | | MECHANICAL, ELECTRICAL, & GAS REVIEW | | | WILL BE REQUIRED. | | | 3) SEPARATE GAS PLANS & PERMIT ARE | | | REQUIRED. SEE ATTACHED SHEET SHOWING GAS | | | PERMIT APPLICATION REQUIREMENTS. THESE | | | REQUIREMENTS SHALL BE SUBMITTED WITH THE | | | APPLICATION FOR THE GAS PERMIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-20 |
Time |
14:40 |
Rev Time |
1.78 |
| Received By |
kstevens |
Date |
2005-04-20 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2005-04-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT M-1 SANITARY RISER DIAGRAMS DO | | | NOT MEET CODE REQUIREMENTS, NOR DO THEY | | | REFLECT THE FLOOR PLAN. CORRECT THE | | | FOLLOWING: | | | A. KITCHEN SINK RISER INDICATES TO | | | EXISTING 3" MAIN, BUT FLOOR PLAN STATES | | | EXISTING 4" SAN. PLEASE CORRELATE RISER | | | AND FLOOR PLAN. SECTION 104.2.1. | | | B. MASTER BATH RISER SHOWS A HORIZONTAL | | | DRY VENT. THIS IS NOT APPROVED PER | | | SECTIONS 905.3 & 905.4. | | | C. UTILITY ROOM RISER SHOWS A BRANCH | | | ARM TO "US" FIXTURE ABOVE THE WASH | | | MACHINE DRAIN LINE. THIS IS NOT SHOWN ON | | | THE FLOOR PLAN. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 2) NEW GENERATOR SHOWN ON PLANS. A | | | RES-GEN PERMIT IS REQUIRED. A SURVEY | | | SHOWING THE LOCATION OF THE GENERATOR IS | | | REQUIRED. SHOW THE LOCATION OF ALL | | | OPENINGS IN THE HOUSE AND SHOW THE | | | LOCATION OF ADJOINING PROPERTY LINE AND | | | THE LOCATION OF STRUCTURES ON ADJOINING | | | PROPERTY. A BUILDING, ZONING, | | | MECHANICAL, ELECTRICAL, & GAS REVIEW | | | WILL BE REQUIRED. | | | 3) SEPARATE GAS PLANS & PERMIT ARE | | | REQUIRED. SEE ATTACHED SHEET SHOWING GAS | | | PERMIT APPLICATION REQUIREMENTS. THESE | | | REQUIREMENTS SHALL BE SUBMITTED WITH THE | | | APPLICATION FOR THE GAS PERMIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-16 |
Time |
17:38 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2004-09-18 |
Time |
12:23 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-30 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-09-01 |
Time |
15:19 |
Sent To |
I |
|
| Notes |
| 2004-09-01 00:00:00 | MUST PULL SEPARATE PERMIT FOR POOL & | | | FENCE & DECK MM |
|
|