Plan Review Details - Permit 04081345
Plan Review Stops For Permit 04081345
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-07 Cont ID  
Sent By btrobaug Date 2004-10-07 Time 12:43 Rev Time 0.50
Received By btrobaug Date 2004-10-07 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:18 Rev Time 0.33
Received By dpalmer Date 2004-09-16 Time 13:46 Sent To  
Notes
2004-09-16 00:00:00******* UNSAT *******
  
 PLEASE SEE NOTES FROM FIRST REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 2)NOTE: PLEASE SEE A RISER DIAGRAM IS
 NOW BEING SUBMITTED, HOWEVER NO AIC
 RATING FOR EQUIPMENT IS BEING INDICATED
 AS REQUESTED ON PREVIOUS REVIEW.
 110.9/215.5
  
 3)NOTE: PLEASE VERIFY METHOD OF
 EQUIPMENT GROUNDING FROM MAIN TO PANEL,
 IS THIS RIGID ALSO? ONLY IF PVC.
 250.24
  
 4)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS.
  
 5)NOTE: PLEASE SEE SD'S ARE INDICATED
 ON SEPARATE CIRCUIT WHICH IS PERMITTED,
 THESE ARE ALSO REQUIRED TO BE ARC-FAULT
 PER 210.12 OF 2002 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-09-14 Time 16:12 Rev Time 0.50
Received By btrobaug Date 2004-08-31 Time 12:54 Sent To  
Notes
2004-08-31 00:00:00 
 PLEASE PROVIDE A RISER DIAGRAM PER 215.5
 WITH AIC RATINGS PER 110.9
  
 PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BC WIRE, OCP SIZES AND REQUIRED CIRCUIT
 COMPLIANCE CAN BE DETERMINED.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:18 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 14:18 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 16:12 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 16:12 Sent To E
Notes
2004-09-14 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:19 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 09:19 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved