| Plan Review Stops For Permit 04081257 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-11-12 |
Time |
10:24 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2004-11-12 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-11-01 |
Time |
15:22 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
2004-11-01 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2004-11-01 00:00:00 | BUILDING PLAN REVIEW | | | | | | 1. THE FLORIDA ENERGY CODE FORM IS | | | STILL | | | NOT SIGNED BY THE OWNER/AGENT. | | | | | | 2. ADDITIONAL FEES STILL UNPAID | | | TOTALING | | | $1865.11. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-09-16 |
Time |
11:51 |
Rev Time |
4.00 |
| Received By |
lsmith |
Date |
2004-10-06 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. THE ENERGY CODE FORM HAS TO BE SIGNED | | | BY THE OWNER/AGENT. | | | | | | 2. THE THERMA-TRU DOORS REQUIRE | | | HURRICANE PANELS. NO INFORMATION HAS | | | BEEN SUBMITTED FOR THE STORM PANELS. | | | | | | 3. THERE ARE NO PRODUCT APPROVALS FOR | | | THE SINGLE HUNG WINDOWS. | | | | | | 4. THE FIXED WINDOWS UNDER 30' WILL | | | REQUIRE HURRICANE PANELS. | | | | | | 5. A NOTICE OF COMMENCEMENT MUST BE | | | FILED AT THE PBC CLERK'S OFFICE AND A | | | COPY SUBMITTED BEFORE A PERMIT CAN BE | | | PRINTED | | | | | | 6. THERE ARE ADDITIONAL FEES OF | | | $1865.11DUE. | | | | | | 7. SUBMIT THE REQUIRED PRODUCT APPROVALS | | | FOR THE STORM PANELS. | | | | | | 8. THE LICENSES FOR THE A/C & BUILDING | | | CONTRACTOR HAVE EXPIRED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-26 |
Time |
18:20 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-07-26 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | REDLINED 210.52H |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-22 |
Time |
16:23 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-10-22 |
Time |
16:23 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-08-31 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-18 |
Time |
15:21 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-08-31 |
Time |
06:46 |
Sent To |
M |
|
| Notes |
| 2004-08-31 00:00:00 | *** NOTES REDLINED *** | | | | | | 1)NOTE: MISSING FRONT GFI RECEPT PER | | | 210.52E | | | | | | 2)NOTE: MISSING ALL REQUIRED SD'S PER | | | NFPA-72 8-1.4.1.6.2 | | | | | | IF ANY REVISIONS ARE MADE TO PLANS, | | | PLEASE ADDRESS ABOVE AT THAT TIME. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-25 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-25 |
Time |
11:36 |
Sent To |
E |
|
| Notes |
| 2005-07-25 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-25 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-25 |
Time |
11:35 |
Sent To |
P |
|
| Notes |
| 2005-07-25 00:00:00 | TO "P" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-08 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-08 |
Time |
11:01 |
Sent To |
P |
|
| Notes |
| 2004-11-08 00:00:00 | TO KS BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-11-01 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-18 |
Time |
15:21 |
Sent To |
E |
|
| Notes |
| 2004-10-18 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-27 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
2004-08-26 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2004-08-30 00:00:00 | TO SFD RACK/E | | 2004-08-26 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-31 |
Time |
06:54 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-09-16 |
Time |
11:51 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-08-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-08 |
Time |
08:47 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-08-08 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2005-08-08 00:00:00 | AS BUILTS PLUMBING RISER DIAGRAM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-10 |
Time |
16:15 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2004-11-10 |
Time |
16:15 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-11-01 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2004-11-01 |
Time |
15:15 |
Sent To |
B |
|
| Notes |
| 2004-11-01 00:00:00 | PLUMBING PLAN REVIEW DENIED FBC 2001 | | | SEC 909 WET VENTING. | | | ONLY THE FIFTURE WITHIN THE BATH ROOM | | | GROUP SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN.( WASH MACHINE) | | | ANY ADDITONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. | | | END OF COMMENTS,QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-22 |
Time |
16:23 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2004-09-15 |
Time |
19:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-27 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-08-27 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
2004-11-12 |
Time |
10:31 |
Sent To |
B |
|
| Notes |
| 2004-11-12 00:00:00 | APPROVED & STAMPED BY MMCLEAN 8/27/04 LS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-27 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-08-27 |
Time |
15:10 |
Sent To |
I |
|
| Notes |
| 2004-08-27 00:00:00 | MUST PULL A SEPARATE PERMIT FOR POOL MM |
|
|