Plan Review Details - Permit 04081247
Plan Review Stops For Permit 04081247
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-01 Cont ID  
Sent By rbrown Date 2005-02-01 Time 08:53 Rev Time 0.00
Received By rbrown Date 2005-02-01 Time 08:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-24 Cont ID  
Sent By rbrown Date 2005-01-24 Time 17:26 Rev Time 0.00
Received By rbrown Date 2005-01-24 Time 17:26 Sent To  
Notes
2005-01-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 489.105(3) F.S.THE SUBMITTED CHANGE
 OF CONTRACTOR LETTER REFERS TO FOUR
 PERMIT NUMBERS BUT DOES NOT INCLUDE
 THIS
 PERMIT NUMBER (04081247), SO IT IS NOT
 VALID FOR THIS PROJECT.THE WORK IS TO
 BE PERFORMED ON A BUILDING EXCEEDING
 THREE HABITABLE STORIES AND SO IT IS
 OUTSIDE THE SCOPE OF A RESIDENTIAL
 CONTRACTOR LICENSE, AS HELD BY JOSEPH
 JORY. SUBMIT A VALID CHANGE OF
 CONTRACTOR LETTER.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-19 Cont ID  
Sent By rbrown Date 2004-11-19 Time 18:00 Rev Time 0.00
Received By rbrown Date 2005-01-24 Time 17:18 Sent To  
Notes
2004-11-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) UNITY OF TITLE.THIS COMMENT HAS NOT
 BEEN ADDRESSED SINCE THE LAST REVIEW.
 THE PROPOSED CONNECTION OF ADJACENT
 CONDOS BREACHES THE FIRE SEPARATION
 BETWEEN UNITS.A 'UNITY OF TITLE' SHALL
 BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 TITLE' DOCUMENT SO THAT FBC 704.3 TENANT
 SEPARATION REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By rbrown Date 2004-10-06 Time 10:03 Rev Time 0.00
Received By rbrown Date 2004-10-06 Time 10:03 Sent To  
Notes
2004-10-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE PROPOSED CONNECTION OF ADJACENT
 CONDOS BREACHES THE FIRE SEPARATION
 BETWEEN UNITS.A 'UNITY OF TITLE' SHALL
 BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC 704.3
 TENANT SEPARATION REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM LICENSE NUMBER (SEE
 COMMENT BELOW, RE: CERTIFICATE OF
 AUTHORIZATION)
 - INCLUDE THE PRINTED NAME AND LICENSE
 NUMBER OF THE ARCHITECT SEALING THE
 PLANS
 - HAVE THE SEAL DATED BY THE ARCHITECT
  
 3) 481.219(2) F.S.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
  
 4) FBC 11-11THE BATHROOM DOOR AND THE
 DOORS LEADING TO THE BATHROOM SHALL HAVE
 A 29" CLEAR OPENING.
  
 5) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-27 Cont ID  
Sent By dpalmer Date 2005-01-27 Time 13:47 Rev Time 0.50
Received By dpalmer Date 2005-01-27 Time 13:47 Sent To  
Notes
2005-01-27 00:00:00ARCH CAME INAND PROVIDEDLETTERS, AND
 CORRECTED ELECTRICAL COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 13:14 Rev Time 0.00
Received By dpalmer Date 2005-01-24 Time 16:55 Sent To  
Notes
2005-01-24 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 NOW COMING BACK WITH TWO COMPLETELY
 DIFFERENT SIGNATURES.
 PLEASE SEE FS 481.221 WHICH REQUIRES
 PLANS TO BE SIGNED WITH LEGAL, ORIGINAL
 SIGNATURE.
 SINCE PLANS NOW HAVE TWO SIGNATURES,
 PLEASE SUBMIT A SIGNED, DATED AND SEALED
 NOTORIZED LTR FOR LEGAL SIGNATURE
 VERIFICATION. USE OF MORE THAN ONE
 SIGNATURE IS NOT PERMITTED AND WILL NOT
 BE ACCEPTED BY THIS OFFICE.
  
 2)NOTE: PLEASE SEE ATTACHED SHEETS
 SIGNED AND SEALED WITHOUT TITLE BLOCKS.
 REQUIRED PER FAC 61G1-16.004. PLEASE
 ALSO SEE ATTAHCED PLUMB SHEETS.
 PLEASE SEE ONE OF THE ELECTRICAL SHEETS
 HAVE GLUED ON PANEL SCHEDULES. PLEASE
 RE-PRINT AND HAVE PLANS RESIGNED AND
 SEALED, DATED. FS 481
  
 PLEASE SUBMIT TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 10:28 Rev Time 0.33
Received By dpalmer Date 2004-11-18 Time 10:28 Sent To  
Notes
2004-11-18 00:00:00****** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE:PLEASE SEE NOTE #5, PANEL
 SCHEDULES SHOWN, HOWEVER NO LOAD
 CALCULATIONS, RISER ETC HAVE BEEN
 SUBMITTED.
 PREVIOUS PLANS CALLED FOR NEW 100A
 PANEL, HOWEVER THESE PLANS ARE NOW
 CALLING FOR 125A PANELS.
 PLEASE PROVIDE INFORMATION ON THE NEW PR
 EXSITING FEEDS FOR THESE PANELS. OCP,
 AWG, CONDUIT SIZES ETC.
  
 2)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 MIN 20A #12 CIRCUITS REQUIRED FOR BATH
 GFI'S. PANEL SCHEDULE INDICATES 15A,
 #14.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFETC
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By dpalmer Date 2004-08-31 Time 10:20 Rev Time 0.50
Received By dpalmer Date 2004-08-31 Time 10:19 Sent To  
Notes
2004-08-31 00:00:00************* UNSAT ***************
  
 **PLEASE SEE PLANS ARE NOT COMPLETE AT
 THIS TIME FOR COMPLETE REVIEW.
 PLEASE SEE THE FOLLOWING NOTES.
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK. PLEASE ALSO SEE FS 481.219 FOR
 REQUIRED LICENSE #(S).
 PLEASE ALSO SEE ONLY ONE SET HAS BEEN
 SIOGNED AND SEALED. FBC 104.2.1 REQUIRES
 BOTH.
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHED-
 -ULE TO BE SUBMITTED.
 215.5
  
 5)NOTE: PLEASE SEE PLANS SHOW A NEW
 100A PANEL, YET NO OTHER INFORMATION IS
 GIVEN??
 OCP, AWG, CONDUIT(S) ETC.
 PLEASE ALSO SUBMIT LOAD CALCAULTIONS
 PER 215.5,220.31B
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-28 Cont ID  
Sent By mcarsill Date 2004-09-28 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2004-09-28 Time 15:34 Sent To  
Notes
2004-09-28 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED INSIDE AND OUTSIDE OF
 EACH SLEEPING ROOM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-10 Cont ID  
Sent By adarroug Date 2006-01-10 Time 10:40 Rev Time 0.00
Received By adarroug Date 2006-01-10 Time 10:40 Sent To P
Notes
2006-01-10 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 13:11 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 13:11 Sent To  
Notes
2005-01-24 00:00:00NOW "COMM BD#2"
2005-01-12 00:00:00TO "COMM BD#1" /RESUB#3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 11:03 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 13:49 Sent To  
Notes
2004-11-17 00:00:00SENT TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 14:30 Sent To  
Notes
2004-11-12 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-06 Cont ID  
Sent By kstevens Date 2004-10-06 Time 18:17 Rev Time 0.00
Received By kstevens Date 2004-08-25 Time 15:51 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-04 Cont ID  
Sent By pkrauss Date 2004-12-04 Time 09:30 Rev Time 0.35
Received By pkrauss Date 2004-12-04 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-09-18 Cont ID  
Sent By pkrauss Date 2004-09-18 Time 08:30 Rev Time 0.30
Received By pkrauss Date 2004-09-18 Time 08:25 Sent To  
Notes
2004-09-18 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES DUCT WORK
 BUT DOES NOT INDICATE IF THE A/C
 EQUIPMENT WILL BE NEW OR EXISTING.
 PLEASE CLARIFY.
  
 2.SEE ALSO COMMENT 1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 10:28 Rev Time 0.33
Received By jleech Date 2006-01-13 Time 10:28 Sent To  
Notes
2006-01-13 00:00:00SUBMITTAL FOR CLOSET FLANGES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-01 Cont ID  
Sent By kstevens Date 2005-02-01 Time 11:17 Rev Time 0.25
Received By kstevens Date 2005-02-01 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-09 Cont ID  
Sent By kstevens Date 2004-12-09 Time 07:47 Rev Time 0.33
Received By kstevens Date 2004-12-09 Time 07:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By kstevens Date 2004-10-06 Time 18:02 Rev Time 0.50
Received By kstevens Date 2004-10-06 Time 18:02 Sent To  
Notes
2004-10-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) BOTH SETS OF PLANS SHALL BE SIGNED,
 SEALED AND DATED BY THE ARCHITECT OF
 RECORD, AND SEAL SHALL SHOW ALL INFORM-
 ATION REQUIRED BY FAC 61G1-16.001 AND
 FS 481.221.
 2) TITLE BLOCK ON ALL SHEETS SHALL HAVE
 THE MINIMUM INFORMATION. FIRM LICENSE
 NUMBER, & SPACE FOR PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16
 .004(2) & (6). FS 481.2055
 3) A CERTIFICATE OF AUTHROIZATION NUMBER
 IS REQUIRED FOR THE ARCHITECTURAL COMP-
 ANY PER FS481.219
 4) SHT A-2 DEMO SHEET, IN THE INSTALLAT-
 ION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. - ALL CAPPED PIPING SHALL
 BE INSPECTED PRIOR TO COVERING.
 5) SHT A-6 DETAIL 6 MASTER BATH SHOWER
 SHOWS 28" WIDTH. SECTION 417.4 STATES,
 SHOWER COMPARTMENTS SHALL NOT BE LESS
 THAN 30" IN MINIMUM DIMENSION MEASURED
 FROM THE FINISHED INTERIOR DIMENSION AND
 SHALL BE MEASURED AS THE SIDE OF A REC-
 TANGLE.
 6) SHT M-1 PLUMBING NOTES 9 AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM NOTES. SEE
 SECTION 604.9 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE, ICE MAKER,
 AND DISHWASHER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]