Plan Review Details - Permit 04081214
Plan Review Stops For Permit 04081214
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By rbrown Date 2004-09-15 Time 10:22 Rev Time 0.00
Received By rbrown Date 2004-09-15 Time 10:22 Sent To  
Notes
2004-09-15 00:00:00PLANS REDLINED WITH PROVISO:
  
 ANY EXISTING FIRE DOORS AT THE ELEVATOR
 LOBBY SHALL BE RETAINED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-08-31 Cont ID  
Sent By dpalmer Date 2004-08-31 Time 08:50 Rev Time 0.25
Received By dpalmer Date 2004-08-31 Time 08:50 Sent To  
Notes
2004-08-31 00:00:00NO ELECTRICAL DEMO SHOWN.
 ELECTRICAL PERMIT REQUIRED FOR DEMO
 WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-14 Cont ID  
Sent By nmccray Date 2004-09-14 Time 16:00 Rev Time 0.00
Received By nmccray Date 2004-09-14 Time 15:59 Sent To  
Notes
2004-09-14 00:00:00SHALL COMPLY WITH NFPA 241

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-24 Cont ID  
Sent By kstevens Date 2004-09-24 Time 09:29 Rev Time 0.00
Received By kstevens Date 2004-08-25 Time 13:46 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-24 Cont ID  
Sent By pkrauss Date 2004-09-24 Time 09:31 Rev Time 0.35
Received By pkrauss Date 2004-09-24 Time 09:31 Sent To  
Notes
2004-09-24 00:00:00APPROVED 9-15-04/DEMO

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-09-24 Cont ID  
Sent By kstevens Date 2004-09-24 Time 09:29 Rev Time 0.50
Received By kstevens Date 2004-09-24 Time 09:29 Sent To  
Notes
***NONE***