Plan Review Details - Permit 04081124
Plan Review Stops For Permit 04081124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-03 Cont ID  
Sent By alange Date 2005-02-03 Time 11:27 Rev Time 1.00
Received By alange Date 2005-02-03 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-20 Cont ID  
Sent By alange Date 2005-01-20 Time 09:06 Rev Time 0.75
Received By alange Date 2005-01-20 Time 09:06 Sent To  
Notes
2005-01-20 00:00:00DENIED
  
 1. NOC ABOUT TO EXPIRE, (90 DAYS FROM
 ISSUANCE IF NO WORK HAS BEEN DONE)
 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 REQUIRE THE FOLLOWING TO BE ATTACHED;
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT:CHANGES HAVE BEEN MADE TO
 PLANS IN PENCIL.ALL CHANGES ARE TO BE
 IN INK AND SIGNED BY THE ARCHITECT OF
 RECORD.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-13 Cont ID  
Sent By alange Date 2004-12-13 Time 16:55 Rev Time 1.00
Received By alange Date 2004-12-13 Time 16:28 Sent To  
Notes
2004-12-13 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 4.SEE SMOKE DETECTOR REQUIREMENT AS
 MENTION IN ECECTRICAL REVIEW COMPLYING
 WITH FBC 905.2
  
 5.SHOW FINISH FLOOR OF ELEVATION OF
 NEW ROOM FORMALLY A GARAGE.MUST BE 4"
 ABOVE GRADE PER FBC 1804.1.7 WPB
 AMMENDMENTS.
  
 6.INCORRECT PRODUCT APPROVALS
 SUBMITTED FOR ENTRY DOOR.PLANS SHOW
 INSWING,PRODUCT APPROVALS ARE FOR
 OUTSWING.
  
 7. ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED TO THE QUALITY
 ASSURANCE.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 08:44 Rev Time 0.33
Received By dpalmer Date 2005-01-13 Time 08:44 Sent To P
Notes
2005-01-13 00:00:00REDLINED POOL PUMP. SHOWN @2P60A FOR
 POOL PUMP W/ 1600 VA LOAD?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 16:48 Rev Time 0.50
Received By dpalmer Date 2004-11-24 Time 16:48 Sent To P
Notes
2004-11-24 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 ** PLEASE SEEMISSING INSIDE AND
 OUTSIDE NEW BEDRM.
  
 3)NOTE: PLEASE SEE 210.52C3/ 210.8A6 FOR
 MISSING GFI RECEPT FOR NEW PENINSULAR.
  
 4)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL IN NEW MASTER BEDRM. 210.52
  
 5)NOTE: PLEASE SEE RECEPT OUTSIDE TO BE
 GFI. 210.8
  
 6)NOTE: PLEASE VERIFY PANEL LOCATION AND
 LOCATION OF WHAT IS TO BE A J-BOX IN NEW
 BATHRM WALL.
  
 7)NOTE: PLEASE SEE 1P60A POOL-PUMP??
 PLEASE VERIFY.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFET ELECTRICAL
 SHEETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 09:51 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 09:51 Sent To B
Notes
2005-01-31 00:00:00TO "AL" DESK/RESIB.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 11:42 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 11:42 Sent To E
Notes
2005-01-10 00:00:00PUT IN RESUB PACKAGE @"DP"
 DESK/SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 16:46 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 16:46 Sent To E
Notes
2005-01-06 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-22 Cont ID  
Sent By mjacobs Date 2004-11-22 Time 18:13 Rev Time 0.00
Received By mjacobs Date 2004-11-22 Time 18:13 Sent To E
Notes
2004-11-22 00:00:00SENT TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 07:58 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 07:58 Sent To Z
Notes
2004-11-16 00:00:00SENT TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 17:48 Rev Time 0.20
Received By pkrauss Date 2004-12-01 Time 17:48 Sent To B
Notes
2004-12-01 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 WITH THIS PERMIT APPLICATION

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-15 Cont ID  
Sent By jleech Date 2005-01-15 Time 13:08 Rev Time 0.33
Received By jleech Date 2005-01-15 Time 13:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 13:07 Rev Time 0.25
Received By kstevens Date 2004-11-27 Time 13:07 Sent To M
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 3 SANITARY RISER DIAGRAM DOES NOT
 MEET THE CODE REQUIREMENTS.
 A) LAV IS NOT VENTED, AND PIPED AS
 SHOWN WILL BE AN "S" TRAP WHICH IS NOT
 APPROVED. SECTION 1002.3(5)
 B) ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1 (THE WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM FIXTURES).
 2) SEE RED-LINE CORRECTIONS ON ONE SET
 OF PLANS SHOWING HOW THIS CAN BE
 CORRECTED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-22 Cont ID  
Sent By mmclean Date 2004-11-22 Time 16:38 Rev Time 0.00
Received By mmclean Date 2004-11-22 Time 16:38 Sent To I
Notes
***NONE***