Plan Review Details - Permit 04081123
Plan Review Stops For Permit 04081123
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-23 Cont ID  
Sent By alange Date 2005-05-23 Time 09:05 Rev Time 0.33
Received By alange Date 2005-05-23 Time 09:05 Sent To  
Notes
2005-05-23 00:00:00REVISION ADD WINDOW IN CLOSET OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-27 Cont ID  
Sent By alange Date 2005-01-27 Time 14:01 Rev Time 1.25
Received By alange Date 2005-01-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-04 Cont ID  
Sent By alange Date 2005-01-04 Time 13:44 Rev Time 1.66
Received By alange Date 2005-01-04 Time 11:16 Sent To  
Notes
2005-01-04 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.ADDITIONAL PERMIT FEES OF $2146.84
 ARE DUE.SEE PREVIOUS REVIEW FOR BREAK
 DOWN.
  
 6. SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR ROOFING, STRAPS AND TIE-DOWNS AND
 IMPACT PROTECTION.
 ALL PRODUCT APPROVALS REWUIRE THE
 FOLLOWING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.FBC 1707.4.4.2 WINDOW BUCK SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE
 FRAME SUCH THAT FULL SUPPORT IS
 PROVIDED.
 REVISE WINDOW BUCK DETAIL.
  
 9.FBC 2309.6 SHOW SIZE AND LOCATION OF
 ATTIC ACCESS.
  
 10.FBC 3401.7.1.2.1 SHOW HOW SMOKE
 DETECTORS WILL COMPLY WITH THIS
 SECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 16:44 Rev Time 2.75
Received By alange Date 2004-10-22 Time 13:08 Sent To  
Notes
2004-10-22 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. SEE ELECTRICAL REVIEW REGARDING
 TITLEBLOCK INFORMATION THAT IS RQUIRED
 BEFOREISSUING OF PERMIT.
  
 3.SHOW HOW SMOKE DETECTORS WILL
 COMPLY WITH 905.2 FBC
  
 4.BUILDING VALUE TOO LOW BASED ON
 SBCCI BUILDING VALUATION DATA.
 3240 SQ.FT. X $76.96 PER SQ.FT =
 $249,350.ADDITIONAL PERMIT FEES OF
 $2146.84 ARE DUE.
  
 5.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 6.SUBMIT 2 COMPLETE SETS OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS, WINDOWS,
 STRAPS AND TIEDOWNS, ROOFING AND
 IMPACT PROTECTION.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.FBC 1707.4.4.2 WINDOW BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE
 FRAME SUCH THAT FULL SUPPORT IS PROVIDED
  
 8.SHOW HOW LEDGER WILL BE FASTENED
 ON THE TRUSS LEDGER DETAIL.
  
 9.FBC 2309.6 SHOW SIZE AND LOCATION
 OF ATTIC ACCESS.
  
 10.FBC 3401.7.1.2.1 SHOW HOW SMOKE
 DETECTORS AND GFCI OUTLETS WILL COMPLY
 WITH THIS SECTION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 19:29 Sent To PC
Notes
2006-06-08 00:00:00PLANS FOR RE-STAMP,
  
 REDLINED RECEPT MISSING PER 210.52 WHICH
 WAS ON RECORD SET.
  
 REDLINED ALL RECEPTS IN EXISTING
 DWELLING IN LOCATIONS WHERE GFI
 PROTECTION IS REQUIRED PER 210.8A, SHALL
 BE BROUGHT UP TO GFI PROTECTION PER
 CHAPTER 34 FOR EXISTING DWELLINGS.
  
 ** PLEASE KNOW, BOTH OF THE ABOVE ITEMS
 ARE ON RECORD SET REV #2. PLANS
 SUBMITTED FOR RE-STAMPED ARE ONLY
 THROUGH REV #1.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 18:23 Rev Time 0.30
Received By dpalmer Date 2005-01-19 Time 18:23 Sent To M
Notes
2005-01-19 00:00:00** ELECTRICAL PLANS STAMPED**
 OK.
  
 ** PLEASE NOTE** PLANS ALSO INCLUDE
 TEMPORARY ELECTRICAL SERVICE FOR
 CONTRUCTION. TEMP POWER POLE DOES NOT
 NEED SEPARATE ELECTRICAL PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 06:40 Rev Time 0.50
Received By dpalmer Date 2004-12-23 Time 06:24 Sent To P
Notes
2004-12-23 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE MOST NOTES FROM ORIG REVIEW
 HAVE NOTE BEEN CORRECTED.
  
 1)NOTE: PLEASE SEE NOTES #'S:
 5,6,7,8,10,11,12.
 PLEASE SEE COPY OF THESE NOTES ARE
 ATTACHED.
  
 NEW NOTE DUE TO CHANGE IN PLANS.
  
 1)NOTE: PLEASE SEE RISER NOW SHOWS A
 NEW
 250A MCB, YET PANEL IS SHOWN AS 100A ON
 PANEL SCHEDULE?
  
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
 A 4X FEE WILL BE ACCESSED TO DESIGN
 PROFESSIONAL FOR PLAN REVIEW PORION OF
 PERMIT FEE IF ANY OF THESE COMMENTS ARE
 NOT ADDRESSED.
 THIS IS ACTUALLY THE THIRD REVIEW BY
 ELECTRICAL, HOWEVER CONTRACTOR?OB CLAIMS
 PLANS NEVER WENT OUT FOR CORRECTIONS.
 ONE COPY OF EACH ELECTRICAL PLAN IS NOW
 BEING RETAINED FOR POSSIBLE REVIEW BY
 THE FL BOARD OF ARCH'S, DBPR.
  
 PLEASE SEE A 10% RESUB WILL BE DUE IN
 NEXT RE-SUB.
  
 PLEASE SEE AS REQUESTED ON PREVIOUS
 REVIEWS, PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT ONLY NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. ONE SET OF OLD SHEETS TO
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 13:21 Rev Time 0.50
Received By dpalmer Date 2004-10-05 Time 13:21 Sent To M
Notes
2004-10-05 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:39 Rev Time 1.25
Received By dpalmer Date 2004-08-30 Time 14:26 Sent To P
Notes
2004-08-30 00:00:00********* UNSAT ******************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004
 PLEASE ALSO INCLUDE PRINTED NAME AND
 LICENSE # FOR ARCH OF RECORD IN TITLE
 BLOCK.
 THIS IS REQUIRED ON ALL SHEETS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 ** MISSING SD LEADING TO FLR ABOVE. **
  
 4)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
 PLEASE ALSO SHOW LOCATIONS FOR CU'S AND
 PLEASE SEE 440.11 FOR DISC MEANS.
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE ADJUST.
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP ON
 HEAT OF AHU'S.
  
 7)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING TO BE INSTALLED
 UNTIL AFTER THE FIRST MEANS OF DISC.
  
 8)NOTE: PLEASE SEE MISSING RECEPT ON 2'
 OF WALL IN MAST BR. 210.52
  
 9 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
  
 10)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDTIONS TO EXSITING DWELLINGS.
 PLEASE PROVIDE LAYOUT OF EXSIT. THIS IS
 TO BROUGHT UP TO CODE OR IF EXISTING
 MEETS 2002 NEC
 PLEASE ALSO SEE SD'S TO MEET NFPA-72
 PER PREVIOUS NOTE.
  
 12)NOTE: PLEASE SEE KVA SHOWN FOR A/C
 AHU'S DO NOT APPEAR TO CORRELATE TO
 LOAD CALCS?
  
 13)NOTE: PLEASE ALSO SEE BLDG REVIEW
 NOTES FOR VALUATION OF PERMIT.
 SHOWN AT 45K FOR 3240 SQ FT.
 VALUE TO BE ADJUSTED. PER FBC 104.6.5.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD PLANS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 10:41 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 10:41 Sent To E
Notes
2005-01-19 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 08:42 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 08:42 Sent To E
Notes
2004-12-20 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-24 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-09-24 Time 09:39 Sent To E
Notes
2004-09-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-20 Cont ID  
Sent By mmclean Date 2004-09-23 Time 12:09 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 14:26 Sent To Z
Notes
2004-09-20 00:00:00TO MM/SUBMITTAL/RETURN TO DEE TO PUT
 W/ORIG PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-08-26 Time 16:57 Rev Time 0.00
Received By csiegber Date 2004-08-26 Time 16:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-08-26 Time 12:47 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:11 Sent To  
Notes
2004-08-24 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-01-20 Cont ID  
Sent By prafter Date 2005-01-20 Time 13:00 Rev Time 2.00
Received By prafter Date 2005-01-20 Time 13:00 Sent To B
Notes
2005-01-20 00:00:00MECH. REV.
 A/C PLANS/ENERG. CAULK. AND EQUIPMENT
 INFORMATION SUPPLYED.
 PAT RAFTER 561/805/6725 OR805/6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-01-04 Cont ID  
Sent By hmoser Date 2005-01-04 Time 08:26 Rev Time 0.00
Received By hmoser Date 2005-01-04 Time   Sent To  
Notes
2005-01-04 00:00:00PLAN DENIED
 1) CAN NOT INSTALL OUTDOOR AIR ON ROOF
 SECTION 609.1.ABC.1#2 FLORIDA ENERGY
 CODE.
 2) REFER TO SECTION 601.4 FBC(M)BALANCED
 RERURN AIR SIZEING
 3) PLANS MUST BE STAMPED OR TITLE BLOCK
 CUT OFF.
 4) DO NOT NEED RETURN AIR IN BATHROOM OR
 CLOSET.
 5) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN FBC.(M)
 6) REFER TO SECTION 1107.2.1 REFRIGERANT
 PIPING
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-07 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 16:43 Rev Time 0.25
Received By pkrauss Date 2004-10-07 Time 16:30 Sent To B
Notes
2004-10-07 00:00:00DENIED:
 COMMENTS FROM 1ST REVIEW NOT ADDRESSED.
 SEE ATTACHED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-09-20 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 13:21 Rev Time 0.40
Received By pkrauss Date 2004-09-20 Time 13:19 Sent To B
Notes
2004-09-20 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 FOR THE ADDITIONAL PER 2001 FBC CHAPTER
 13 SUB-CHAPTER 6.
  
 2.PROVIDE EQUIPMENT SCHEDULE.
  
 3.PROVIDE A PLAN INDICATING DUCT AND
 GRILLE SIZE, LAYOUT AND MATERIAL.
  
 4.SEE ALSO COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By jleech Date 2004-12-29 Time 18:56 Rev Time 0.50
Received By jleech Date 2004-12-29 Time 18:56 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-08-30 Time 14:41 Rev Time 0.33
Received By jleech Date 2004-09-16 Time 18:51 Sent To M
Notes
2004-09-16 00:00:00NO RISER DIAGRAM UN-ABLE TO DO PLUMBING
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2004-09-23 Cont ID  
Sent By mmclean Date 2004-09-23 Time 12:09 Rev Time 0.00
Received By mmclean Date 2004-09-23 Time 12:09 Sent To B
Notes
2004-09-23 00:00:00PULLED & ATTACHED PLANS MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-26 Cont ID  
Sent By csiegber Date 2004-09-20 Time 14:26 Rev Time 0.00
Received By mmclean Date 2004-08-26 Time 12:47 Sent To I
Notes
2004-08-26 00:00:00DENIED, NEED TO PROVIDE 2 SETS OF PLANS.
 SITE PLAN MUST SHOW SETBACKS FOR FRONT
 SIDES & REAR TO SCALE.CALLED OWNER
 LEFT MSG ON VOICE MAIL. MM
 CUSTOMER PROVIDED 2ND COPY OF PLANS AND
 WILL PROVIDE SITEPLANS WITH SETBACKS. MM