Plan Review Details - Permit 04081018
Plan Review Stops For Permit 04081018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By jwitmer Date 2004-11-24 Time 13:41 Rev Time 0.77
Received By jwitmer Date 2004-11-24 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-02 Cont ID  
Sent By jwitmer Date 2004-11-02 Time 09:53 Rev Time 3.00
Received By jwitmer Date 2004-11-02 Time 09:52 Sent To  
Notes
2004-11-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04081018
 ADD: 477 S ROSEMARY AV# 302
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2NDREVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 ENTRY DOORS SHALL COMPLY WITH SECTION
 11-4.13.6MANUEVERING CLEARENCES AT
 DOORS
 SHEET A-1.0 DEMOLITION PLAN INDICATES
 THE ENTRY DOORS BEING CHANGED FROM
 INSWING TO OUT SWING DOORS.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) COMMENT# 5 FROM THE PREVIOUS REVIEW,
 SHEET A1-1 & A-3.1 PLATFORM: 403.2.4.1
 PLATFORMS ARE TO BE MADE OF FIRE
 RETARDANT MATERIALS. TYPE II BUILDING
 SECTION 604, FLOORS ARE TO BE OF A NON-
 COMBUSTIBLE MATERIALS.
  
 4) COMMENT# 7 FROM THE PREVIOUS REVIEW:
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO
 THE
 AUTHORITY HAVING JURISDICTION. SUCH
 IDEN
 TIFICATION SHALL BE ABOVE ANY
 DECORATIVE
 CEILING CEILING AND IN CONCEALED
 SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) COMMENT# 8 FROM THE PREVIOUS REVIEW:
 705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE
 WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT
 LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
  
 6) PLANS (E-3) INDICATE A NEW TOWER, BUT
  
 THERE IS NO INFORMATION FOR A TOWER.
 IF TO BE COVERED UNDER THIS PERMIT,
 PRO-
 VIDE INFORMATION, LOCATION, HEIGHT,
 WIND
 INFORMATION, ETC.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By jwitmer Date 2004-09-16 Time 07:38 Rev Time 0.75
Received By jwitmer Date 2004-09-16 Time 07:38 Sent To PC
Notes
2004-09-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04081018
 ADD:700 S ROSEMARY AV
 CONT: ANDERSON MOORE CONST
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, SHEET A-0 INDICATES WORK TO
 BE COMPLETED AT 700 S ROSEMARY, APPLICA-
 TION HAD 700 S ROSEMARY, SCRATCHED THRU
 AND 477 WAS ADDED. NOTE THE PCN IS STILL
 FOR 700 S ROSEMARY, CORRECT. ALSO ADD
 THE UNIT NUMBER WHERE WORK WILL BE COM-
 PLETED.
  
 3) CHECK PROJECT INFORMATION IF THIS PRO
 JECT IS LOCATED AT 477 S ROSEMARY.
 CLASSIFICATION, EXITS, ETC
  
 4) ENTRY DOORS SHALL COMPLY WITH SECTION
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. 18" MINIMUM PULL SIDE.
 IF EXISTING DOORS SHOW WHERE 20% OF
 WORK COMPLIES WITH DISPROPORTIONATE COST
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 5) SHEET A1-1 PLATFORM: 403.2.4.1. PLAT-
 FORMS SHALL BE MADE OF FIRE RETARDANT
 TREATED MATERIALS.
  
 6) SHEET A-3.1 TYPE II BUILDINGS REQUIRE
 BLOCKING IN WALLS TO BE NON-COMBUSTIBLE
 609.2.1.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 17:14 Rev Time 0.25
Received By dpalmer Date 2005-03-01 Time 17:14 Sent To  
Notes
2005-03-01 00:00:00GENERATOR MOVED FROM PLANS.
 GENERATOR IS UNDER SEPARATE PERMIT.
 TOWER IS STILL TO BE UNDER SEPARATE
 PERMIT.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-23 Time 19:11 Rev Time 0.50
Received By dpalmer Date 2004-11-23 Time 19:11 Sent To  
Notes
2004-11-23 00:00:00********* NOTES REDLINED *******
  
  
 1)NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS,
 TOWER FOR STATION TO BE UNDER SEPARATE
 PERMIT.
  
 2)NOTE: PLEASE SEE GENERATOR WILL ALSO
 BE UNDER SEPARATE PERMIT.
  
 3)NOTE: THE UPS SYSTEM WILL REQUIRE
 SPECS FOR ELECTRICAL EQUIPMENT ALSO
 UNDER SEPARATE PERMIT
  
 ****************************************
 ***************************************
 ALL THE ABOVE MUST SHOW AND INDICATE
 LISTING(S) BY A NRTL.
 ****************************************
 ***************************************
  
 THE ABOVE MUST BE SUBMITTED FOR PERMIT,
 ALONG WITH ANY PLANS AND SPECS.
 SEPARATE FEES FOR PERMITTING THE ABOVE
 WILL BE DUE AT TIME OF SUBMITTING FOR
 ABOVE PERMITS. ALL OF THE ABOVE
 ELECTRICAL MAY BE SUBMITTED UNDER ONE
 PERMIT.
  
 PLEASE BE SURE THIS IS SUBMITTED IN A
 TIMELY MANNER TO HELP AVOID ANY DELAYS
 IN PROJECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 06:52 Rev Time 0.75
Received By dpalmer Date 2004-10-27 Time 06:35 Sent To  
Notes
2004-10-27 00:00:00********* UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NO SPECS
 FOR GENERATOR, ATS, OR UPS WAS SUBMITTED
 BACK WITH PACKAGE.?
 PLEASE SUBMITMANUFACTURER SPECS FOR
 THE ABOVE ITEMS AT THIS TIME.
 IF THESE ITEMS ARE NOT SUBMITTED AT THIS
 TIME, ALL OF THESE ITEMS WILL BE REQUIR-
 -ED TO BE SUBMITTED UNDER SEPARATE
 PERMIT. ADDITIONAL FEES WILL BE ASSESSED
 AT THAT TIME.
  
 4)NOTE: NOTE #4 NO, PLEASE SHOW GROUND-
 -ING OF GENERATOR. ATS IS SHOWN AS A 3-
 -POLE UNIT, THIS WOULD NOT BE SEPARATE-
 -LYDERIVED SYSTEM.
 **PLEASE ALSO KEEP IN MIND, IF NEUTRAL
 IS NOT BROKEN, THEN ANY UNBALANCED LOAD
 MY FEED BACK TO FPL.***
 250.24,250.30,250.50
  
 5)NOTE: NOTE #5 NO, COULD NOT LOCATE
 ANY DEATIL FOR THIS.
 110.27 ETC.
  
 6)NOTE: NOTE #6 OK
  
 7)NOTE: NOTE #7 OK.
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B). THIS IS ONLY A NOTICE AT THIS TIME
 AND MUST BE GIVEN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETET SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 *** PLEASE SEE SOME PLANS STILL SHOW
 ADDRESS OF 700 S. ROSEMARY. ***
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-26 Cont ID  
Sent By dpalmer Date 2004-08-26 Time 16:36 Rev Time 1.50
Received By dpalmer Date 2004-08-26 Time 15:36 Sent To  
Notes
2004-08-26 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS HAVE ADDRESS OF
 700 S ROSEMARY ALONG WITH PERMIT APPLI-
 -CATION.
 PLEASE SEE WORK APPEARS TO BE AT 477.
 PLEASE ALSO INCLUDE UNIT # TO BE.
  
 2)NOTE: PLEASE SEE 230.72, 230.76,230.79
 FOR MEANS OF DISC FROM GEN INTO SPACE.
 DISC MEANS MUST BE PLACED AT LOCATION OF
 NEW 400A MAIN FOR SPACE.
  
 3)NOTE: PLEASE SUBMIT SPECS FOR GEN/ATS
 UPS.
 PLEASE NOTE: EVEN IF ALL THIS EQUIPMENT
 IS OWNER SUPPLIED VALUE OF THESE ITEMS
 MUST BE INCLUDED IN VALUATION OF PERMIT.
 104.6.5 FBC.
  
 4)NOTE: PLEASE CLARIFY GROUNDING OF
 GENERATOR.IF SEP DERIVE OR NOT?
  
 5)NOTE: PLEASE PROVIDE INFORMATION ON
 HOW GENERATOR WILL BE FENCED/WALL OFF
 ETC.110.27
  
 5)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 6)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 7)NOTE: PLEASE SIGN PLANS WITH SIGNATURE
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 16:08 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 16:08 Sent To  
Notes
2004-11-05 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW 70KW NATURAL GAS EMERGENCY
 GENERATOR.
  
 2) ENSURE ALL FIRE DOORS ARE RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-01 Cont ID  
Sent By nmccray Date 2004-09-01 Time 12:47 Rev Time 0.00
Received By nmccray Date 2004-09-01 Time 12:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 16:45 Sent To E
Notes
2005-02-22 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 16:26 Sent To M
Notes
2005-02-22 00:00:00TO PKRAUSS BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-02-17 Time 10:41 Rev Time 0.00
Received By adarroug Date 2005-02-17 Time 10:41 Sent To M
Notes
2005-02-17 00:00:00TO PKRAUSS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 08:03 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 08:03 Sent To M
Notes
2005-01-07 00:00:00TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 07:22 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 12:57 Sent To  
Notes
2004-11-23 00:00:00SENT TO CDOMM BD#14/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 15:35 Sent To  
Notes
2004-10-18 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 16:19 Sent To  
Notes
2004-08-20 00:00:00TO COMM BD#17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-30 Cont ID  
Sent By pkrauss Date 2005-03-30 Time 12:11 Rev Time 0.25
Received By pkrauss Date 2005-03-30 Time 12:11 Sent To  
Notes
2005-03-30 00:00:00SUBMITTAL LETTER ADDRESSED TO MR BOWMEN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-24 Cont ID  
Sent By prafter Date 2005-02-24 Time 12:13 Rev Time 0.50
Received By prafter Date 2005-02-24 Time 12:13 Sent To  
Notes
2005-02-24 00:00:00MECH. REVISION 2/16/05 THREE M SHEETS
  
 PAT RAFTER 561/805/6728.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By pkrauss Date 2004-09-15 Time 08:58 Rev Time 1.15
Received By pkrauss Date 2004-09-15 Time 07:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By kstevens Date 2004-11-24 Time 13:27 Rev Time 0.50
Received By kstevens Date 2004-11-24 Time 13:27 Sent To  
Notes
2004-11-24 00:00:00PASSED/PROVISO
  
 30X48 CLEAR FLOOR SPACE - FRONTAL
 APPROACH REQUIRED AT SINK
  
 6-1/2" MAX DEPTH AT SINK

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 18:08 Rev Time 0.60
Received By kstevens Date 2004-11-05 Time 18:08 Sent To  
Notes
2004-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW:
 2) THE EXISTING BATHROOM & KITCHEN SINK
 SHALL COMPLY WITH SECTION 11-4.23, AND
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT DETAILS FOR THESE REQUIREMENTS.
 THE BATHROOM SHALL BE ACCESSIBLE NOT
 ADAPTABLE. SHOW HEIGHT OF W/C
 11-4.16.3,
 GRAB BARS 11-4.16.4, FLUSH CONTROLS
 11-4.16.5, LAV HEIGHT AND CLEARANCES
 11-4.19.2, EXPOSED PIPES AND SURFACES
 11-4.19.4, SEAT 11-4.20.3, GRAB BARS
 11-4.20.4, CONTROLS 11-4.20.5, SHOWER
 UNIT 11-4.20.6. SEE FIGS. 33 & 34. THE
 KITCHEN SINK SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. SUBMIT A DETAIL
 SHOWING HEIGHT 11-4.24.2, KNEE CLEARANCE
 11-4.24.3, SINK DEPTH 11-4.24.4, A CLEAR
 FLOOR SPACE AT LEAST 30"X48" COMPLYING
 WITH 11-4.2.4 SHALL BE PROVIDED IN FRONT
 OF A SINK TO ALLOW FORWARD APPROACH.
 EXPOSED PIPES AND SURFACES 11-4.24.6
 B) SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) AND THE DESIGN
 PROFESSIONAL
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-01 Cont ID  
Sent By kstevens Date 2004-09-01 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2004-11-24 Time 14:17 Sent To  
Notes
2004-09-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ADDRESS APPEARS TO BE INCORRECT. THE
 BLDG ADDRESS FOR THE APPLICATION AND ON
 THE PLANS SHALL BE VERIFIED. SECTION
 104.1.5.
 2) THE EXISTING BATHROOM & KITCHEN SINK
 SHALL COMPLY WITH SECTION 11-4.22 AND
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT DETAILS FOR THESE REQUIREMENTS.
 3) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1
 4) SECTION 704.5 - IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 5) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025
 INITIALS ARE NOT ACCEPTABLE.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By jwitmer Date 2004-11-24 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2004-11-24 Time 14:17 Sent To PC
Notes
2004-11-24 00:00:0011-24-04 OK'ED BY S GRAHAM , TOWER TO BE
 UNDER SEPERATE PERMIT

Review Stop Z ZONING
Rev No 2 Status F Date 2004-10-25 Cont ID  
Sent By mmclean Date 2004-10-25 Time 14:22 Rev Time 0.00
Received By mmclean Date 2004-10-25 Time 14:22 Sent To  
Notes
2004-10-25 00:00:00DENIED, NEED TO DO A MINOR AMENDMENT FOR
 GENERATOR & ANTENNAS.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-27 Cont ID  
Sent By mmclean Date 2004-08-27 Time 11:19 Rev Time 0.00
Received By mmclean Date 2004-08-27 Time 11:19 Sent To  
Notes
2004-08-27 00:00:00DENIED, NEED MINOR AMENDMENT FOR
 GENERATORS AND ANTENNAS.CALLED ERIC
 SCHNEIDER, 822-1446.


Account Summary | Usage Policy | Privacy Policy