Plan Review Details - Permit 04080997
Plan Review Stops For Permit 04080997
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-06 Cont ID  
Sent By shill Date 2004-10-06 Time 10:17 Rev Time 1.00
Received By shill Date 2004-10-06 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-19 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 08:35 Rev Time 0.50
Received By dpalmer Date 2004-10-18 Time 16:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-27 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:01 Rev Time 0.50
Received By dpalmer Date 2004-08-27 Time 15:33 Sent To  
Notes
2004-08-27 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE RISER. WIREWAY DOES
 NOT SEEM TO BE FED FROM BUS-DUCT/DISC??
 PLEASE VERIFY.
 215.5
  
 2)NOTE: PLEASE PROVIDE LODA ON EXISTING
 300A BUS-DUCT DISC.
 215.5,220
  
 3)NOTE: PLEASE PROVIDE NOTE OR SHOW
 GROUNDING OF NEW TRANSFORMER. 250.30
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-20 Cont ID  
Sent By nmccray Date 2004-09-20 Time 15:58 Rev Time 0.00
Received By nmccray Date 2004-09-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 11:01 Sent To E
Notes
2004-10-13 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-06 Cont ID  
Sent By pkrauss Date 2004-10-06 Time 17:32 Rev Time 0.00
Received By pkrauss Date 2004-08-20 Time 14:40 Sent To  
Notes
2004-08-20 00:00:00TO COMM BD#15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-06 Cont ID  
Sent By pkrauss Date 2004-10-06 Time 17:29 Rev Time 0.40
Received By pkrauss Date 2004-10-06 Time 17:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-09-17 Cont ID  
Sent By kstevens Date 2004-09-17 Time 16:53 Rev Time 0.25
Received By kstevens Date 2004-09-17 Time 16:53 Sent To  
Notes
2004-09-17 00:00:00NO PLUMBING WORK SHOWN.