| 2004-11-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING |
| | POOLS |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, |
| | OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW. |
| | 1) FBC-2001424.2.6.6.2 SHOW |
| | COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE |
| | MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO |
| | NOTES) |
| | 2) INDICATE MAXIMUM LENGTH TO VENT LINE |
| | CONNECTION. |
| | 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL)-THE PIPING SCHEMATIC SHOWS NO |
| | MINIMUM MEASURMENT. PLEASE INDICATE THE |
| | MINIMUM MEASURMENT ON PLANS. SECTION |
| | 104.2.1. |
| | 4) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 5) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 6) FBC02001 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE |
| | PLANS |
| | AND PERMIT REQUIRED. |
| | 7) VACUUM LINE NOT SHOWN ON POOL LAYOUT |
| | SHEET. THIS IS SHOWN ON THE PIPING |
| | DIAGRAM. PLEASE CLARIFY AND CORRELATE |
| | PLANS. SECTION 104.2.1 |
| | 8) NOTE STATES HEATER IS EXCEMPT FROM |
| | STATE ENERGY CODE. GAS HEATERS ARE NOT |
| | 90% EFFECIENT. DELETE NOTE. SECTION |
| | 104.2.1 |
| | 9) PIPING SCHEMATIC SHOWS A 109K HEAT |
| | PUMP, BUT POOL EQUIPMENT INDICATES A |
| | 400K NATURAL GAS POOL HEATER. PLEASE |
| | CLARIFY, AND CORRELATE PLANS. SECTION |
| | 104.2.1 |
| | 10) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |