Plan Review Details - Permit 04080907
Plan Review Stops For Permit 04080907
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-21 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:17 Rev Time 0.50
Received By lsmith Date 2004-10-21 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-12 Cont ID  
Sent By pkrauss Date 2004-10-20 Time 06:42 Rev Time 1.00
Received By lsmith Date 2004-10-12 Time 10:45 Sent To  
Notes
2004-10-12 00:00:00BUILDING PLAN REVIIEW
  
 1. THE PLANS MUST BE TAKEN TO PBC FOR IM
 PACT FEES. THEY WILL STAMP THE PLANS AND
 ISSUE A RECEIPT. THIS MUST BE SUBMITTED
 BEFORE A PERMIT CAN BE PRINTED.
  
 2. THERE ARE ADDITIONAL FEES DUE.
  
 ANY QUESTIONS PLEASE CALL
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-21 Cont ID  
Sent By jleech Date 2004-09-15 Time 17:56 Rev Time 3.00
Received By lsmith Date 2004-09-21 Time 08:49 Sent To  
Notes
2004-09-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. PLANS MUST BE TAKEN TO PBC AND IMPACT
 FEES PAID.THE PLANS MUST BE STAMPED
 BY THEM, A COPY OF THE PAID RECEIPT
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 3. NEED FLORIDA PRODUCT APPROVALS FOR
 THE STRUCTURAL COMPONENTS (TRUSS
 STRAPS, ETC.)
  
 4. THE SQ. FT. ON APPLICATION HAS BEEN
 CORRECTED.ADDITIONAL FEES ARE DUE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-05-24 Cont ID  
Sent By btrobaug Date 2006-05-24 Time 17:45 Rev Time 0.50
Received By btrobaug Date 2006-05-24 Time 17:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2006-04-25 Time 16:19 Sent To PC
Notes
2006-04-26 00:00:00PLANS REVISED AFTER ROUGH ELECTRICAL
 INSOECTIONS.
 INFORMATION SENT TO CHIEF ELECTRICAL
 INSPECTOR.
2006-04-25 00:00:00ON HOLD AS REVISIONS ARE BEING
 SUBMITTED AFTER ROUGH ELECTRICAL
 INSPECTIONS HAVE BEEN DONE.
 SEE JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 07:05 Sent To PC
Notes
2006-04-03 00:00:00*************UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS.
 PLEASE SEE RISER SHOWS PANELS AS 200A
 MCB AND PANELS ARE SHOWN AS 150A?
  
 2) NOTE: PLEASE SEE RISER SHOWS PANEL
 "A" FEEDING A POOL "DISCONNECT", HOWEVER
 PLANS SEEM TOIN DICATE A POOL
 "PANEL".?
 PLEASE ALSO SEE THAT PANEL "A" DOES NOT
 INDICATE A FEED TO EITHER A POOL
 DISCONNECT OR POOL PANEL.
 PLEASE CORRELATE AND AADJUST PLANS AND
 RISER.
 PLEASE SEE PLANS DO NOT INDICAT EITHER A
 POOL PANEL OR A POOL DISCONNECT AT THE
 LOCATION OF POOL EEQUIPMENT?
 ** PLEASEBE SURE TO UPDATE LOAD
 CALCULATIONS.
 ** PLEASE ADJUST CONTINUOUS LOADS AT
 125%. (POOL PUMP). 215.3,230.42
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 21:05 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 20:49 Sent To PC
Notes
2006-02-09 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE PLANS INDICATE AND
 SHOW TWO COMPLETELT DIFFERENT RISER
 DIAGRAMS.
 IT IS UNCLEAR WHICH ONE IS FOR REVIEW.
 IF THE RISER IS THE HANDRAWN ONE, PLEASE
 CORRELATE WITH PLANS/ PANELS ETC.
 IF HANDRAWN, WRONG SIZE GEC, FOR 400A
 SERVICE BASED ON 250.66,310.15B6
 1/0 MIN.
  
 2)NOTE: PLEASE SEE MANY REQUIRED 20A
 CIRCUITS ON PANEL "A" WHICH ARE SHOWN AS
 15A FOR SMALL APPL, DINING RM ETC.
 210.11C1,210.52B1 ETC
  
 3)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 4)NOTE: PLEASE SEE NO HANDWRITTEN
 CHANGES OR WHITE-OUT PERMITTED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-14 Cont ID  
Sent By btrobaug Date 2005-12-14 Time 15:40 Rev Time 0.50
Received By btrobaug Date 2005-12-02 Time 09:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 06:20 Rev Time 0.25
Received By dpalmer Date 2004-10-05 Time 06:15 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-09-24 Time 10:19 Rev Time 0.50
Received By dpalmer Date 2004-08-25 Time 14:23 Sent To M
Notes
2004-08-25 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PANELS.
 RISER SHOWS 150A PANELS AND PANELS
 INDICATE 200A PANELS?
 PLEASE ALSO SEE PANELS INDICATE A 149.16
 A LOAD AFTER DERATING??
  
 2)NOTE: PLEASE SEE POOL PANEL LOAD
 SHOWN AS 10KW ON PANEL 'A'. PLEASE
 CORRELATE W/ POOL PANEL.
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-24 Cont ID  
Sent By ssherman Date 2006-05-24 Time 08:18 Rev Time 0.00
Received By ssherman Date 2006-05-24 Time 08:17 Sent To  
Notes
2006-05-24 00:00:00ELEC REVISION GIVEN TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 11:39 Sent To E
Notes
2006-04-24 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 15:07 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 15:07 Sent To E
Notes
2006-03-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 09:04 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 09:04 Sent To E
Notes
2006-02-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 16:17 Sent To B
Notes
2004-10-25 00:00:00TO LS DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-24 Cont ID  
Sent By csiegber Date 2004-09-24 Time 10:19 Rev Time 0.00
Received By csiegber Date 2004-09-24 Time 10:19 Sent To E
Notes
2004-09-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-21 Cont ID  
Sent By mmclean Date 2004-08-24 Time 12:38 Rev Time 0.00
Received By lsmith Date 2004-08-20 Time 10:01 Sent To  
Notes
2004-08-25 00:00:00TO SFD RACK/E
2004-08-20 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-20 Cont ID  
Sent By pkrauss Date 2004-10-20 Time 06:41 Rev Time 0.25
Received By pkrauss Date 2004-10-20 Time 06:27 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 06:39 Rev Time 0.15
Received By pkrauss Date 2004-10-08 Time 06:28 Sent To  
Notes
2004-10-08 00:00:00DENIED:
 COMMENTS FROM THE 1ST REVIEW WAS NOT
 ADDRESSED. SEE ATTACHED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-28 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 06:20 Rev Time 0.25
Received By pkrauss Date 2004-08-28 Time 07:57 Sent To P
Notes
2004-08-28 00:00:00DENIED:
 THE MANUAL J CALCULATIONS AND THE
 EQUIPMENT SCHEDULE ON PLAN SHEET M-1
 DO NOT MATCH THE ENERGY CALCULATIONS.
 THE ENERGY CALCULATIONS SHOW 12.6 SEER
 WHEREAS SYSTEM #2 ON THE MANUAL J & THE
 EQUIPMENT SCHEDULE SHOW ONLY 12 SEER.
 EQUIPMENT SHALL NOT BE LESS EFFICIENT
 THAN WHAT THE ENERGY CALCULATIONS
 DICTATE, PLEASE REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 08:01 Rev Time 0.33
Received By jleech Date 2004-09-15 Time 17:56 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-08-24 Time 12:38 Rev Time 0.00
Received By mmclean Date 2004-08-24 Time 12:38 Sent To I
Notes
***NONE***