Plan Review Details - Permit 04080905
Plan Review Stops For Permit 04080905
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-17 Cont ID  
Sent By lsmith Date 2004-09-17 Time 15:32 Rev Time 1.00
Received By lsmith Date 2004-09-17 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:12 Rev Time 2.00
Received By lsmith Date 2004-08-30 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-08-29 Cont ID  
Sent By dpalmer Date 2005-08-29 Time 20:16 Rev Time 0.40
Received By dpalmer Date 2005-08-29 Time 20:16 Sent To  
Notes
2005-08-29 00:00:00REDLINED , NO EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO MAINS/FIRST
 MEANS OF DISCONNECT.
 250.6.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-08-24 Cont ID  
Sent By dpalmer Date 2005-08-24 Time 07:07 Rev Time 0.50
Received By dpalmer Date 2005-08-23 Time 21:57 Sent To  
Notes
2005-08-24 00:00:00******* UNSAT ********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND NEW COMMENTS DUE TO CHANGES
 IN PLANS.
  
  
  
 1)NOTE: PLEASE SEE THE CONDUCTORS FROM
 METER TO MAIN BRKR PANELS HAVE BEEN TO
 CORRECTED, HOWEVER PLEASE SEE "EQUIPMENT
 GROUNDING" CONDUCTOR ARE NOW SHOWN FROM
 METER TO MAIN/FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, AN 'EQUIP GROUNDING
 CONDUCTOR IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE SEE FEEDERS FOR POOL SUB
 PANEL ARE NOT SHOWN ON RISER DIAGRAM.
 PLEASE ALSO SEE PANEL DOES NOT INDICATE
 ANY LOAD FOR POOL PANEL??
 PLEASE SEE THIS IS SHOWN AS "POOL DISC".
 PLEASE SEE POOL PANEL IS NOT SHOWN ON
 PLANS.
 215.5, 310.16,240.4 ETC
  
 3)NOTE: PLEASE SEE 250.66,310.15B6, THE
 MIN GROUNDING ELECTRODE CONDUCTOR SIZE
 IS 1/0, PLEASE SEE #2 SHOWN NEEDS TO BE
 CORRECTED.
 PLEASE SEE PREVIOUS PLANS AND ORIGINAL
 PLANS INDICATED A 300A SERVICE. PLEASE
 SEE SERVICE IS NOW BEING SHOWN AS
 400A'S. THIS WAS NOT CORRECTED.
  
 3)NOTE: PLEASE SEE PLANS DO NOT EITHER
 SHOW POOL HEATER AS INDICATED ON POOL
 PANEL OR 2ND CU AS INDICATED ON PANEL
 "A".
 PLEASE SEE PLANS, POOL EQUIPMENT IS
 SHOWN? OR IS THIS THE CU?
 PLEASE SEE MISSING DISC FOR A/C CU.
 440.11PLEASE CORRELATE.
  
 4)NOTE: PLEASE SEE A SPA TUB IS SHOWN ON
 PANEL SCHEDULE, HOWEVER THIS REQUIRED
 GFI PROTECTED OUTLET COULD NOT BE
 LOCATED ON PLANS.
  
 5)NOTE: PLEASE SEE THIS IS A REVISION
 AND A REV FEE IS OWED. PLEASE SEE
 PREVIOUS REVISION FEE IS SHOWN AS NOT
 PAID.PLEASE SEE THAT ALL REV'S ARE
 PAID WHEN SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2005-08-23 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-17 Cont ID  
Sent By dpalmer Date 2005-08-17 Time 07:46 Rev Time 0.75
Received By dpalmer Date 2005-08-17 Time 07:46 Sent To  
Notes
2005-08-17 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE 310.15B6 FOR MIN
 CONDUCTORS FOR 200A PANELS.
  
 2)NOTE: PLEASE SEE 250.66,310.15B6, THE
 MIN GROUNDING ELECTRODE CONDUCTOR SIZE
 IS 1/0, PLEASE SEE #2 SHOWN NEEDS TO BE
 CORRECTED.
 PLEASE SEE PREVIOUS PLANS AND ORIGINAL
 PLANS INDICATED A 300A SERVICE. PLEASE
 SEE SERVICE IS NOW BEING SHOWN AS
 400A'S.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE 4-A/C SYSTEMS SHOWN IN LOAD
 CALCULATIONS, HOWEVER THIS DOES NOT
 CORRELATE WITH PLANS..
 215.5, 220
  
 4)NOTE: PLEASE SEE LOADS FOR EACH PANEL
 IS SHOWN AS BLANK,
 PLEASE SEE LOADS ARE SHOWN AS THE SAME
 ON EACH PANEL SCHEDULE AND LOAD
 CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-01 Cont ID  
Sent By dpalmer Date 2004-09-01 Time 14:15 Rev Time 0.33
Received By dpalmer Date 2004-09-01 Time 14:15 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-09-01 Time 09:07 Rev Time 0.33
Received By dpalmer Date 2004-08-24 Time 13:18 Sent To M
Notes
2004-08-24 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CORRELATEPANELS/MCB
 FROM RISER AND PANELS .
 RISER SHOWS PANELS AS 150A'S AND PANELS
 INDICATE 200A?
 PLEASE ALSO SEE LOAD ON PANEL "A" IS
 ALREADY SHOWN AT 149.16A'S WITH ALL
 DERATING TAKEN.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM MAINS TO PANELS.
 250.24,250.110,250.122
  
 3)NOTE: PLEASE SEE POOL PANEL IS SHOWN
 AS HAVING 10KW LOAD ON PANEL "A" YET
 POOL PANEL LOAD DOES NOT SHOW THIS?
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 RECEPTS ARE THE AFCI PROTECTED ITEMS
 SHOWN ON PANELS AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 08:41 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 08:41 Sent To E
Notes
2005-08-22 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 15:44 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 15:43 Sent To E
Notes
2005-08-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:12 Rev Time 0.00
Received By csiegber Date 2004-09-17 Time 09:12 Sent To B
Notes
2004-09-17 00:00:00TO LS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-01 Time 09:07 Rev Time 0.00
Received By csiegber Date 2004-09-01 Time 09:07 Sent To E
Notes
2004-09-01 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-08-24 Time 10:14 Rev Time 0.00
Received By lsmith Date 2004-08-20 Time 10:02 Sent To  
Notes
2004-08-24 00:00:00TO SFD RACK/E
2004-08-20 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-29 Cont ID  
Sent By pkrauss Date 2005-07-29 Time 14:44 Rev Time 0.20
Received By pkrauss Date 2005-07-29 Time 14:44 Sent To  
Notes
2005-07-29 00:00:00SUBMITTAL CHANGE EQUIPMENT MANUFACTURER
 - SAME SEER & TONNAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By pkrauss Date 2004-09-16 Time 08:30 Rev Time 0.30
Received By pkrauss Date 2004-09-16 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-28 Cont ID  
Sent By dpalmer Date 2004-09-01 Time 14:15 Rev Time 0.20
Received By pkrauss Date 2004-08-28 Time 06:39 Sent To P
Notes
2004-08-28 00:00:00DENIED:
 THE MANUAL J CALCULATIONS AND THE
 EQUIPMENT SCHEDULE ON PLAN SHEET M-1
 DO NOT MATCH THE ENERGY CALCULATIONS.
 THE ENGERY CALCULATIONS SHOW 12.6 SEER
 WHEREAS SYSTEM #2 ON THE MANUAL J & THE
 EQUIPMENT SCHEDULE SHOW ONLY A 12 SEER.
 PLEASE CORRELATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 06:41 Rev Time 0.33
Received By jleech Date 2004-08-28 Time 11:06 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-08-24 Time 10:14 Rev Time 0.00
Received By mmclean Date 2004-08-24 Time 10:14 Sent To I
Notes
***NONE***