Plan Review Details - Permit 04080838
Plan Review Stops For Permit 04080838
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-17 Cont ID  
Sent By lsmith Date 2004-09-17 Time 14:44 Rev Time 1.00
Received By lsmith Date 2004-09-17 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-30 Cont ID  
Sent By jleech Date 2004-08-28 Time 10:38 Rev Time 2.00
Received By lsmith Date 2004-08-30 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-04-04 Cont ID  
Sent By dpalmer Date 2005-04-04 Time 08:37 Rev Time 0.30
Received By dpalmer Date 2005-04-04 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-03-31 Cont ID  
Sent By dpalmer Date 2005-03-31 Time 10:56 Rev Time 0.50
Received By dpalmer Date 2005-03-31 Time 10:52 Sent To  
Notes
2005-03-31 00:00:00*** UNSAT 2ND REVIEW ***
  
 PLEASE SEE SOME ITEMS FROM PREVOUS
 REVIEW STILL NEED CORRECTING.
  
 1)NOTE: PLEASE SEE BATH CIRCUIT IS STILL
 SHOWN AS 20A (REQ'D) ON #14 AWG WHICH IS
 ONLY RATED FOR 15A'S.
 210.52D,210.11C3
  
  
 2)NOTE: PLEASE SEE ONLY 1-#12 CONDUCTOR
 IS SHOWN FEEDING SPRINKLER TIME CLOCK.
 PLEASE VERIFY THIS? (MISPRINT).
 THERE SOULD BE MORE THAN ONE CONDUCTOR
 FEEDING TIME CLOCK.
  
 3)NOTE: PLEASE SEE FOUNDATION STEEL HAS
 NOW BEEN REMOVED FROM RISER DIAGRAM FOR
 REQUIRED FOOTER STEEL CONNECTION.
 PLEASE SEE UNDER 250.50 FOR NEW
 CONSTRUCTION FOOTER/FOUNDATION STEEL IS
 REQUIRED.
 THIS IS THE RESONSIBLITY OF THE
 ELECTRICAL CONTRACTOR TO INSTALL AS IT
 WAS DETAILED ON THE ORIGINAL PLANS AS
 SET-FORTH BY THE ENGINEER OF RECORD AND
 IS REQUIRED UNDER NEC.
 THIS SHALL BE SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-14 Cont ID  
Sent By dpalmer Date 2005-03-14 Time 18:13 Rev Time 0.40
Received By dpalmer Date 2005-03-14 Time 18:13 Sent To  
Notes
2005-03-14 00:00:00*** UNSAT ***
  
 **PLEASE SEE THERE HAVE BEEN NUMEROUS
 CHANGES TO ORIGINAL ELECTRICAL PLANS
 WHICH HAVE NOW GENERATED NEW COMMENTS.**
  
 1)NOTE: PLEASE SEE BATH CIRCUIT IS NOW
 SHOWN AS 20A (REQ'D) ON #14 AWG WHICH IS
 ONLY RATED FOR 15A'S.
 210.52D,210.11C3
  
 2)NOTE: PLEASE SEE DINING RM RECEPTS ARE
 NOW SHOWN ON A 15A #14 AWG CIRCUIT.
 PLEASE SEE 210.52B1. DINING RM ETC REQ'D
 TO BE 20, #12.
 IN THE KITCHEN, PANTRY, BREAKFAST ROOM,
 DINING ROOM, OR SIMILAR AREA OF A
 DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED
 BY 210.11(C)(1) SHALL SERVE ALL
 RECEPTACLE OUTLETS COVERED BY 210.52(A)
 AND (C) AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT.
  
 3)NOTE: PLEASE SEE DISCONNETCS FOR A/C
 COND UNITS ARE NOW SHOWN DIRECTLY BEHIND
 CU'S.
 ORIG PLAN, DISC'S SHOWN TO MEET 110.26.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR TO POOL SUB PANEL
 FROM METER/MAIN COMBO.
 250.110,250.122 ETC.
  
 5)NOTE: PLEASE SEE ONLY 1-#12 CONDUCTOR
 IS SHOWN FEEDING SPRINKLER TIME CLOCK.
 PLEASE VERIFY THIS? (MISPRINT).
  
 6)NOTE: PLEASE SEE ORIGINAL PLANS
 INDICATED 17-RECESSED LTS ON PANEL
 SCHEDULE AND 17-RECESSED FIXTURES WERE
 SHOWN ON PLANS. PLEASE SEE PANEL
 SCHEDULE NOW INDCIATES 28-RECESSED
 FIXTURES, HOWEVER PLANS STILL ONLY
 INDICATE 17-FIXTURES??
 PLEASE CORRELATE # OF FIX'S ON PANEL
 SCHEDULE WITH PLANS.
 215.5
  
 ** NOTE**
 PLEASE SEE PLANS INDICATE WASHER AND
 DRYER AS "OPTIONAL". PLEASE SEE PLANS
 ARE REQUIRED TO HAVE ALL REVISIONS AND
 OPTIONS SUBMITTED FOR REVIEW BEFORE
 ROUGH ELECTRICAL INSPECTION.
 PLEASE ALSO NEC REQUIRES A MIN LAUNDRY
 CIRCUIT.1.5VA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-17 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 14:25 Rev Time 0.25
Received By dpalmer Date 2004-09-17 Time 14:25 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-09-15 Time 09:58 Rev Time 0.50
Received By dpalmer Date 2004-08-23 Time 13:36 Sent To M
Notes
2004-08-23 00:00:00***************UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 3)NOTE: PLEASE MOVE SD INTO MASTER BEDRM
 FROM HALL. NFPA-72 8-1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 13:37 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 13:37 Sent To E
Notes
2005-04-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 10:32 Sent To E
Notes
2005-03-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 11:47 Sent To E
Notes
2005-03-14 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 14:25 Sent To M
Notes
2005-01-11 00:00:00TO "M/AC" BOX./REVISION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 09:58 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 09:58 Sent To E
Notes
2004-09-15 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-08-19 Time 13:34 Rev Time 0.00
Received By lsmith Date 2004-08-30 Time 10:18 Sent To  
Notes
2004-08-20 00:00:00TO SFD RACK/E
2004-08-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-11 Cont ID  
Sent By pkrauss Date 2005-01-11 Time 15:39 Rev Time 0.35
Received By pkrauss Date 2005-01-11 Time 15:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-25 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 14:26 Rev Time 0.35
Received By pkrauss Date 2004-08-25 Time 07:31 Sent To P
Notes
2004-08-25 00:00:00PROVISO:
 SUPPLY AIR FROM THE BATH #2 AND BEDROOM
 #2 ARE NOT SIZED ON PLAN. PLEASE PROVIDE
 REVISED PLAN OR LETTER ON COMPANY LETTER
 HEAD INDICATING THE DUCT SIZE.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-25 Time 07:51 Rev Time 0.33
Received By jleech Date 2004-08-28 Time 10:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-19 Cont ID  
Sent By mmclean Date 2004-08-19 Time 13:33 Rev Time 0.00
Received By mmclean Date 2004-08-19 Time 13:33 Sent To I
Notes
***NONE***