Plan Review Details - Permit 04080784
Plan Review Stops For Permit 04080784
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-30 Cont ID  
Sent By jwitmer Date 2004-11-30 Time 14:52 Rev Time 0.55
Received By jwitmer Date 2004-11-30 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-24 Cont ID  
Sent By jwitmer Date 2004-08-24 Time 16:44 Rev Time 1.11
Received By jwitmer Date 2004-08-24 Time 16:36 Sent To  
Notes
2004-08-24 00:00:00 
 BUILDING PROVISO:
 FRENCH DOORS, 1012.1.8. A LATCH OR OTHER
 FASTENING DEVISE ON A DOOR SHALL BE PRO-
 VIDED WITH A RELEASING DEVISE HAVING AN
 OBVIOUS METHOD OF OPERATION UNDER ALL
 LIGHTING CONDITIONS. THE RELEASING MECH-
 ANISM FOR ANY LATCH SHALL BE LOCATED AT
 LEAST 34" AND NOT MORE THAN 48" ABOVE
 THE FINISH FLOOR. DOORS SHALL BE OPEN-
 ABLE WITH NOT MORE THAN ONE RELEASING
 OPERATION (THIS INCLUDES FLUSH BOLTS).
  
 1012.1.6 DOOR HANLES, PULLS, LATCHES,
 LOCKS AND OTHER OPERATING DEVICES SHALL
 BE OPERABLE WITH ONE HAND & SHALL NOT
 REQUIRE GRASPING, PINCHING, OR TWISTING
 OF THE WRIST TO OPERATE. THE FORCE RE-
 QUIRED TO OPERATE THE CONTROLS SHALL BE
 NO GREATER THAN 5 LBS.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 15:28 Rev Time 0.20
Received By dpalmer Date 2004-11-12 Time 15:26 Sent To  
Notes
2004-11-12 00:00:00NO ELECTRICAL UNDER THIS PLAN REVIEW
 UNDER SEPARATE PERMIT.
 04100667

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-30 Cont ID  
Sent By dpalmer Date 2004-08-30 Time 07:43 Rev Time 0.25
Received By dpalmer Date 2004-08-30 Time 07:42 Sent To  
Notes
2004-08-30 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK PER 61G1-16.-
 -.004 AS REQUIRED UNDER FS 481.219
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 2)NOTE: PLEASE SEE ALL RECEPTS W/ THE
 EXCEPTION OF ONE ARE ALL SHOWN ON THE
 SAME CIRCUIT?
 PLEASE CLARIFY
 PLEASE ALSO SEE NEC 220.13 FOR 180 VA
 PER RECEPT AND SEE MAX LOADING OF A
 15A OR 20A CIRCUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-20 Cont ID  
Sent By nmccray Date 2004-09-20 Time 11:43 Rev Time 0.00
Received By nmccray Date 2004-09-20 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-02 Cont ID  
Sent By csiegber Date 2004-11-02 Time 10:34 Rev Time 0.00
Received By csiegber Date 2004-11-02 Time 10:34 Sent To  
Notes
2004-11-02 00:00:00TO COMM BD#58

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-21 Cont ID  
Sent By mjacobs Date 2004-09-21 Time 07:55 Rev Time 0.00
Received By mjacobs Date 2004-08-18 Time 14:47 Sent To  
Notes
2004-08-18 00:00:00TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 17:07 Rev Time 0.45
Received By pkrauss Date 2004-11-30 Time 16:46 Sent To  
Notes
2004-11-30 00:00:00BUILDING AND MECHANICAL ONLY/NO PLUMBING
 PLANS SUBMITTED.ELECTRICAL TO APPLY
 FOR SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By pkrauss Date 2004-09-16 Time 15:02 Rev Time 0.40
Received By pkrauss Date 2004-09-16 Time 15:02 Sent To  
Notes
2004-09-16 00:00:00DENIED:
 SEE COMMENT #2 BY DEWEY PALMER
 ELECTRICAL PLAN REVIEW.PLANS ARE
 OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.