Plan Review Details - Permit 04080749
Plan Review Stops For Permit 04080749
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-30 Cont ID  
Sent By alange Date 2005-12-30 Time 10:16 Rev Time 0.66
Received By alange Date 2005-12-30 Time 09:41 Sent To  
Notes
2005-12-30 00:00:00DENIED
 BUILDING REVIEW OK
  
 PERSON RESPONSIBLE FOR THE DESIGN MUST
 PRINT AND SIGN THERE NAME.FBC 104.2.1
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-21 Cont ID  
Sent By alange Date 2004-12-21 Time 11:27 Rev Time 1.25
Received By alange Date 2004-12-21 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-16 Cont ID  
Sent By alange Date 2004-11-16 Time 16:16 Rev Time 1.00
Received By alange Date 2004-11-16 Time 16:16 Sent To  
Notes
2004-11-16 00:00:00DENIED
  
 SEE COMMENTS FROM FIRST REVIEW.NONE OF
 THE COMMENTS HAVE BEEN ADDRESSED.
  
 5. THIS IS OK SINCE BEDROOM HAS A DOOR
 EXITING TOO THE OUTSIDE.
  
 PLEASE REVIEW NOTES FROM FIRST REVIEW
 AND CONTACT ME IF YOU HAVE QUESTIONS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By pkrauss Date 2004-09-01 Time 09:40 Rev Time 1.33
Received By alange Date 2004-09-16 Time 13:38 Sent To  
Notes
2004-09-16 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA THE BUILDING VALUATION HAS BEEN
 CHANGED TO $82,812.ADDITIONAL PERMIT
 FEES OF $342.96 ARE DUE.
  
 4.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR THE FOLLOWING:ROOFING, WINDOWS,
 EXTERIOR DOORS, SHUTTERS AND STRAPS AND
 TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.MASTER BEDROOM EMERGENCY ESCAPE
 RESCUE OPENINGS MUST COMPLY WITH
 FBC 1005.4.A SH 24 WILL NOT WORK.
  
 6.SHOW LOCATION OF WINDOW "B" ON PLAN.
  
 7.1804.6.2.3 CRAWL SPACE ACCESS UNDER
 BUILDINGS WITHOUT BASEMENTS SHALL PRO
 VIDE ONE OPENING NOT LESS THAN 18X24"
  
 8.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT
 WILLREJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 9.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-21 Cont ID  
Sent By btrobaug Date 2005-12-21 Time 14:44 Rev Time 0.75
Received By btrobaug Date 2005-12-20 Time 09:59 Sent To P
Notes
2005-12-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESONSIBLE FOR THE PLANS
 MUST PRINT AND SIGN THEIR NAME TO SAME
 PER 104.2.1 FBC.
  
 2} THE INFORMATION ON THE PANELBOARD HAS
 BEEN REMOVED, PLEASE REPLACE.
  
 3} THE ELECTRICAL RISER GROUNDING
 ELECTRODE CONDUCTOR SYSTEM MUST COMPLY
 WITH 250.50 FOR THE RELOCATED METER.
  
 4} THERE ARE SEVERAL APPLIANCES ON THE
 PANEL SCHEDULE NOT LISTED IN THE
 CALCULATIONS. SEE 330.31.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-20 Time 15:24 Rev Time 0.50
Received By btrobaug Date 2004-08-24 Time 12:50 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 17:41 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 17:41 Sent To E
Notes
2005-12-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 13:31 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 13:31 Sent To M
Notes
2005-11-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 13:21 Sent To P
Notes
2004-12-13 00:00:00SENT TO "P" BOX./REV.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 16:07 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 16:07 Sent To P
Notes
2004-11-01 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 15:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-18 Cont ID  
Sent By mmclean Date 2004-08-20 Time 13:57 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 09:23 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-21 Cont ID  
Sent By tgordon Date 2005-11-21 Time 08:25 Rev Time 0.25
Received By tgordon Date 2005-11-21 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-01 Cont ID  
Sent By kstevens Date 2004-08-25 Time 15:01 Rev Time 0.35
Received By pkrauss Date 2004-09-01 Time 08:22 Sent To B
Notes
2004-09-01 00:00:00PROVISO:
 1.PER 2001 FBC(M) 307.2.3, AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED.
  
 2.A MINIMUM OF 4" CLEARANCE AROUND THE
 AHU IS REQUIRED PER 2001 FBC(M) 603.1.3.
  
 3.RETURN AIR REQUIRED FROM BEDROOM
 AREAS PER 2001 FBC(M) 601.4.SEE THE
 ATTACHED SCHEDULE FOR PROPER SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-23 Cont ID  
Sent By jleech Date 2005-12-23 Time 10:53 Rev Time 0.33
Received By jleech Date 2005-12-23 Time 10:53 Sent To B
Notes
2005-12-23 00:00:00PLUMBING PAGE REVISED OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 09:10 Rev Time 33.00
Received By kstevens Date 2004-11-04 Time 09:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By btrobaug Date 2004-08-24 Time 13:38 Rev Time 0.33
Received By kstevens Date 2004-08-25 Time 15:00 Sent To M
Notes
2004-08-25 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-18 Time 09:23 Rev Time 0.00
Received By mmclean Date 2004-08-20 Time 13:57 Sent To I
Notes
***NONE***