Plan Review Details - Permit 04080627
Plan Review Stops For Permit 04080627
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-11 Cont ID  
Sent By alange Date 2005-03-11 Time 09:06 Rev Time 1.00
Received By alange Date 2005-03-11 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-11 Cont ID  
Sent By prafter Date 2005-01-14 Time 08:09 Rev Time 1.50
Received By alange Date 2005-01-14 Time 08:09 Sent To  
Notes
2005-01-14 00:00:00DENIED
  
  
 1.713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
 NOC IS EXPIRED.
  
 3. QUALITY ASSURANCE PRODUCT APPROVAL
 MISSING FOR IMPACT PROTECTION FOR
 EXTERIOR DOORS.
 DCA APPROVAL FOR JELD-WEN DOOR DOES NOT
 GO WITH MIAMI-DADE APPROVAL. NOA NUMBERS
 DO NOT MATCH.
  
 ALL QUALITY ASSURANCE APPROVALS (
 MIAMI-DADE) FOR EXAMPLE REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.CORRECTIONS MADE TO PLANS NEED TO BE
 SIGNED BY THE ARCHITECT.
  
 7.ENERGY CALCS WALL "R" VALUE DIFFERS
 FROM PLANS TO ENERGY CALCS.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-17 Time 16:37 Rev Time 1.50
Received By alange Date 2004-08-19 Time 13:45 Sent To  
Notes
2004-08-19 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR THE FOLLOWING:
 EXT. DOORS, WINDOWS, IMPACT PROTECTION,
 ROOFING, TIEDOWNS AND STRAPS, HARDIE
 PLANK SIDING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.FBC 2309.6SHOW SIZE AND LOCATION
 OF ATTIC ACCESS.
  
 5.SHOW METHOD OF SLAB REINFORCEMENT.
  
 6.FBC 11-11 A MINIMUM NET CLEAR
 OPENING FOR BATHROOM DOOR IS 29" OR A
 32" DOOR.
  
 7.SUBMIT ENERGY CALCS COMPLYING WITH
 CHAPTER 13 FBC
  
 8.SHOW USE OF ROOMS ON FLOOR PLAN.
  
 9.SUBMIT 2 COPIES OF A SOILS REPORT.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-29 Cont ID  
Sent By dpalmer Date 2005-03-29 Time 17:07 Rev Time 0.25
Received By dpalmer Date 2005-03-29 Time 16:58 Sent To B
Notes
2005-03-29 00:00:00REDLINED 250.32,
 BLDG FOOTER STEEL AND CWP. AT DETACHED
 BLDG GROUNDING ELECTRODE SYSTEM.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-24 Cont ID  
Sent By gsalfeld Date 2005-03-04 Time 14:40 Rev Time 0.33
Received By dpalmer Date 2005-02-24 Time 06:36 Sent To P
Notes
2005-02-24 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE INCLUDE FOOTER STEEL AND
 COLD WATER FOR GROUNDING ELECTRODE AT
 DETACHED BLDG.250.32,250.50
 PLEASE SEE MISSING #8 EQUIPMENT GRND
 FROM EXISTING MAIN PANEL TO
 J-BOX.250.122
  
 2)NOTE: PLEASE SEE NEW PANEL SCHEDULE
 SUBMITTED, SHOULD INCLUDE AWG FOR BRANCH
 CIRCUITS ALONG WITH OCP.
  
 3)NOTE: PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED FOR LIV RM/ ADAPTABLE
 SLEEPING RM.
 210.12
  
 4)NOTE: PLEASE VERIFY IF NEW WASHER AND
 DRYER IS REPLACING EXSITNG? PLEASE SEE
 LOAD CALCS INCLUDE ONE ONLY?
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCS.
  
 6)NOTE: PLEASE SEE CONDUIT FILL FOR 1"
 SCHEDULE 80, 3#4'S AND 1#8. PLEAS
 INCREASE TO 1 1/4".
  
  
 PLEASE SEE BLDG COMMENTS FOR NOC EXPIRED
 PER FS 713
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 09:19 Rev Time 0.30
Received By dpalmer Date 2005-01-19 Time 09:19 Sent To P
Notes
2005-01-19 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT ELECTRICAL
 PLAN/DRAWINGS WHICH MEET CODE COMPLIANCE
 FOR 2002 NEC.
 PLEASE ALSO SEE NFPA-72 8-1 FOR SD
 REQUIREMENTS.
 PLEASE SEE THERE ARE MANY THING MISSING
 REQUIRED. RISER DIAGRAM, DISC, A/C
 RECEPTS ETC.
  
 2)NOTE: PLEASE SEEFBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE THE PRINTED NAME
 AND SIGNATURE FOR THE PERSON RESPONSIBLE
 FOR PLANS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) THAT MAY AFFECT
 ELECTRICAL PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 11:27 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 11:27 Sent To M
Notes
2006-06-30 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 10:20 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 10:19 Sent To E
Notes
2005-03-29 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 08:48 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 08:48 Sent To E
Notes
2005-02-18 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 12:27 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 12:27 Sent To B
Notes
2005-01-10 00:00:00TO "AL" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-17 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-08-17 Time 16:36 Sent To B
Notes
2004-08-17 00:00:00TO RES BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-13 Cont ID  
Sent By mmclean Date 2004-08-17 Time 13:08 Rev Time 0.00
Received By csiegber Date 2004-08-13 Time 13:58 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-07-26 Cont ID  
Sent By tgordon Date 2006-07-26 Time 13:47 Rev Time 0.20
Received By tgordon Date 2006-07-26 Time 13:47 Sent To  
Notes
2006-07-26 00:00:00REVISION TO E- CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-07-06 Cont ID  
Sent By tgordon Date 2006-07-06 Time 11:10 Rev Time 0.30
Received By tgordon Date 2006-07-06 Time 11:10 Sent To  
Notes
2006-07-06 00:00:00REVISION TO ENERGY CAL'S
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-2001 (2001) AS YOUR BUILDING
 PERMIT MUST COMPLY WITH 2001 FBC.
  
 2) NEW ENERGY CAL'S ARE TAKING HVAC
 CREDITS FOR MULTIZONE COOLING AND
 MULTIZONE HEATING, THERE TI ONLY ONE A/C
 SYSTEM SO YOU CAN NOT HAVE MULTIZONE,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-02 Cont ID  
Sent By hmoser Date 2006-05-02 Time 13:57 Rev Time 0.00
Received By hmoser Date 2006-05-02 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-09 Time   Rev Time 0.00
Received By hmoser Date 2005-03-09 Time 17:16 Sent To B
Notes
2005-03-09 00:00:00REFER TO SECTION 610.1ABC.3.5.2 FLORIDA
 ENERGY CODE. NOTICE TO HOMEOWNER.CHECK
 ON FINAL INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By prafter Date 2005-01-25 Time 08:50 Rev Time 0.00
Received By prafter Date 2005-01-25 Time 09:31 Sent To B
Notes
2005-01-25 00:00:00REQUIRED TWO SET OF A/C PLANS WITH
 DUCT WORK SIZES AND GRILL SIZE.
 EQUIPMENT INFORMATION WITH LOCATION /
 CONDENSATE DETAILS /BATH ROOM EXHAUST,
 MUST BE REFLECTED ON A/C PLANS.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-04 Cont ID  
Sent By gsalfeld Date 2005-03-04 Time 14:42 Rev Time 0.50
Received By gsalfeld Date 2005-03-04 Time 14:42 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-01-20 Cont ID  
Sent By jleech Date 2005-01-20 Time 14:50 Rev Time 0.25
Received By jleech Date 2005-01-20 Time 14:50 Sent To M
Notes
2005-01-20 00:00:00NO PLUMBING INFORMATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-13 Time 13:58 Rev Time 0.00
Received By mmclean Date 2004-08-17 Time 13:08 Sent To I
Notes
***NONE***