Plan Review Details - Permit 04080603
Plan Review Stops For Permit 04080603
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-16 Time 11:47 Rev Time 0.75
Received By btrobaug Date 2004-08-23 Time 14:57 Sent To  
Notes
2004-08-23 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE INTENT OF THIS PROVISO IS TO ALLOW
 WORK TO BEGIN WHILE DETERMINATION OF
 DEVICE LOCATION IS MADE PER ACTUAL
 FIELD CONDITIONS. THE PLANS SUBMITTED
 NEED TO HAVE ADDITIONAL INFORMATION.
 PROVIDE A REVISED SET OF PLANS WITH THE
 FOLLOWING PRIOR TO CALLING A ROUGH
 INSPECTION.
  
 1} INDICATE THE LOCATION OF ALL SERVICE
 EQUIPMENT.
  
 2} LABEL ALL ROOMS. INDICATE DOOR
 LOCATIONS SO COMPLIANCE WITH 210.70 CAN
 BE DETERMINED. ALSO SHOW LIGHT AND
 SWITCHING DEVICE LOCATION.
  
 3} INDICATE COMPLIANCE WITH 210.52(E) &
 210.63.
  
 4} INCLUDE OCP AND CONDUCTOR SIZE ON THE
 PANEL SCHEDULE.
  
 5} INDICATE COMPLIANCE WITH 210.12 AND
 210.11(C)(3) ON THE PANEL SCHEDULE.
  
 THE DESIGNER OF RECORD RESPONSIBLE FOR
 THE DRAWING SHALL PRINT AND SIGN NAME
 ON SAME, FBC 104.2.1.
  
 ALLOW 2-3 DAYS AFTER SUBMITTING ABOVE
 FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 11:47 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 11:47 Sent To E
Notes
***NONE***