| Plan Review Stops For Permit 04080588 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-22 |
Time |
16:23 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-12-22 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2004-12-22 00:00:00 | 12-22-04 FIRESTOPPING DETAILSJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-05 |
Time |
14:14 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2004-11-05 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2004-11-05 00:00:00 | 11/05/04 LETTER FROM ARCH FOR FLOOR DECK | | | OF RAISED PLATFORM.JW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-10-08 |
Time |
15:06 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2004-10-08 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2004-10-08 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 04080588 | | | ADD: 700 S ROSEMARY# 208 | | | CONT: SCHIPPA CONST | | | TEL: (954)658-7493 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) FROM PREVIOUS REVIEW (5) PROVIDE | | | INFORMATION ON THE LIVE FLOOR LOADS FOR | | | THE RAISED SEATING AREA, ALSO PROVIDE | | | THE DESIGN CRITERIA LIVE LOAD FOR THE | | | RAMP, SEE TABLE 1604.1. | | | | | | 3) SEE 403.2.4.1. PERMANENT PLATFORMS | | | THAT ARE GREATER THAN 3000 SQ FT FOR | | | TYPE I, II, III, AND IV CONSRUCTION, | | | ( 80X45=3600+(12X12X.5)72=3672 SQ FT OF | | | RAISED DECK). | | | SHALL BE CONSTRUCTED OF THE SAME MATER- | | | IALS AS REQUIRED FOR THE TYPE OF CON- | | | STRUCTION OF THE BUILDING IN WHICH THE | | | PERMANENT PLATFORM IS LOCATED. | | | | | | 4) HANDRAILS ARE REQUIRED ON BOTH SIDES | | | OF THE STAIRS COMMENT# 13 FROM PREVIOUS | | | REVIEW. | | | B) 1007.5.2 STAIRWAYS SHALL HAVE HAND- | | | RAILS ON EACH SIDE. | | | C) 1007.5.5 HANDRAILS SHALL EXTEND AT | | | LEAST 12" HORIZONTALLY BEYOND THE TOP | | | RISER OF A FLIGHT OF STAIRS OR RAMP. AT | | | THE BOTTOM THE HANDRAIL SHALL CONTINUE | | | TO SLOPE FOR A DISTANCE OF THE DEPTH OF | | | ONE TREAD FROM THE BOTTOM RISER.SEE | | | BOTTOM OF RAMP! | | | | | | 5) COMMENT 10 FROM PREVIOUS REVIEW, REST | | | ROOMS SHALL HAVE A "NONABSORBANT" MATER- | | | IAL TO A HEIGHT OF 4'-0" ABOVE THE FLOOR | | | | | | 6)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-08-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-08-25 |
Time |
11:22 |
Rev Time |
6.60 |
| Received By |
jwitmer |
Date |
2004-08-25 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2004-08-25 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04080588 | | | ADD: 700 S ROSEMARY # 208 | | | CONT: SCHIPPA CONST | | | TEL: (954)658-7493 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PLANS ARE CONCEPTUAL IN NATURE, THEY DO | | | NOT PROVIDE DETAILS AAS TO WHAT WORK | | | WILL BE COMPLETED UNDER THIS PERMIT? | | | | | | 3) PLANS DO NOT PROVIDE THE MINIMUM | | | BUILDING TYPE? | | | | | | 4) PLANS INDICATE A DOOR# 3, WITH WIND | | | PRESSURES, IS THIS A NEW DOOR? IF THIS | | | IS A NEW DOOR PROVIDE PRODUCT APPROVAL, | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: DOOR# 3. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5) PROVIDE INFORMATION ON THE LIVE FLOOR | | | LOADS FOR THE RAISED SEATING AREA, ALSO | | | PROVIDE THE DESIGN CRITERIA LIVE LOAD | | | FOR THE RAMP, SEE TABLE 1604.1. | | | | | | 6) SEE 403.2.4.1. PERMANENT PLATFORMS | | | THAT ARE GREATER THAN 3000 SQ FT FOR | | | TYPE I, II,III AND IV CONSTRUCTION SHALL | | | BE CONSTRUCTED OF MATERIALS AS REQUIRED | | | FOR THE TYPE OF CONSTRUCTION OF THE | | | BUILDING IN WHICH THE PERMANENT PLATFORM | | | IS LOCATED.WHEN THE SPACE BENEATH THE | | | PERMANENT PLATFORM IS USED FOR STORAGE | | | OR ANY OTHER EQUIPMENT, WIRING, OR PLUMB | | | ING, THE FLOOR CONSTRUCTION SHALL NOT BE | | | LESS THAN 1-HOUR FIRE RESISTANT CON- | | | STRUCTION. | | | | | | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 8) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 9) PROVIDE A ROOM FINISH SCHEDULE. | | | | | | 10) 1204.2 SURROUNDING MATERIALS; | | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | | ROOMS SHALL BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | | FLOOR. | | | | | | 11) MISSING EXIT LIGHT AT THE REAR EXIT. | | | | | | 12) DOOR# 3, SHALL COMPLY WITH: | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 13) PLANS INDIATE THE USE OF A STAIARWAY | | | WITH 4 RISERS, TO COMPLY WITH: | | | A)1007.5.1 STAIRS WITH A MINIMUM OF | | | 4 RISERS SHALL BE EQUIPPED WITH HAND- | | | RAILS LOCATED NO LESS THAN 34" NOR MORE | | | THAN 38" ABOVE THE LEADING EDGE OF A | | | TREAD. | | | B) 1007.5.2 STAIRWAYS SHALL HAVE HAND- | | | RAILS ON EACH SIDE. | | | C) 1007.5.5. HANDRAILS SHALL EXTEND AT | | | LEAST 12 INCHES HORIZONTALLY BEYOND THE | | | TOP RISER OF A FLIGHT. .AT THE BOTTOM, | | | THE HANDRAIL SHALL CONTINUE TO SLOPE FOR | | | A DISTANCE OF THE DEPTH OF ONE TREAD | | | FROM THE BOTTOM RISER. | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-17 |
Time |
07:05 |
Rev Time |
0.20 |
| Received By |
dpalmer |
Date |
2005-02-17 |
Time |
07:05 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-03 |
Time |
10:19 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-03 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2004-12-03 00:00:00 | LTR TO REVISE AND PERMIT THE USE OF MC | | | CABLE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-28 |
Time |
16:20 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-10-28 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-24 |
Time |
08:58 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-09-24 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2004-09-24 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS | | | REVIEW. IF FLOOR BOXES ARE NOT ACCESS- | | | -IBLE, ALL WIRING MUST BE REMOVED AND | | | SHALL NOT BE CAPPED OFF AS NOTED ON | | | PLANS. | | | | | | 2)NOTE: PLEASE SEE NOTE ON PREVIOUS | | | REVIEW. | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS MAY BE | | | SUBMITTED SEPARATELY FOR REFERENCE ONLY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-24 |
Time |
09:30 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-08-24 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2004-08-24 00:00:00 | *********** UNSAT *********** | | | | | | 1)NOTE: PLEASE CLARIFY CONTROL(S) FOR | | | HIBACHI TABLE"S EXHAUST FANS? | | | | | | 2)NOTE: PLEASE PROVIDE MORE INFORMATION | | | FOR SHUT DOWN OF HOOD/ELECTRICAL DEVICES | | | ETC. | | | PER NFPA-96 CHAPTES 5,6,7,9 | | | | | | 3)NOTE: PLEASE SEE A NOTE ON PLANS MENT- | | | -IONS ALL FLOOR RECEPTS TO BE CAPPED | | | AND CIRCUITING ABANDONED. | | | PLEASE SEE IF THESE FLOOR BOXES WILL NOT | | | REMAIN ACCESSIBLE THEN WIRING WILL BE | | | REQUIRED TO BE REMOVED COMPLETELY. | | | RACEWAYS MAY REMAIN/ALONG W/ BOXES AFTER | | | WIRING IS REMOVED. | | | | | | 4)NOTE: PLEASE SEE SOME SHEETS ALONG | | | W/ TITLE SHEETS CONTAIN "METRO DESIGN | | | GROUP" PLEASE EITHER REMOVE THIS OR | | | PLEASE INCLUDE REQUIRED LICENSE # INFOR- | | | -MATION AS REQUIRED UNDER FS 471.023 AND | | | FAC 61G15-23.002. | | | PLEASE SEE ONE SET OF PLANS HAVE SAID | | | SHEETS REMOVED AND RETAINED FOR FILE. | | | | | | THIS IS FOR ALL SHEETS WHEATHER OR NOT | | | COMMENT IS MADE FROM OTHER REVIEWERS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | REVIEWS AS THEY MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-02-23 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-02-23 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-02-23 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2005-02-23 00:00:00 | REVISION ADD EXISTING HORN/STROBE TO | | | PLAN |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-11-10 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-11-10 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2004-09-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-09-28 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-09-28 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2004-09-28 00:00:00 | 1) HANDRAILS REQUIRED ON BOTH SIDES | | | OF NEW STAIRS TO ELEVATED PLATFORMS. | | | | | | 2) WHERE ARE THE FIRE ALARM DEVICES. | | | COULD NOT LOCATE ANY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-09-15 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-09-15 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2004-09-15 00:00:00 | ************DENIED********************** | | | | | | 1) HOW DOES THIS REMODEL AFFECTS THE | | | FIRE SPRINKLER PROTECTION COVERAGE. | | | | | | 2) SEPARATE PLAN AND PERMIT APPLICATION | | | ARE REQUIRED FOR FIRE SPRINKLER SYSTEM. | | | | | | 3) THERE IS A STAIR LEADING TO THE | | | ELEVATED DINNING AREA THAT REQUIRES | | | HANDRAILS ON BOTH SIDES. | | | | | | 4) SEPARATE PLAN AND PERMIT APPLICATION | | | ARE REQUIRED FOR HOOD SUPPRESSION SYSTEM | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-11 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-11 |
Time |
16:28 |
Sent To |
E |
|
| Notes |
| 2005-02-11 00:00:00 | TO DPALMER DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-03 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-03 |
Time |
15:41 |
Sent To |
G |
|
| Notes |
| 2005-02-03 00:00:00 | TO KS DESK/REVISIONS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-12-17 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-17 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-17 |
Time |
15:46 |
Sent To |
B |
|
| Notes |
| 2004-12-17 00:00:00 | SENT TO "JW" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-25 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-25 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | TO COMM BD#36 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-10-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-20 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-20 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2004-10-20 00:00:00 | TO COMM BD# |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-10-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-19 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-19 |
Time |
11:34 |
Sent To |
P |
|
| Notes |
| 2004-10-19 00:00:00 | TO KS BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-09-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-23 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-23 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2004-09-23 00:00:00 | TO COMM BD#53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-09-15 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-08-13 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2004-08-13 00:00:00 | TO COMM BD#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-11-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-15 |
Time |
09:22 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2004-11-15 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2004-11-15 00:00:00 | PROVISO: | | | 1.ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPPRESSION, AND WALK-IN | | | COOLERS/FREEZERS.PROVIDE MANUFACTURER | | | SUBMITTAL & INSTALLATION INSTRUCTIONS | | | WITH PERMIT APPLICATION. | | | | | | 2.GREASE DUCT TO BE INSPECTED PRIOR TO | | | COVERING. | | | | | | 3.PROVIDE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THE "3M FASTWRAP +" | | | WITH THE PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-14 |
Time |
09:51 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2004-10-14 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2004-10-14 00:00:00 | DENIED: | | | 1.PROVIDE REVISED OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE IN | | | ACCORDANCE WITH 2001 FBC(M) 501.4. | | | | | | HOOD REVIEW: | | | PLEASE NOTE, PLANS SUBMITTED WITH THE | | | BUILDING APPLICATION.ADDITIONAL PERMIT | | | REQUIRED FOR THE HOOD.ADDITIONAL PLANS | | | AND PERMIT REQUIRED FOR THE FIRE | | | SUPPRESSION. | | | | | | 1.PLEASE INDICATE HOW COMPLIANCE WITH | | | 506.3.10, WILL BE MET.SHOW ACCESS TO | | | CLEANOUTS. | | | | | | 2.WELDS ARE TO BE INSPECTED PRIOR TO | | | COVERING. | | | | | | 3.A MINIMUM SLOPE OF 1/4" PER FT | | | REQUIRED FOR THE GREASE DUCT IN | | | ACCORDANCE WITH 2001 FBC(M) 506.3.9. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-08-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-27 |
Time |
10:24 |
Rev Time |
1.50 |
| Received By |
pkrauss |
Date |
2004-08-27 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2004-08-27 00:00:00 | DENIED: | | | HVAC REVIEW | | | 1.SHEET A3.5 INDICATES A NOTE ON THE FAN | | | COIL DETIAL "NOT APPROVED" PLEASE | | | CLARIFY. | | | | | | 2.SHEET A3.5 FAN COIL EQUIPMENT SCHEDULE | | | INDICATES NEW FAN COIL WITH DUCT SMOKE | | | DETECTOR.PLEASE VERIFY EXISTING FAN | | | COILS THAT HAVE THE CAPACITY TO EXCEED | | | 2,000 CFM ARE EQUIPPED WITH DUCT SMOKE | | | DETECTORS. | | | | | | HOOD REVIEW: | | | PLEASE NOTE ADDITIONAL PERMITS REQUIRED | | | FOR HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS.THE FOLLOWING COMMENTS ARE | | | FOR THE PLANS SUBMITTED FOR THE HOOD AND | | | GREASE DUCT. | | | | | | 1.PLAN SHEET A3.5 HIBACHI TABLE | | | EXHAUST.DETAIL INDICATES GREASE DUCT | | | SHARING THE SAME SHAFT.PER 2001 FBC(M) | | | 506.3.12 & 2001 NFPA 96 7.7.5.2, THE | | | ENCLOSURE SHALL BE SEPARATED FROM THE | | | DUCT BY A MINIMUM OF 6" & A MAXIMUM OF | | | 12".THE ENCLOSURE SHALL SERVE A SINGLE | | | GREASE DUCT.PLEASE REVISE DETAIL. | | | | | | 2.DUCTS ARE TO BE INSPECTED PRIOR TO | | | BEING ENCLOSED. | | | | | | 3.PROVIDE DISTANCE TO COMBUSTIBLES. | | | | | | 4.EXHAUST TO TERMINATE A MINIMUM OF | | | 40" ABOVE THE ROOF SURFACE. NFPA 96 | | | 7.8.2.1 (8). | | | | | | 5.10 FT MINIMUM REQUIRED FROM FRESH | | | AIR INTAKE, PROPERTY LINES AND ADJACENT | | | BUILDINGS. | | | | | | 6.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE HOOD. | | | | | | 7.EQUIPMENT SCHEDULE ON PLAN SHEET | | | A3.6 ONLY INDICATES TWO EXHAUST FANS. | | | PLANS INDICATE SIX NEW GRILL AREAS. | | | PLEASE SPECIFY ALL NEW GREASE DUCT & | | | HOODS WILL BE INSTALLED. | | | | | | 8.MINIMUM SLOPE OF 1/4" PER FOOT | | | REQUIRED PER 2001 FBC(M) 506.3.9. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-11-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-11-15 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-11-15 00:00:00 | 11/15/04 PLANS WERE APPROVED ON 11/8/04 | | | BY KEN, SEE DRAWINGS FOR HIS SIGNATURE. | | | LM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-10-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-19 |
Time |
11:34 |
Rev Time |
3.50 |
| Received By |
kstevens |
Date |
2004-10-12 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2004-10-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: COMMENT NUMBER TO | | | STAY THE SAME AS FIRST REVIEW. | | | | | | 6) SUBMIT MANUFACTURE SPECIFICATION FOR | | | WASTE PUMP. PUMP SHALL BE VENTED TO AT- | | | MOSPHERE. SECTION 916.5 | | | | | | 11(G) SUBMIT MANUF SPECIFICATIONS FOR | | | THE GAS REGULATORS. | | | | | | ********WHEN RESUBMITTING PLANS********* | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-09-15 |
Time |
17:53 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2004-09-15 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2004-09-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) METRO DESIGN GROUP SHOWN ON TITLE | | | BLOCK. SUBMIT A CERTIFICATE OF AUTHORI- | | | ZATION AS REQUIRED BY FAC 61G15-23.002 & | | | FS 471.025. | | | 2) DPBR STAMP IS REQUIRED ON BOTH SETS | | | OF PLANS AND A COPY OF THE DBPR WORK | | | SHEET REQUIRED ON EACH SET OF PLANS. | | | SECTION 101.4.7 | | | 3) SHTS A-3.2 & A-3.4 DISH WASHER SHALL | | | DISCHARGE INTO THE SANITARY SYSTEM, NOT | | | THE GREASE SYSTEM AS SHOWN. CITY UTILITY | | | REQUIREMENT. | | | 4) SHT A-3.4 GREASE/SANITARY RISERS: | | | SECTION 704.2 THE SIZE OF THE DRAINAGE | | | PIPE SHALL NOT BE REDUCED IN THE DIRECT- | | | ION OF THE FLOOR. MANY 3" FLOOR SINKS | | | ARE DRAINING INTO 2" DRAIN LINES. | | | 5) SHT A-3.4 GREASE/SANITARY RISERS, | | | SHOW ALL PIPE SIZES THROUGHOUT EACH SYS- | | | TEM. SECTION 104.2.1 | | | 6) SUBMIT MANUFACTURE SPECIFICATION FOR | | | EACH WASTE PUMP. EACH PUMP SHALL BE VEN- | | | TED TO ATMOSPHERE. - SECTION 916.5 | | | 7) WASTE PUMPS SHALL HAVE A CHECK VALVE | | | WITH A GATE VALVE ON THE DISCHARGE SIDE | | | OF THE CHECK VALVE. SECTION 712.2 | | | 8) SHT A-3.4 PLUMBING NOTES: | | | #8 MINIMUM 1/4" FT. REQUIRED FOR 2-1/2" | | | AND SMALLER PIPE. CORRECT NOTE. SECTION | | | 104.2.1 - TABLE 704.1 | | | #12 AIR CHAMBERS ARE NOT APPROVED. DE- | | | LETE FROM REFERENCE. SECTION 604.9 | | | 9) A WATER RISER DIAGRAM IS REQUIRED PER | | | SECTION 104.3.1.1. | | | 10) INDICATE MINIMUM FIXTURES PER TABLE | | | 1003.1. ARE SEATS FIXED OR NOT FIXED? | | | 11) THE FOLLOWING INFORMATION IS REQUIR- | | | ED FOR THE GAS PERMIT. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - SOME PIPE SIZES AND THE | | | LENGTHS ARE NOT SHOWN. | | | B. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). - INDICATE | | | THE DISTANCE FROM L/P TANK TO SECOND | | | STAGE (2 PSI - .5 PSI) REGULATOR. - THE | | | DISTANCE FROM THE SECOND STAGE REGULAT- | | | ORS AND MOST REMOTE FIXTURE IS SHOWN AS | | | APPROX. 100', BUT ADDS UP TO APPROX 148' | | | PLEASE CLARIFY. | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | D. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | E. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | G) SUBMIT MANUF. SPECIFICATIONS FOR THE | | | THE GAS REGULATORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|