Plan Review Details - Permit 04080588
Plan Review Stops For Permit 04080588
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-22 Cont ID  
Sent By jwitmer Date 2004-12-22 Time 16:23 Rev Time 0.75
Received By jwitmer Date 2004-12-22 Time 16:23 Sent To  
Notes
2004-12-22 00:00:0012-22-04 FIRESTOPPING DETAILSJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-05 Cont ID  
Sent By jwitmer Date 2004-11-05 Time 14:14 Rev Time 2.00
Received By jwitmer Date 2004-11-05 Time 14:14 Sent To  
Notes
2004-11-05 00:00:0011/05/04 LETTER FROM ARCH FOR FLOOR DECK
 OF RAISED PLATFORM.JW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-08 Cont ID  
Sent By jwitmer Date 2004-10-08 Time 15:06 Rev Time 3.00
Received By jwitmer Date 2004-10-08 Time 15:05 Sent To  
Notes
2004-10-08 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 04080588
 ADD: 700 S ROSEMARY# 208
 CONT: SCHIPPA CONST
 TEL: (954)658-7493
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FROM PREVIOUS REVIEW (5) PROVIDE
 INFORMATION ON THE LIVE FLOOR LOADS FOR
 THE RAISED SEATING AREA, ALSO PROVIDE
 THE DESIGN CRITERIA LIVE LOAD FOR THE
 RAMP, SEE TABLE 1604.1.
  
 3) SEE 403.2.4.1. PERMANENT PLATFORMS
 THAT ARE GREATER THAN 3000 SQ FT FOR
 TYPE I, II, III, AND IV CONSRUCTION,
 ( 80X45=3600+(12X12X.5)72=3672 SQ FT OF
 RAISED DECK).
 SHALL BE CONSTRUCTED OF THE SAME MATER-
 IALS AS REQUIRED FOR THE TYPE OF CON-
 STRUCTION OF THE BUILDING IN WHICH THE
 PERMANENT PLATFORM IS LOCATED.
  
 4) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF THE STAIRS COMMENT# 13 FROM PREVIOUS
 REVIEW.
 B) 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
 C) 1007.5.5 HANDRAILS SHALL EXTEND AT
 LEAST 12" HORIZONTALLY BEYOND THE TOP
 RISER OF A FLIGHT OF STAIRS OR RAMP. AT
 THE BOTTOM THE HANDRAIL SHALL CONTINUE
 TO SLOPE FOR A DISTANCE OF THE DEPTH OF
 ONE TREAD FROM THE BOTTOM RISER.SEE
 BOTTOM OF RAMP!
  
 5) COMMENT 10 FROM PREVIOUS REVIEW, REST
 ROOMS SHALL HAVE A "NONABSORBANT" MATER-
 IAL TO A HEIGHT OF 4'-0" ABOVE THE FLOOR
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By jwitmer Date 2004-08-25 Time 11:22 Rev Time 6.60
Received By jwitmer Date 2004-08-25 Time 11:09 Sent To  
Notes
2004-08-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080588
 ADD: 700 S ROSEMARY # 208
 CONT: SCHIPPA CONST
 TEL: (954)658-7493
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE CONCEPTUAL IN NATURE, THEY DO
 NOT PROVIDE DETAILS AAS TO WHAT WORK
 WILL BE COMPLETED UNDER THIS PERMIT?
  
 3) PLANS DO NOT PROVIDE THE MINIMUM
 BUILDING TYPE?
  
 4) PLANS INDICATE A DOOR# 3, WITH WIND
 PRESSURES, IS THIS A NEW DOOR? IF THIS
 IS A NEW DOOR PROVIDE PRODUCT APPROVAL,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: DOOR# 3.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) PROVIDE INFORMATION ON THE LIVE FLOOR
 LOADS FOR THE RAISED SEATING AREA, ALSO
 PROVIDE THE DESIGN CRITERIA LIVE LOAD
 FOR THE RAMP, SEE TABLE 1604.1.
  
 6) SEE 403.2.4.1. PERMANENT PLATFORMS
 THAT ARE GREATER THAN 3000 SQ FT FOR
 TYPE I, II,III AND IV CONSTRUCTION SHALL
 BE CONSTRUCTED OF MATERIALS AS REQUIRED
 FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORM
 IS LOCATED.WHEN THE SPACE BENEATH THE
 PERMANENT PLATFORM IS USED FOR STORAGE
 OR ANY OTHER EQUIPMENT, WIRING, OR PLUMB
 ING, THE FLOOR CONSTRUCTION SHALL NOT BE
 LESS THAN 1-HOUR FIRE RESISTANT CON-
 STRUCTION.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 9) PROVIDE A ROOM FINISH SCHEDULE.
  
 10) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 11) MISSING EXIT LIGHT AT THE REAR EXIT.
  
 12) DOOR# 3, SHALL COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 13) PLANS INDIATE THE USE OF A STAIARWAY
 WITH 4 RISERS, TO COMPLY WITH:
 A)1007.5.1 STAIRS WITH A MINIMUM OF
 4 RISERS SHALL BE EQUIPPED WITH HAND-
 RAILS LOCATED NO LESS THAN 34" NOR MORE
 THAN 38" ABOVE THE LEADING EDGE OF A
 TREAD.
 B) 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
 C) 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-02-17 Cont ID  
Sent By dpalmer Date 2005-02-17 Time 07:05 Rev Time 0.20
Received By dpalmer Date 2005-02-17 Time 07:05 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 10:19 Rev Time 0.25
Received By dpalmer Date 2004-12-03 Time 10:19 Sent To  
Notes
2004-12-03 00:00:00LTR TO REVISE AND PERMIT THE USE OF MC
 CABLE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-28 Cont ID  
Sent By dpalmer Date 2004-10-28 Time 16:20 Rev Time 0.33
Received By dpalmer Date 2004-10-28 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 08:58 Rev Time 0.33
Received By dpalmer Date 2004-09-24 Time 07:49 Sent To  
Notes
2004-09-24 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS
 REVIEW. IF FLOOR BOXES ARE NOT ACCESS-
 -IBLE, ALL WIRING MUST BE REMOVED AND
 SHALL NOT BE CAPPED OFF AS NOTED ON
 PLANS.
  
 2)NOTE: PLEASE SEE NOTE ON PREVIOUS
 REVIEW.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS MAY BE
 SUBMITTED SEPARATELY FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-24 Cont ID  
Sent By dpalmer Date 2004-08-24 Time 09:30 Rev Time 1.00
Received By dpalmer Date 2004-08-24 Time 09:23 Sent To  
Notes
2004-08-24 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY CONTROL(S) FOR
 HIBACHI TABLE"S EXHAUST FANS?
  
 2)NOTE: PLEASE PROVIDE MORE INFORMATION
 FOR SHUT DOWN OF HOOD/ELECTRICAL DEVICES
 ETC.
 PER NFPA-96 CHAPTES 5,6,7,9
  
 3)NOTE: PLEASE SEE A NOTE ON PLANS MENT-
 -IONS ALL FLOOR RECEPTS TO BE CAPPED
 AND CIRCUITING ABANDONED.
 PLEASE SEE IF THESE FLOOR BOXES WILL NOT
 REMAIN ACCESSIBLE THEN WIRING WILL BE
 REQUIRED TO BE REMOVED COMPLETELY.
 RACEWAYS MAY REMAIN/ALONG W/ BOXES AFTER
 WIRING IS REMOVED.
  
 4)NOTE: PLEASE SEE SOME SHEETS ALONG
 W/ TITLE SHEETS CONTAIN "METRO DESIGN
 GROUP" PLEASE EITHER REMOVE THIS OR
 PLEASE INCLUDE REQUIRED LICENSE # INFOR-
 -MATION AS REQUIRED UNDER FS 471.023 AND
 FAC 61G15-23.002.
 PLEASE SEE ONE SET OF PLANS HAVE SAID
 SHEETS REMOVED AND RETAINED FOR FILE.
  
 THIS IS FOR ALL SHEETS WHEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWS AS THEY MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-02-23 Cont ID  
Sent By nmccray Date 2005-02-23 Time 10:45 Rev Time 0.00
Received By nmccray Date 2005-02-23 Time 10:45 Sent To  
Notes
2005-02-23 00:00:00REVISION ADD EXISTING HORN/STROBE TO
 PLAN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-10 Cont ID  
Sent By nmccray Date 2004-11-10 Time 10:46 Rev Time 0.00
Received By nmccray Date 2004-11-10 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-28 Cont ID  
Sent By mcarsill Date 2004-09-28 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2004-09-28 Time 15:46 Sent To  
Notes
2004-09-28 00:00:001) HANDRAILS REQUIRED ON BOTH SIDES
 OF NEW STAIRS TO ELEVATED PLATFORMS.
  
 2) WHERE ARE THE FIRE ALARM DEVICES.
 COULD NOT LOCATE ANY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By nmccray Date 2004-09-15 Time 09:54 Rev Time 0.00
Received By nmccray Date 2004-09-15 Time 09:54 Sent To  
Notes
2004-09-15 00:00:00************DENIED**********************
  
 1) HOW DOES THIS REMODEL AFFECTS THE
 FIRE SPRINKLER PROTECTION COVERAGE.
  
 2) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 3) THERE IS A STAIR LEADING TO THE
 ELEVATED DINNING AREA THAT REQUIRES
 HANDRAILS ON BOTH SIDES.
  
 4) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR HOOD SUPPRESSION SYSTEM
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 16:28 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 16:28 Sent To E
Notes
2005-02-11 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 15:41 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 15:41 Sent To G
Notes
2005-02-03 00:00:00TO KS DESK/REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 15:46 Sent To B
Notes
2004-12-17 00:00:00SENT TO "JW" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:19 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 14:19 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:50 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:50 Sent To  
Notes
2004-10-20 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 11:34 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 11:34 Sent To P
Notes
2004-10-19 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-23 Cont ID  
Sent By csiegber Date 2004-09-23 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-09-23 Time 11:50 Sent To  
Notes
2004-09-23 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-15 Cont ID  
Sent By pkrauss Date 2004-09-15 Time 10:53 Rev Time 0.00
Received By mjacobs Date 2004-08-13 Time 09:32 Sent To  
Notes
2004-08-13 00:00:00TO COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-15 Cont ID  
Sent By pkrauss Date 2004-11-15 Time 09:22 Rev Time 2.00
Received By pkrauss Date 2004-11-15 Time 07:56 Sent To  
Notes
2004-11-15 00:00:00PROVISO:
 1.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION, AND WALK-IN
 COOLERS/FREEZERS.PROVIDE MANUFACTURER
 SUBMITTAL & INSTALLATION INSTRUCTIONS
 WITH PERMIT APPLICATION.
  
 2.GREASE DUCT TO BE INSPECTED PRIOR TO
 COVERING.
  
 3.PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE "3M FASTWRAP +"
 WITH THE PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-14 Cont ID  
Sent By pkrauss Date 2004-10-14 Time 09:51 Rev Time 1.00
Received By pkrauss Date 2004-10-14 Time 08:53 Sent To  
Notes
2004-10-14 00:00:00DENIED:
 1.PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.PROVIDE AIR BALANCE SCHEDULE IN
 ACCORDANCE WITH 2001 FBC(M) 501.4.
  
 HOOD REVIEW:
 PLEASE NOTE, PLANS SUBMITTED WITH THE
 BUILDING APPLICATION.ADDITIONAL PERMIT
 REQUIRED FOR THE HOOD.ADDITIONAL PLANS
 AND PERMIT REQUIRED FOR THE FIRE
 SUPPRESSION.
  
 1.PLEASE INDICATE HOW COMPLIANCE WITH
 506.3.10, WILL BE MET.SHOW ACCESS TO
 CLEANOUTS.
  
 2.WELDS ARE TO BE INSPECTED PRIOR TO
 COVERING.
  
 3.A MINIMUM SLOPE OF 1/4" PER FT
 REQUIRED FOR THE GREASE DUCT IN
 ACCORDANCE WITH 2001 FBC(M) 506.3.9.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-27 Cont ID  
Sent By pkrauss Date 2004-08-27 Time 10:24 Rev Time 1.50
Received By pkrauss Date 2004-08-27 Time 09:14 Sent To  
Notes
2004-08-27 00:00:00DENIED:
 HVAC REVIEW
 1.SHEET A3.5 INDICATES A NOTE ON THE FAN
 COIL DETIAL "NOT APPROVED" PLEASE
 CLARIFY.
  
 2.SHEET A3.5 FAN COIL EQUIPMENT SCHEDULE
 INDICATES NEW FAN COIL WITH DUCT SMOKE
 DETECTOR.PLEASE VERIFY EXISTING FAN
 COILS THAT HAVE THE CAPACITY TO EXCEED
 2,000 CFM ARE EQUIPPED WITH DUCT SMOKE
 DETECTORS.
  
 HOOD REVIEW:
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.THE FOLLOWING COMMENTS ARE
 FOR THE PLANS SUBMITTED FOR THE HOOD AND
 GREASE DUCT.
  
 1.PLAN SHEET A3.5 HIBACHI TABLE
 EXHAUST.DETAIL INDICATES GREASE DUCT
 SHARING THE SAME SHAFT.PER 2001 FBC(M)
 506.3.12 & 2001 NFPA 96 7.7.5.2, THE
 ENCLOSURE SHALL BE SEPARATED FROM THE
 DUCT BY A MINIMUM OF 6" & A MAXIMUM OF
 12".THE ENCLOSURE SHALL SERVE A SINGLE
 GREASE DUCT.PLEASE REVISE DETAIL.
  
 2.DUCTS ARE TO BE INSPECTED PRIOR TO
 BEING ENCLOSED.
  
 3.PROVIDE DISTANCE TO COMBUSTIBLES.
  
 4.EXHAUST TO TERMINATE A MINIMUM OF
 40" ABOVE THE ROOF SURFACE. NFPA 96
 7.8.2.1 (8).
  
 5.10 FT MINIMUM REQUIRED FROM FRESH
 AIR INTAKE, PROPERTY LINES AND ADJACENT
 BUILDINGS.
  
 6.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE HOOD.
  
 7.EQUIPMENT SCHEDULE ON PLAN SHEET
 A3.6 ONLY INDICATES TWO EXHAUST FANS.
 PLANS INDICATE SIX NEW GRILL AREAS.
 PLEASE SPECIFY ALL NEW GREASE DUCT &
 HOODS WILL BE INSTALLED.
  
 8.MINIMUM SLOPE OF 1/4" PER FOOT
 REQUIRED PER 2001 FBC(M) 506.3.9.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-15 Cont ID  
Sent By lmartine Date 2004-11-15 Time 13:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2004-11-15 00:00:0011/15/04 PLANS WERE APPROVED ON 11/8/04
 BY KEN, SEE DRAWINGS FOR HIS SIGNATURE.
 LM

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-19 Time 11:34 Rev Time 3.50
Received By kstevens Date 2004-10-12 Time 15:21 Sent To  
Notes
2004-10-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW: COMMENT NUMBER TO
 STAY THE SAME AS FIRST REVIEW.
  
 6) SUBMIT MANUFACTURE SPECIFICATION FOR
 WASTE PUMP. PUMP SHALL BE VENTED TO AT-
 MOSPHERE. SECTION 916.5
  
 11(G) SUBMIT MANUF SPECIFICATIONS FOR
 THE GAS REGULATORS.
  
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By kstevens Date 2004-09-15 Time 17:53 Rev Time 2.50
Received By kstevens Date 2004-09-15 Time 17:53 Sent To  
Notes
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) METRO DESIGN GROUP SHOWN ON TITLE
 BLOCK. SUBMIT A CERTIFICATE OF AUTHORI-
 ZATION AS REQUIRED BY FAC 61G15-23.002 &
 FS 471.025.
 2) DPBR STAMP IS REQUIRED ON BOTH SETS
 OF PLANS AND A COPY OF THE DBPR WORK
 SHEET REQUIRED ON EACH SET OF PLANS.
 SECTION 101.4.7
 3) SHTS A-3.2 & A-3.4 DISH WASHER SHALL
 DISCHARGE INTO THE SANITARY SYSTEM, NOT
 THE GREASE SYSTEM AS SHOWN. CITY UTILITY
 REQUIREMENT.
 4) SHT A-3.4 GREASE/SANITARY RISERS:
 SECTION 704.2 THE SIZE OF THE DRAINAGE
 PIPE SHALL NOT BE REDUCED IN THE DIRECT-
 ION OF THE FLOOR. MANY 3" FLOOR SINKS
 ARE DRAINING INTO 2" DRAIN LINES.
 5) SHT A-3.4 GREASE/SANITARY RISERS,
 SHOW ALL PIPE SIZES THROUGHOUT EACH SYS-
 TEM. SECTION 104.2.1
 6) SUBMIT MANUFACTURE SPECIFICATION FOR
 EACH WASTE PUMP. EACH PUMP SHALL BE VEN-
 TED TO ATMOSPHERE. - SECTION 916.5
 7) WASTE PUMPS SHALL HAVE A CHECK VALVE
 WITH A GATE VALVE ON THE DISCHARGE SIDE
 OF THE CHECK VALVE. SECTION 712.2
 8) SHT A-3.4 PLUMBING NOTES:
 #8 MINIMUM 1/4" FT. REQUIRED FOR 2-1/2"
 AND SMALLER PIPE. CORRECT NOTE. SECTION
 104.2.1 - TABLE 704.1
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SECTION 604.9
 9) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 10) INDICATE MINIMUM FIXTURES PER TABLE
 1003.1. ARE SEATS FIXED OR NOT FIXED?
 11) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR THE GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - SOME PIPE SIZES AND THE
 LENGTHS ARE NOT SHOWN.
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - INDICATE
 THE DISTANCE FROM L/P TANK TO SECOND
 STAGE (2 PSI - .5 PSI) REGULATOR. - THE
 DISTANCE FROM THE SECOND STAGE REGULAT-
 ORS AND MOST REMOTE FIXTURE IS SHOWN AS
 APPROX. 100', BUT ADDS UP TO APPROX 148'
 PLEASE CLARIFY.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 G) SUBMIT MANUF. SPECIFICATIONS FOR THE
 THE GAS REGULATORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved