Plan Review Details - Permit 04080563
Plan Review Stops For Permit 04080563
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-03 Cont ID  
Sent By alange Date 2005-08-03 Time 12:39 Rev Time 0.50
Received By alange Date 2005-08-03 Time 12:39 Sent To  
Notes
2005-08-03 00:00:00SHUTTER REV. OK FOR FRENCH DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-18 Cont ID  
Sent By alange Date 2005-02-18 Time 11:09 Rev Time 0.33
Received By alange Date 2005-02-18 Time 11:09 Sent To  
Notes
2005-02-18 00:00:00REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-28 Cont ID  
Sent By alange Date 2005-01-28 Time 13:07 Rev Time 0.66
Received By alange Date 2005-01-28 Time 13:07 Sent To  
Notes
2005-01-28 00:00:00DENIED
  
 1.REVISION SUBMITED IS REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD.
  
 2.CLEARLY MARK REVISION ON PLANS, I
 DID NOT LOCATE ANY CHANGES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-19 Cont ID  
Sent By alange Date 2004-11-19 Time 13:35 Rev Time 1.25
Received By alange Date 2004-11-19 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By pkrauss Date 2004-10-27 Time 10:54 Rev Time 2.00
Received By alange Date 2004-10-28 Time 13:34 Sent To  
Notes
2004-10-28 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF
 COMMENCEMENTSHALL BE RECORDED AT PALM
 BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BERE-RECORDED IF THE DESCRIBED
 IMPROVEMENTOR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.ORIGONAL PERMIT APPLICATION MISSING.
  
 4.INCLUDE BOTH NEW AND EXISTING WORK
 IN AREA TOTALS.
  
 5.SUBMIT 2 SIGNED AND SEALED COPIES OF
 A SOILS REPORT.
  
 6.SMOKE DETECTORS SHALL COMPLY WITH
 FBC 905.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-06-29 Cont ID  
Sent By jleahy Date 2005-06-29 Time 23:23 Rev Time 1.00
Received By jleahy Date 2005-06-29 Time 23:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-04-19 Cont ID  
Sent By jleahy Date 2005-04-19 Time 09:54 Rev Time 0.30
Received By jleahy Date 2005-04-19 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-04-12 Cont ID  
Sent By jleahy Date 2005-04-12 Time 10:05 Rev Time 1.00
Received By jleahy Date 2005-04-12 Time 10:05 Sent To  
Notes
2005-04-12 00:00:00RISER DIAGRAM SHOWS A 200 AMP SERVICE
  
 LOAD CALCULATION SHOWS 380 AMPS.RISER
  
 SHOW JUST TWO 200 AMP PANELS, BUT PLAN
  
 SHOWS TWO ADDITIONAL 60 AMP SUB PANELS.
  
 IN THE MASTER BEDROOM THERE APEARS TO BE
  
  
 TWO WALK IN CLOSETS, BOTH HAVE LIGHTS
  
 THAT APEAR TO BE IN VIOLATION OF 410.8
  
 A-D.PLAN SHOW A 100 AMP SERVICE ON
  
 DRAWINGS?PLANS SHOW TWO DIFFERENT
  
 LOCATIONS FOR THE A/C COMPRESSORS.
  
 PANEL SCHEDULES AND LOAD CALCULATIONS
  
 DO NOT REFLECT THE TWO 60 AMP
  
 SUB-PANELS.
  
 PLANS OUT FRONT UNDER "S"JL

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-07 Cont ID  
Sent By btrobaug Date 2004-12-07 Time 11:54 Rev Time 0.00
Received By btrobaug Date 2004-12-06 Time 16:52 Sent To  
Notes
2004-12-07 00:00:00 
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH ELECTRICAL
 INSPECTION.
  
 1} SUBMIT RISER DIAGRAM REFLECTING ALL
 COMPONENTS IN THE SYSTEM. PLEASE
 CORRELATE RATINGS ON THE RISER WITH THE
 RATINGS SHOWN ON THE PLAN AT PANEL
 LOCATIONS, SEE REDLINED SET OF
 DRAWINGS.
  
 2} THE PANEL LOCATED IN THE "STORAGE
 ROOM" IS IN VIOLATION OF 240.24(D).
 ALSO
 NOTE THIS IS SHOWN AS 125 AMPS AND THE
 ORIGINAL RISER DID NOT SHOW ANY PANEL
 THAT SIZE.
  
 3} NOTE MISSING RECEPTACLES IN ALL
 BEDROOMS. 210.52(A)(1) & (2).
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-17 Cont ID  
Sent By btrobaug Date 2004-11-17 Time 12:26 Rev Time 0.50
Received By btrobaug Date 2004-11-17 Time 07:44 Sent To B
Notes
2004-11-17 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
  
  
 1} PLEASE PROVIDE A CALCULATION INCLUDI-
 NG ALL ADDED LOADS IMPOSED,ALL EXISTING
 LOADS AND THE EXISTING OR PROPOSED SERVI
 CE SPECIFICATIONS PER 215.15. INDICATE
 IF THE SERVICE IS NEW OR EXISTING.
  
 2}PLEASE PROVIDE PANEL SCHEDULES FOR
 ALL PANELS
  
 3} SHEET E-14 SHOWS 5 CONDENSING UNITS.
 PLEASE VERIFY, CORRELATE LOCATION WITH
 MECHANICAL PLAN AND SHOW CORRECT NUMBER
 AND LOCATION ON ELECTRICAL PLAN.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:28 Rev Time 0.75
Received By btrobaug Date 2004-10-19 Time 10:23 Sent To P
Notes
2004-10-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED
 SERVICE SPECIFICATIONS PER 215.15.
 ALSO INCLUDE PANEL SCHEDULES SO THAT
 BRANCH CIRCUIT REQUIREMENTS FOR OCP AND
 WIRE SIZES MAY BE REVIEWED.
  
 2} PLEASE COMBINE EXISTING DEVICES AND
 ADDED DEVICES ON THE SAME DRAWING WITH
 EXISTING DEVICES IDENTIFIED. IT IS
 UNCLEAR LOOKING AT EXISTING AND
 PROPOSED PLANS WHICH WILL BE REMOVED
 DUE TO CHANGES IN ARCHITECTURE. COMBINE
 ALL DEVICES ON PROPOSED PLAN.
  
 3} ONE OF THE EXISTING CONDENSING UNITS
 DOES NOT APPEAR ON THE NEW PLAN. THE
 ELECTRICAL PLAN DIFFERS FROM THE
 MECHANICAL PLAN, PLEASE CORRELATE.
  
 4} PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 5} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52(E).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 13:38 Sent To B
Notes
2005-08-02 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 15:55 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 15:55 Sent To E
Notes
2005-04-14 00:00:00TO "JLEAHY"

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-04-11 Cont ID  
Sent By adarroug Date 2005-04-11 Time 13:07 Rev Time 0.00
Received By adarroug Date 2005-04-11 Time 13:07 Sent To E
Notes
2005-04-11 00:00:00TO "JLEAHY" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 11:22 Sent To M
Notes
2005-03-17 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:13 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:13 Sent To B
Notes
2005-02-28 00:00:00TO "MISC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 15:16 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 15:16 Sent To B
Notes
2005-02-11 00:00:00TO ALANGE DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 16:14 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 16:14 Sent To Z
Notes
2005-02-03 00:00:00TO " Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-01-24 Cont ID  
Sent By mjacobs Date 2005-01-24 Time 17:08 Rev Time 0.00
Received By mjacobs Date 2005-01-24 Time 17:08 Sent To B
Notes
2005-01-24 00:00:00TO "AL" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 16:09 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 16:09 Sent To Z
Notes
2005-01-19 00:00:00TO "Z" BOX/REV.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-12-03 Time 08:11 Rev Time 0.00
Received By mjacobs Date 2004-12-03 Time 08:11 Sent To E
Notes
2004-12-03 00:00:00SENT TO "BT" DESK.
 SENT TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 14:13 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 14:13 Sent To E
Notes
2004-11-05 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:28 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:28 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-04 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:22 Sent To Z
Notes
2004-10-04 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 15:24 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-31 Time   Rev Time 0.00
Received By hmoser Date 2005-03-31 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-27 Cont ID  
Sent By kstevens Date 2004-10-21 Time 11:47 Rev Time 0.25
Received By pkrauss Date 2004-10-26 Time 16:32 Sent To B
Notes
2004-10-27 00:00:00THE ORIGINAL PERMIT WAS NOT WITH THE
 RE-SUBMITTAL PACKAGE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-10-21 Cont ID  
Sent By btrobaug Date 2004-10-19 Time 11:15 Rev Time 0.50
Received By kstevens Date 2004-10-21 Time 11:47 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2005-02-11 Cont ID  
Sent By mmclean Date 2005-02-11 Time 13:32 Rev Time 0.00
Received By mmclean Date 2005-02-11 Time 13:32 Sent To I
Notes
2005-02-11 00:00:00APPROVING GARAGE EXPANDED 8" BACKWARDS
 IN REAR.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-01-24 Cont ID  
Sent By mmclean Date 2005-01-24 Time 16:14 Rev Time 0.00
Received By mmclean Date 2005-01-24 Time 16:14 Sent To I
Notes
2005-01-24 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY SHOWING THE EXPANSION OF GARAGE
 BY 8", TO MAKE SHOW IT MEETS THE
 SETBACK.REVISION. CALLED CONTR

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-18 Cont ID  
Sent By mmclean Date 2004-10-18 Time 10:36 Rev Time 0.00
Received By mmclean Date 2004-10-18 Time 10:36 Sent To I
Notes
2004-10-18 00:00:00MUST PULL SEPARATE PERMIT FOR WALL/FENCE
 WITH UTILITY EASEMENT APPROVAL FROM
 CITY UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:22 Rev Time 0.00
Received By mmclean Date 2004-08-19 Time 12:05 Sent To  
Notes
2004-08-19 00:00:00DENIED, NEED TO MEET FRONT SETBACK
 OF 25FT.CALLED CONTR FOR P/U S MM


Account Summary | Usage Policy | Privacy Policy