Plan Review Details - Permit 04080424
Plan Review Stops For Permit 04080424
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-13 Cont ID  
Sent By dpalmer Date 2004-10-14 Time 13:20 Rev Time 0.00
Received By btrobaug Date 2004-11-10 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-12-16 Cont ID  
Sent By dpalmer Date 2004-12-16 Time 11:28 Rev Time 0.33
Received By dpalmer Date 2004-12-16 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-10 Cont ID  
Sent By btrobaug Date 2004-11-10 Time 13:04 Rev Time 0.75
Received By btrobaug Date 2004-11-10 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-10 Cont ID  
Sent By btrobaug Date 2004-11-10 Time 13:02 Rev Time 0.75
Received By btrobaug Date 2004-10-23 Time 16:38 Sent To  
Notes
2004-11-10 00:00:00THIS STOP SND THIS NOTE WAS ENTERED BY
 DEE. THE OUT WAS LEFT OPEN HENCE MY
 NAME
 APPEARS.
  
 BILL TROBAUGH
2004-10-23 00:00:00***PLANS RESUBBED W/OUT APPLICATION,
 ORIG PLANS ETC.
 RE-SUB SENT BACK TO PEGGY.
 COMPLETE PACKAGE/PLANS TO BE SUBMITTED
 BEFORE THEY CAN BE REVIEWED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:07 Rev Time 0.33
Received By dpalmer Date 2004-10-14 Time 13:04 Sent To B
Notes
2004-10-14 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PREVIOUS NOTES.
 PLEASE PROVIDE ALL INFORMATION ON TITLE
 BLOCK(S). AS REQUIRED UNDER FAC 61G1-16,
 .004, FAC 61G15-23.002.
 FS 481.219,471.023.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE CLARIFY METHOD OF TRANS-
 -FER OF POWER FROM PERM TO STANDBY.
 APPEARS POWERE MAY BE ON EQUIPMENT FROM
 BOTH SOURCES AT THE SAME TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:54 Rev Time 0.50
Received By dpalmer Date 2004-08-19 Time 15:31 Sent To  
Notes
2004-08-19 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS RQUIRED UNDER FAC 61G-
 15-23.002.
 FS 471.023
  
 2)NOTE: PLEASE SEE 230.72 FOR GROUPING
 OF MAINS/SIGNAGE PER 230.2E
 PLEASE PROVIDE NOTES ON PLANS FOR
 CORRETC SIGNAGE TO BE PROVIDED.
  
 3)NOTE: PLEASE SEE RISER. PLEASE SEE
 EQUIPMENT GROUNDING CONDUCTOR INSTALLED
 FROM METER TO THE FIRST MEANS OF DISC.
 THIS IS NOT PEERMITTED UNDER NEC 250.24,
 250.6 ETC.
  
 4)NOTE: PLEASE SEE FBC 104.6.5 FOR VALUE
 OF SCOPE OF WORK. THIS IS TO INCLUDE
 ALL LABOR AND MATERIALS WHEATHER OR NOT
 EQUIPMENT IS OWNER SUPPLIED.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-12-15 Cont ID  
Sent By mjacobs Date 2004-12-15 Time 14:57 Rev Time 0.00
Received By mjacobs Date 2004-12-15 Time 14:57 Sent To E
Notes
2004-12-15 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-02 Cont ID  
Sent By csiegber Date 2004-11-02 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-11-02 Time 16:38 Sent To E
Notes
2004-11-02 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:07 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 17:07 Sent To E
Notes
2004-10-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:54 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 14:54 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-13 Cont ID  
Sent By alange Date 2004-08-13 Time 09:57 Rev Time 0.00
Received By alange Date 2004-08-13 Time 09:57 Sent To  
Notes
2004-08-13 00:00:00ON COMM BD #44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 15:59 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-10 Cont ID  
Sent By mmclean Date 2004-08-12 Time 12:19 Rev Time 0.00
Received By csiegber Date 2004-08-10 Time 15:27 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-10 Time 15:27 Rev Time 0.00
Received By mmclean Date 2004-08-12 Time 12:18 Sent To I
Notes
2004-08-12 00:00:00OK PER ANGELLA JONES MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved