Plan Review Details - Permit 04080359
Plan Review Stops For Permit 04080359
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By alange Date 2004-10-13 Time 07:53 Rev Time 0.50
Received By alange Date 2004-10-13 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By alange Date 2004-08-13 Time 13:35 Rev Time 0.66
Received By alange Date 2004-08-13 Time 13:35 Sent To  
Notes
2004-09-15 00:00:00DENIED
 1. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT FOR REVIEW.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 07:37 Rev Time 0.25
Received By dpalmer Date 2004-09-24 Time 07:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-16 Cont ID  
Sent By dpalmer Date 2004-08-16 Time 14:19 Rev Time 0.33
Received By dpalmer Date 2004-08-16 Time 14:19 Sent To  
Notes
2004-08-16 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE SEE THE PRINTED NAME AND LICENSE
 # OF ENGINEER OS ALSO REQUIRED ON TITLE
 BLOCK.
  
 2)NOTE: PLEASE INLCLUDE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED SHOWING ALL
 MIN REQUIRED CIRCUITS UNDER 2002 NEC.
 210.52,210.11C1,C3.
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: PLEASE SEE THAT HANDWRITTEN
 CHANGES TO PLANS MAY NOT BE DONE TO PLAN
 'S WHICH ARE SIGNED AND SEALED BY THE
 ENGINEER.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 10:03 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-09-21 Time 08:17 Rev Time 0.00
Received By csiegber Date 2004-09-21 Time 08:17 Sent To  
Notes
2004-09-21 00:00:00TO COMM BD#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-16 Cont ID  
Sent By mjacobs Date 2004-09-16 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2004-08-10 Time 17:12 Sent To  
Notes
2004-08-10 00:00:00TO COMM BD#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 16:18 Rev Time 0.30
Received By pkrauss Date 2004-10-08 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By pkrauss Date 2004-09-16 Time 08:46 Rev Time 0.40
Received By pkrauss Date 2004-09-16 Time 08:38 Sent To  
Notes
2004-09-16 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW:
  
 1.GENERAL NOTES #6 INDICATES A/C
 CONTRACTOR TO PROVIDE CALCULATIONS.THE
 CONTRACTOR IS SIGNED-ON TO THE BUILDING
 PERMIT APPLICATION, THEREFORE ALL
 INFORMATION AND PLANS SHOULD BE
 SUBMITTED WITH THIS PERMIT APPLICATION.
  
 2.PROVIDE EQUIPMENT SCHEDULE, DUCT
 & GRILLE LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-10-13 Cont ID  
Sent By kstevens Date 2004-10-13 Time 09:37 Rev Time 0.25
Received By kstevens Date 2004-10-13 Time 09:37 Sent To  
Notes
2004-10-13 00:00:00EXACT CHANGE OUT OF PLUMBING FIXTURES
 IN SAME LOCATION

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By kstevens Date 2004-09-15 Time 12:19 Rev Time 0.50
Received By kstevens Date 2004-09-15 Time 12:19 Sent To  
Notes
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) MORE INFORMATION REQUIRED. SUBMIT AN
 EXISTING FLOOR PLAN SHOWING LOCATION OF
 BATHROOMS AS APPLICATION INDICATES NEW
 BATHS. - IF NEW LOCATION FOR BATHROOMS/
 KITCHEN, A SANITARY & WATER RISER DIAG-
 RAM WILL BE REQUIRED. IF FIXTURE CHANGE
 OUT IN EXACT LOCATION, PLEASE INDICATE.
 SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]