Plan Review Details - Permit 04080335
Plan Review Stops For Permit 04080335
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-30 Cont ID  
Sent By alange Date 2004-08-30 Time 11:00 Rev Time 0.75
Received By alange Date 2004-08-30 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-26 Cont ID  
Sent By mjacobs Date 2004-08-26 Time 11:25 Rev Time 2.00
Received By mjacobs Date 2004-08-26 Time 11:24 Sent To  
Notes
2004-08-26 00:00:00BUILDING PLAN REVIEW
 PERMIT:04080335
 ADD: 643 33RD STREET
 CONT:NORTHWOOD BUSINESS DEV CORP
 TEL: (561)832-7959
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 PLEASE INDICATE CLEARLY WHERE EACH
 COMPONENT FOR TIE WILL BE USED.
  
 2) INFO. GUARDRAILS SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL
 PATTERN SUCH THAT A 4" DIAMETER SPHERE
 CANNOT PASS THROUGH ANY OPENING UP TO A
 HEIGHT OF 34". A BOTTOM RAIL OR CURB
 SHALL BE PROVIDED THAT WILL REJECT THE
 PASSAGE OF 2" DIAMETER SPHERE. ALSO
 PLEASE FBC. SEC.1015 AND SEC.1608.2.3
  
 3)1507.3.8. ASPHALT SHINGLES LOW
 SLOPE ROOFING, UNDERLAYMENT APPLICATION
 FOR ROOF SLOPES FROM 2:12 UP TO 4:12,
 UNDERLAYMENT SHAL BE A MINIMUM OF TWO
 LAYERS APPLIED AS FOLLOWS:
 1) STARTING AT THE EAVE, A 19-INCH
 STRIP OF UNDERLAYMENT SHALL BE APPLIED
 PARALLEL WITH THE EAVE AND FASTENED
 SUFFICIENTLY TO STAY IN PLACE.
 2) STARTING AT THE EAVE, 36-INCH-WIDE
 STRIPS OF UNDERLAYMENT FELT SHALL BE
 APPLIED OVER LAPPING SUCCESSIVE SHEETS
 19 INCHES AND FASTENED SUFFICIENTLY TO
 STAY IN PLACE. (PLEASE SHOW ROOF SLOPE)
  
 4) IS THE STRUCTURE OF THE HOUSE MADE
 OF WOOD OR CONCRETE BLOCK? PLEASE
 PROVIDE THIS INFORMATION SO WE CAN BE
 SURE THE BEAMS ARE ATTATCH TO CODE.
  
 5) PLEASE INDICATE THE SPACING OF THE
 3/8" BOLTS ON THE DRAWINGS.
  
 6) WPB AMENDEMENTS SEC.104.2.1
 DRAWINGS AND INFORMATION SHALL BE
 SPECIFIC. ALL INFORMATION,DRAWINGS,
 SPECIFICATIONSAND ACCOMPANYING DATA SHAL
 L BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. ALSO
 SEE SEC.104.2.1.3
  
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-24 Time 11:10 Rev Time 1.00
Received By alange Date 2004-08-12 Time 14:24 Sent To  
Notes
2004-08-12 00:00:00DENIED
  
 1.SUBMIT 2 COPIES OF PRODUCT
 APPROVALSFOR STRAPS AND TIE-DOWNS USED
 AND
 FOR ROOFING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.SUBMIT A NAILING SCHEDULE FOR
 ROOF SHEATHING. SHOW SIZE OF NAIL USED
 AND SPACING.
  
 3.SHOW TIE IN DETAIL FOR ROOF LEDGER.
  
 4.SHOW RAILING, INCLUDE HEIGHT AND
 SPACING OF BALISTERS.
  
 5.BUILDING VALUATION TOO LOW.
 REVISE VALUE TO REFLECT CURRENT VALUE OF
 PROJECT.REQUIRED BEFORE A PERMIT
 WILL BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 11:10 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 11:10 Sent To B
Notes
2004-08-24 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 17:20 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 17:20 Sent To B
Notes
2004-08-11 00:00:00TO RES BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-09 Cont ID  
Sent By mmclean Date 2004-08-10 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 11:30 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-08-09 Time 11:30 Rev Time 0.00
Received By mmclean Date 2004-08-10 Time 14:52 Sent To I
Notes
2004-08-10 00:00:00APPROVED BY JOHN ROACH, PLANNER 822-1448
 VARIANCE WAS APPROVEE MM